Lighting And Illumination

Lumens, footcandles, lux, fixture count, lighting load, emergency lighting, and lighting energy calculators.

Sub-topics in this category

The 24 calculators in Lighting And Illumination grouped into 17 sub-topics by the work each is built for. A calculator appears under every sub-topic it serves, so these groups overlap where the same page answers more than one question.

Lighting Load

Lighting load and connected lighting power workflows.

Engineering Estimate

Formula-backed estimates that require professional verification before final use.

Field Layout

Field layout calculations and measurement workflow support.

Energy Cost

Energy-use, rate, and operating-cost calculations.

Control System

Control-system and signal-loop calculations.

Savings Screen

Preliminary energy-savings and payback screens.

Backup Power

Generator and backup-power planning workflows.

Battery Storage

Battery energy, runtime, and capacity estimation workflows.

Capacity Margin

Capacity, margin, and preliminary headroom screens.

Line Current

Line-current and phase-model arithmetic workflows.

Commercial Load

Commercial and industrial connected-load workflows.

Demand Factor

Explicit demand-factor inputs and load-accounting workflows.

Field Verification

Measured field data reduction and verification workflows.

Load Accounting

Transparent connected-load and worksheet accounting workflows.

Simple Payback

Testing and Measurement

Measured test data, instrument readings, and field measurement calculations.

Voltage Drop

Voltage-drop and conductor-length calculation workflows.

What this topic covers

About this category

24 calculators are grouped under Lighting And Illumination, and the work splits into Lighting Load, Engineering Estimate, Field Layout, Energy Cost. Every page states the formula it applies, the inputs and units it expects, and the limits of the estimate, so a result can be checked against the adopted code edition and the equipment nameplate before it is used for a design decision.

Written for Electricians, Engineers, Estimators, Facility Teams, and Technicians.

Basis cited across this topic: IEEE (4), NFPA 70 (NEC) (10), UL (2). Each calculator lists its own source citation and review dates on its page.

Formulas used in this category

The arithmetic the 24 calculators in Lighting And Illumination apply, in the order it is evaluated. These are calculation summaries, not code text — verify each against the source standard before design use. Full explanations for every topic are in the formula reference index.

