Testing, Protection And Grounding

Insulation resistance, short-circuit current, pull-box sizing, grounding, bonding, touch voltage, and protection checks.

Sub-topics in this category

Field Verification

Measured field data reduction and verification workflows.

Equipment Review

Equipment-data and nameplate review workflows.

Testing and Measurement

Measured test data, instrument readings, and field measurement calculations.

Fault Current

Preliminary fault-current and short-circuit contribution screens.

Instrumentation

Instrumentation and control-loop calculations.

Engineering Estimate

Formula-backed estimates that require professional verification before final use.

Grounding

Grounding and earth-electrode measurement workflows.

Control System

Control-system and signal-loop calculations.

Transformer Testing

Transformer test, impedance, and nameplate verification workflows.

Capacity Margin

Capacity, margin, and preliminary headroom screens.

Field Testing

Circuit Identification

Circuit and component relationship calculations.

Backup Power

Generator and backup-power planning workflows.

Field Layout

Field layout calculations and measurement workflow support.

Harmonics

Harmonic-current and power-quality screening workflows.

Load Accounting

Transparent connected-load and worksheet accounting workflows.

Motor Output

Motor and equipment output inputs used in load estimates.

Resistance

Voltage Drop

Voltage-drop and conductor-length calculation workflows.

Voltage Readings

Voltage measurements and voltage-ratio comparison workflows.

What this topic covers

About this category

66 calculators are grouped under Testing, Protection And Grounding, and the work splits into Field Verification, Equipment Review, Testing and Measurement, Fault Current. Every page states the formula it applies, the inputs and units it expects, and the limits of the estimate, so a result can be checked against the adopted code edition and the equipment nameplate before it is used for a design decision.

Written for Electricians, Engineers, Estimators, Facility Teams, Inspectors, and Technicians.

Basis cited across this topic: ANSI C57 (3), IEC (3), IEEE (9), IEEE 43 (4), NEMA MG-1 (2), NETA ATS (2). Each calculator lists its own source citation and review dates on its page.

Formulas used in this category

The arithmetic the 66 calculators in Testing, Protection And Grounding apply, in the order it is evaluated. These are calculation summaries, not code text — verify each against the source standard before design use. Full explanations for every topic are in the formula reference index.

Show formula sheet (66 calculators)
Approach Boundary Worksheet Calculator
  • \(d_{\mathrm{reference,in}} = \mathrm{convert}(d_{\mathrm{reference}})\)
  • \(d_{\mathrm{entered,in}} = \mathrm{convert}(d_{\mathrm{entered}})\)
  • \(\Delta d = d_{\mathrm{entered,in}} - d_{\mathrm{reference,in}}\)
  • \(\mathrm{Comparable} \iff \mathrm{method,\ qualification,\ and\ source\ are\ present}\)
Arc Flash Boundary Calculator
  • \(\Delta d = d_{\mathrm{entered}} - d_{\mathrm{reference}}\)
  • \(\lvert\Delta d\rvert = \left|d_{\mathrm{entered}} - d_{\mathrm{reference}}\right|\)
Arc Flash Input Data Completeness Calculator
  • \(N_{\mathrm{present}} = \mathrm{count}(\mathrm{status}=\mathrm{present})\)
  • \(N_{\mathrm{missing}} = \mathrm{count}(\mathrm{status}=\mathrm{missing})\)
  • \(\mathrm{Completeness} = \frac{N_{\mathrm{present}}}{N_{\mathrm{total}}} \times 100\%\)
  • \(N_{\mathrm{critical\ missing}} = \mathrm{count}(\mathrm{missing\ rows\ marked\ critical})\)
Arc Flash Study Scenario Comparison Calculator
  • \(\Delta = \left|A - B\right|\)
  • \(\mathrm{Percent\ difference} = \frac{\Delta}{\max(\lvert A\rvert,\lvert B\rvert)} \times 100\%\)
  • \(N_{\mathrm{known}} = \mathrm{count}(\mathrm{scenario\ values\ marked\ present})\)
  • \(\mathrm{Comparable} \iff \mathrm{basis\ and\ source\ records\ match}\)
Available Fault Current Calculator
  • \(I_{\mathrm{FL}} = \frac{\mathrm{Transformer\ kVA} \times 1000}{V_{\mathrm{secondary}} \times \mathrm{phase\ multiplier}}\)
  • \(I_{\mathrm{TF}} = \frac{I_{\mathrm{FL}}}{Z_{\%}/100}\)
  • \(I_{\mathrm{AFC}} = I_{\mathrm{TF}} \times \frac{\mathrm{source\ multiplier}_{\%}}{100}\)
  • \(\mathrm{rating\ margin} = I_{\mathrm{rating}} - I_{\mathrm{AFC}}\)
Breaker Interrupting Rating Calculator
  • \(M_{\mathrm{rating}} = I_{\mathrm{rating}} - I_{\mathrm{AFC}}\)
  • \(\mathrm{AFC\ percent} = \frac{I_{\mathrm{AFC}}}{I_{\mathrm{rating}}} \times 100\)
Breaker Size Calculator
  • \(I_{\mathrm{adjusted}} = I_{\mathrm{noncontinuous}} + I_{\mathrm{continuous}} \times \frac{F_{\mathrm{continuous}}}{100}\)
  • \(M_{\mathrm{rating}} = I_{\mathrm{selected}} - I_{\mathrm{adjusted}}\)
  • \(\mathrm{utilization} = \frac{I_{\mathrm{adjusted}}}{I_{\mathrm{selected}}} \times 100\)
Circuit Identification Calculator
  • \(\overline{V}_{\mathrm{LL}} = \frac{V_{AB} + V_{BC} + V_{CA}}{3}\)
  • \(\Delta V_{\max} = \max\left(\left|V_{AB}-V_{\mathrm{nom}}\right|,\left|V_{BC}-V_{\mathrm{nom}}\right|,\left|V_{CA}-V_{\mathrm{nom}}\right|\right)\)
  • \(\Delta V_{\%} = \frac{\Delta V_{\max}}{V_{\mathrm{nom}}} \times 100\)
  • \(\Delta V_{\%} \leq T_{\%} \Rightarrow \text{within the entered tolerance}\)
Conductor Short-Circuit Withstand Calculator
  • \(t_{\mathrm{withstand}} = \left(\frac{K \times A}{I}\right)^2\)
  • \(I^2t = I^2 \times t_{\mathrm{clearing}}\)
  • \(t_{\mathrm{margin}} = t_{\mathrm{withstand}} - t_{\mathrm{clearing}}\)
Continuity Test Calculator
  • \(\text{Corrected resistance} = \text{measured resistance} - \text{lead resistance}\)
  • \(\text{Threshold margin} = \text{reference threshold} - \text{corrected resistance}\)
  • \(\text{Within reference when corrected resistance} \leq \text{entered threshold}\)
CT Ratio Test Calculator
  • \(R_{\mathrm{expected}} = \frac{I_{\mathrm{nameplate,primary}}}{I_{\mathrm{nameplate,secondary}}}\)
  • \(R_{\mathrm{measured}} = \frac{I_{\mathrm{test,primary}}}{I_{\mathrm{test,secondary}}}\)
  • \(\Delta_{\mathrm{signed}} = \frac{R_{\mathrm{measured}} - R_{\mathrm{expected}}}{R_{\mathrm{expected}}} \times 100\%\)
  • \(\Delta_{\mathrm{absolute}} = \left|\Delta_{\mathrm{signed}}\right|\)
  • \(M_{\mathrm{reference}} = \Delta_{\mathrm{reference}} - \Delta_{\mathrm{absolute}}\quad\text{when a reference is entered}\)
Data Logger Interval Calculator
  • expected points = floor(duration seconds / interval seconds) + 1
  • maximum interval = duration seconds / (required points - 1)
  • storage bytes = expected points x channels x bytes per sample
Earth Electrode Test Calculator
  • \(R_{\mathrm{avg}} = \frac{\sum R_i}{n}\)
  • \(\Delta R = R_{\mathrm{max}} - R_{\mathrm{min}}\)
  • \(\Delta R_{\%} = \frac{\Delta R}{R_{\mathrm{avg}}}\times 100\%\)
  • \(R_{\mathrm{V/I}} = \frac{V_{\mathrm{test}}}{I_{\mathrm{test}}}\quad\text{when both are entered}\)
  • \(M_{\mathrm{reference}} = R_{\mathrm{reference}} - R_{\mathrm{avg}}\quad\text{when a reference is entered}\)
Electrical Inspection Checklist Calculator
  • passed items = count(rows with status pass)
  • failed items = count(rows with status fail)
  • completion percent = (passed items + not-applicable items) / total items x 100
  • required failure count = count(failed rows marked required)
Electrical Safe Work Distance Calculator