Show formula sheet (24 calculators)
Daylight Factor Calculator
  • daylight factor ratio = indoor illuminance / outdoor illuminance
  • daylight factor percent = daylight factor ratio x 100
Dimming Energy Savings Calculator
  • baseline annual kWh = baseline watts x hours/day x days/year / 1000
  • dimmed annual kWh = baseline annual kWh x average power percent / 100
  • annual kWh saved = baseline annual kWh - dimmed annual kWh
  • annual cost saved = annual kWh saved x electricity rate
  • savings percent = annual kWh saved / baseline annual kWh x 100
Emergency Lighting Battery Calculator
  • \(\text{Load energy (Wh)} = \text{load watts} \times \text{runtime (h)}\)
  • \(\text{Usable factor} = \frac{\text{usable capacity (\%)}}{100} \times \frac{\text{efficiency (\%)}}{100}\)
  • \(\text{Base battery energy (Wh)} = \frac{\text{load energy (Wh)}}{\text{usable factor}}\)
  • \(\text{Required battery energy (Wh)} = \text{base battery energy} \times \left(1 + \frac{\text{reserve (\%)}}{100}\right)\)
  • \(\text{Required battery capacity (Ah)} = \frac{\text{required battery energy (Wh)}}{\text{battery voltage}}\)
Emergency Lighting Duration Calculator
  • efficiency factor = conversion efficiency percent / 100
  • reserve factor = 1 - reserve percent / 100
  • available energy Wh = usable battery energy Wh x efficiency factor x reserve factor
  • estimated duration hours = available energy Wh / emergency load W
Exit Sign Load Calculator
  • total sign load W = watts per sign x sign count
  • emergency energy Wh = total sign load W x emergency duration hours
Fixture Count Calculator
  • effective lumens per fixture = fixture lumens x coefficient of utilization x light-loss factor
  • unrounded count = target footcandles x area / effective lumens per fixture
  • required count = ceiling(unrounded count)
Fixture Spacing Calculator
  • room area = room length x room width
  • maximum spacing = mounting height x spacing criterion
  • columns = ceiling(room length / maximum spacing)
  • rows = ceiling(room width / maximum spacing)
  • fixture count = columns x rows
Footcandle Calculator
  • \(\text{Effective lumens} = \text{Lumens} \times \mathrm{CU} \times \mathrm{LLF}\)
  • \(\text{Footcandles} = \frac{\text{Effective lumens}}{\text{Area}}\)
  • \(\text{Lux} = \text{Footcandles} \times 10.76390625\)
LED Driver Load Calculator
  • \(\text{Total driver watts} = \text{driver watts} \times \text{driver quantity}\)
  • \(\text{Total driver VA} = \frac{\text{total driver watts}}{\text{power factor}}\)
  • \(\text{Adjusted driver VA} = \text{total driver VA} \times \frac{\text{continuous multiplier (\%)}}{100}\)
  • \(\text{Phase multiplier} = 1 \text{ for single-phase, } \sqrt{3} \text{ for balanced three-phase}\)
  • \(\text{Circuit current} = \frac{\text{adjusted driver VA}}{\text{phase multiplier} \times \text{voltage}}\)
LED Retrofit Payback Calculator
  • existing annual kWh = existing watts x fixture count x hours/day x days/year / 1000
  • LED annual kWh = LED watts x fixture count x hours/day x days/year / 1000
  • annual kWh saved = existing annual kWh - LED annual kWh
  • annual cost saved = annual kWh saved x electricity rate
  • simple payback years = project cost / annual cost saved
Light Loss Factor Calculator
  • combined light loss factor = lamp lumen factor x dirt factor x equipment factor x other factor
  • maintained lumens = initial lumens x combined light loss factor
  • lumen loss percent = (1 - combined light loss factor) x 100
Lighting Circuit Load Calculator
  • \(\text{Total fixture watts} = \text{fixture watts} \times \text{fixture count}\)
  • \(\text{Adjusted circuit VA} = \text{total fixture watts} \times \frac{\text{continuous multiplier (\%)}}{100}\)
  • \(\text{Phase multiplier} = 1 \text{ for single-phase, } \sqrt{3} \text{ for balanced three-phase}\)
  • \(\text{Circuit current} = \frac{\text{adjusted circuit VA}}{\text{phase multiplier} \times \text{voltage}}\)
  • \(\text{Adjusted VA per fixture} = \text{fixture watts} \times \frac{\text{continuous multiplier (\%)}}{100}\)
  • \(\text{Maximum fixtures} = \left\lfloor\frac{\text{breaker (A)} \times \text{voltage} \times \text{phase multiplier}}{\text{adjusted VA per fixture}}\right\rfloor\)
Lighting Circuit Voltage Drop Calculator
  • one-way resistance = one-way length x conductor resistance / 1000
  • phase multiplier = 2 for single-phase two-conductor
  • sqrt(3) for balanced three-phase
  • voltage drop = phase multiplier x current x one-way resistance
  • voltage-drop percent = voltage drop / system voltage x 100
  • estimated end voltage = system voltage - voltage drop
Lighting Controls Savings Calculator