  • reference distance in = reference distance converted to inches
  • entered distance in = entered distance converted to inches
  • distance difference = entered distance in - reference distance in
  • distance comparison status = entered values comparable when the source record is present
Enclosure IP Rating Screen Calculator
  • IP code = IP + entered dust digit + entered water digit
  • dust digit margin = entered dust digit - required dust digit
  • water digit margin = entered water digit - required water digit
  • rating comparison = meets entered screen when both margins are zero or greater
Equipment Short Circuit Rating Calculator
  • rating margin = entered rating - available fault current
  • fault current percent of SCCR = available fault current / entered rating x 100
Extension Cord Voltage Drop Calculator
  • total circuit length = one-way length x 2
  • circuit resistance = total circuit length / 1000 x conductor resistance per 1000 ft
  • voltage drop = load current x circuit resistance
  • voltage drop percent = voltage drop / system voltage x 100
Fault Loop Impedance Calculator
  • measured impedance = test voltage / measured fault current
  • corrected impedance = max(measured impedance - lead impedance, 0)
Fuse Coordination Screen Calculator
  • required upstream time = downstream clearing time x (1 + minimum margin percent / 100)
  • actual time margin = upstream clearing time - downstream clearing time
  • actual margin percent = actual time margin / downstream clearing time x 100
  • coordination comparison = meets entered screen when upstream time is at least required upstream time
Fuse Size Calculator
  • entered reference fuse current = load current x entered fuse factor / 100
  • rating margin = selected fuse rating - entered reference fuse current
  • rating margin percent = rating margin / entered reference fuse current x 100
Generator Backfeed Safety Calculator
  • present controls = count(rows with control status present)
  • missing controls = count(rows with control status missing)
  • control completeness = present controls / total controls x 100
  • topology status = entered complete only when missing, unknown, and duplicate counts are zero
GFCI Trip Time Calculator
  • trip time margin = entered reference limit - measured trip time
  • trip time percent of limit = measured trip time / entered reference limit x 100
Ground Fault Current Calculator
  • prospective fault current = fault voltage / loop impedance
  • factored current = prospective current x factor / 100
Ground Grid Resistance Calculator
  • grid area = grid length x grid width
  • base grid resistance = soil resistivity / (4 x square root of grid area)
  • estimated grid resistance = base grid resistance / parallel paths
  • grid aspect ratio = maximum(length / width, width / length)
Ground Rod Spacing Calculator
  • spacing to rod length ratio = entered spacing / entered rod length
  • entered spacing margin = entered spacing - entered target spacing
Grounding Bond Test Calculator
  • loop resistance = measured voltage drop / test current
  • corrected bond resistance = loop resistance - lead resistance
  • reference margin = entered reference resistance - corrected bond resistance
Grounding Conductor Continuity Calculator
  • corrected resistance = measured resistance - lead resistance
  • threshold margin = reference threshold - corrected resistance
  • within reference when corrected resistance is no greater than the entered threshold
Grounding Resistance Calculator
  • \(\text{Rod length (m)} = \text{Rod length (ft)} \times 0.3048\)
  • \(\text{Rod diameter (m)} = \text{Rod diameter (in)} \times 0.0254\)
  • \(R_{\text{single}} = \frac{\rho}{2\pi L}\left[\ln\left(\frac{8L}{d}\right)-1\right]\)
  • \(\text{Spacing ratio} = \frac{\text{Rod spacing}}{\text{Rod length}}\)
  • \(S_{\text{eff}} = \min\left(1,\max\left(0,\text{Spacing ratio}\right)\right)\)
  • \(\text{Effective rod count} = 1 + (\text{Rod count} - 1)S_{\text{eff}}\)
Instrument Transformer Burden Calculator
  • burden voltage V = secondary current A x burden resistance ohm
  • burden VA = secondary current A squared x burden resistance ohm
Polarization Index Calculator
  • \(\mathrm{PI} = \frac{R_{10\mathrm{min}}}{R_{1\mathrm{min}}}\)
  • \(M_{\mathrm{reference}} = \mathrm{PI} - \mathrm{PI}_{\mathrm{reference}}\)
Insulation Resistance Calculator
  • \(R_{\text{corrected}} = R_{\text{measured}} \times K_T\)
  • \(R_{\text{reference}} = \text{entered screening reference}\)
  • \(M_{\text{screening}} = R_{\text{corrected}} - R_{\text{reference}}\)
  • \(\rho_{\text{screening}} = \frac{R_{\text{corrected}}}{R_{\text{reference}}}\)
  • \(\text{Screening status} = R_{\text{corrected}}\text{ compared with }R_{\text{reference}}\)