  • baseline annual kWh = baseline watts x hours/day x days/year / 1000
  • controlled annual kWh = controlled watts x hours/day x days/year / 1000
  • annual kWh saved = baseline annual kWh - controlled annual kWh
  • annual cost saved = annual kWh saved x electricity rate
  • savings percent = annual kWh saved / baseline annual kWh x 100
Lighting Energy Savings Calculator
  • \(\text{Existing annual energy (kWh)} = \frac{\text{existing watts} \times \text{fixture count} \times \text{hours/day} \times \text{days/year}}{1000}\)
  • \(\text{Replacement annual energy (kWh)} = \frac{\text{replacement watts} \times \text{fixture count} \times \text{hours/day} \times \text{days/year}}{1000}\)
  • \(\text{Annual energy saved} = \text{existing annual energy} - \text{replacement annual energy}\)
  • \(\text{Annual cost saved} = \text{annual energy saved} \times \text{electricity rate}\)
  • \(\text{Simple payback (years)} = \frac{\text{project cost}}{\text{annual cost saved}}\quad\text{when annual cost saved} > 0\)
Lighting Layout Calculator
  • \(\text{Room area (ft}^2\text{)} = \text{room length} \times \text{room width}\)
  • \(\text{Room area (m}^2\text{)} = \text{room area (ft}^2\text{)} \times 0.09290304\)
  • \(\text{Spacing limit} = \text{mounting height} \times \text{spacing criterion}\)
  • \(\text{Columns} = \left\lceil\frac{\text{room length}}{\text{spacing limit}}\right\rceil\)
  • \(\text{Rows} = \left\lceil\frac{\text{room width}}{\text{spacing limit}}\right\rceil\)
  • \(\text{Fixture count} = \text{columns} \times \text{rows}\)
Lighting Power Density Calculator
  • \(\mathrm{LPD}_{\mathrm{ft^2}} = \frac{P_{\mathrm{lighting}}}{A_{\mathrm{served}}}\)
  • \(\mathrm{LPD}_{\mathrm{m^2}} = \mathrm{LPD}_{\mathrm{ft^2}}\times 10.7639104167\)
Lighting Uniformity Calculator
  • min-to-average ratio = minimum illuminance / average illuminance
  • average-to-min ratio = average illuminance / minimum illuminance
  • max-to-min ratio = maximum illuminance / minimum illuminance
  • uniformity percent = minimum illuminance / average illuminance x 100
Lumen Calculator
  • \(\displaystyle \text{Required lumens} = \frac{\text{Area} \times \text{Target illuminance (fc)}}{\text{CU} \times \text{LLF}}\)
  • \(\displaystyle \text{Fixture count} = \begin{cases}\left\lceil \frac{\text{Required lumens}}{\text{Lumens per fixture}} \right\rceil,&\text{fixture lumens}>0\\0,&\text{fixture lumens}=0\end{cases}\)
  • \(\displaystyle \text{Target illuminance (lux)} = \text{Target illuminance (fc)} \times 10.76390625\)
Mounting Height Calculator
  • mounting height above workplane = luminaire mounting height - workplane height
  • maximum spacing = mounting height above workplane x spacing-to-mounting-height ratio
  • estimated rows = ceiling(room length / maximum spacing)
  • actual row spacing = room length / estimated rows
Occupancy Sensor Savings Calculator
  • baseline annual kWh = lighting watts x baseline hours/day x days/year / 1000
  • sensor-case annual kWh = lighting watts x reduced hours/day x days/year / 1000
  • annual kWh saved = baseline annual kWh - sensor-case annual kWh
  • annual cost saved = annual kWh saved x electricity rate
Photocell Load Calculator
  • total load W = connected watts per unit x fixture or load count
  • annual energy kWh = total load W x duty hours/day x operating days/year / 1000
  • annual cost = annual energy kWh x electricity rate
Room Footcandles Calculator
  • \(\text{Effective lumens}=\text{Total lumens}\times\text{CU}\times\text{LLF}\)
  • \(\text{Footcandles}=\text{Effective lumens}/\text{Area in square feet}\)
  • \(\text{Lux}=\text{Footcandles}\times10.76390625\)
Task Lighting Load Calculator
  • \(\text{Connected watts} = \text{Fixture watts} \times \text{Fixture count}\)
  • \(\text{Active watts} = \text{Connected watts} \times \frac{\text{Active-use percent}}{100}\)
  • \(\text{Annual energy (kWh)} = \frac{\text{Active watts} \times \text{Hours per day} \times \text{Days per year}}{1000}\)
  • \(\text{Annual cost} = \text{Annual energy (kWh)} \times \text{Electricity rate}\)

Review basis

Lighting workflows are planning estimates. Confirm photometric files, fixture spacing, controls, emergency lighting, energy code, and project criteria before design decisions.

Everything under Lighting And Illumination is a calculation from values you enter, not an approval. The pages here cite IEEE, NFPA 70 (NEC), and UL among their basis, so confirm the edition adopted in your jurisdiction against the source text before relying on a number for design or installation.

Where to go next: the formula reference, all calculators, or printable worksheets for the same calculations.