  • corrected resistance = measured resistance x temperature correction factor
Insulation Test Duration Calculator
  • duration margin = elapsed duration - target duration
  • completion percent = elapsed duration / target duration x 100
  • remaining time = max(target duration - elapsed duration, 0)
  • planned readings = floor(target seconds / reading interval seconds) + 1
Insulation Test Trend Calculator
  • resistance ratio = ending resistance / starting resistance
  • change = ending resistance - starting resistance
  • change rate = change / elapsed minutes
Insulation Test Voltage Calculator
  • test-to-rated ratio = entered test voltage / equipment rated voltage
  • low margin = entered test voltage - entered minimum test voltage
  • high margin = entered maximum test voltage - entered test voltage
  • window width = entered maximum test voltage - entered minimum test voltage
Leakage Current Screen Calculator
  • leakage margin = entered leakage reference - measured leakage current
  • leakage percent of load = measured leakage current / load current x 100
  • status = within reference when measured leakage current is less than or equal to the entered reference
Limited Approach Boundary Calculator
  • reference distance in = recorded reference distance converted to inches
  • entered distance in = entered distance converted to inches
  • distance difference = entered distance in - reference distance in
  • mode status = entered values comparable when the source record is complete
Lockout Tagout Sequence Calculator
  • complete steps = count(rows with step status complete)
  • missing steps = count(rows with step status missing)
  • order errors = count(rows whose step order differs from row position)
  • sequence status = entered complete only when missing, unknown, order, and duplicate counts are zero
Measurement Uncertainty Calculator
  • combined uncertainty = sqrt(A squared + B squared + C squared)
  • relative uncertainty percent = combined uncertainty / nominal value x 100
Megohm Test Trend Calculator
  • change = latest resistance - initial resistance
  • percent change = change / initial resistance x 100
  • drop percent = max(0, initial resistance - latest resistance) / initial resistance x 100
  • drop margin = entered allowed drop percent - drop percent
Meter Burden Voltage Calculator
  • burden voltage V = current A x input resistance ohm
  • burden power W = current A squared x input resistance ohm
Motor Winding Resistance Imbalance Calculator
  • \(R_{\mathrm{avg}} = \frac{R_A + R_B + R_C}{3}\)
  • \(\Delta R_{\mathrm{max}} = \max(|R_A - R_{\mathrm{avg}}|, |R_B - R_{\mathrm{avg}}|, |R_C - R_{\mathrm{avg}}|)\)
  • \(\mathrm{Imbalance}\% = \frac{\Delta R_{\mathrm{max}}}{R_{\mathrm{avg}}} \times 100\)
  • \(\mathrm{Margin}\% = \mathrm{Reference}\% - \mathrm{Imbalance}\%\)
Oscilloscope Bandwidth Calculator
  • required bandwidth = signal frequency x bandwidth multiplier
  • bandwidth margin = available bandwidth - required bandwidth
  • estimated scope rise time ns = 350 / available bandwidth MHz
Oscilloscope Timebase Calculator
  • time window seconds = seconds per division x horizontal divisions
  • period seconds = time window seconds / cycles in window
  • frequency hertz = 1 / period seconds
Phase Sequence Check Calculator
  • relative B angle = normalize(B angle - A angle)
  • relative C angle = normalize(C angle - A angle)
  • observed sequence = ABC when relative B angle is less than relative C angle, otherwise ACB
  • phase spacing error = minimum target-spacing error / 2
Polarity Test Calculator
  • voltage magnitude = abs(signed measured voltage)
  • actual polarity = sign of signed measured voltage
  • magnitude margin = voltage magnitude - entered minimum expected magnitude
Power Analyzer Sampling Calculator
  • highest frequency = fundamental frequency x highest harmonic order
  • Nyquist minimum sample rate = 2 x highest frequency
  • sampling margin ratio = sample rate / Nyquist minimum sample rate
PPE Category Screen Calculator
  • \(\text{Entered rating margin}=\text{entered arc rating}-\text{entered incident energy}\)
  • \(\text{Comparable record}=\text{method}+\text{unit basis}+\text{source reference}\)
  • \(\text{Source status}=\text{recorded when the source reference is present}\)
Protective Device Clearing Time Calculator
  • \(\text{Clearing-time margin}=t_{\mathrm{limit}}-t_{\mathrm{measured}}\)
  • \(\text{Clearing-time ratio}=\frac{t_{\mathrm{measured}}}{t_{\mathrm{limit}}}\)
Protective Relay Pickup Calculator
  • \(I_{\mathrm{pickup,primary}}=I_{\mathrm{pickup,secondary}}\times\frac{I_{\mathrm{CT,primary}}}{I_{\mathrm{CT,secondary}}}\)
  • \(\text{Pickup margin}=I_{\mathrm{fault}}-I_{\mathrm{pickup,primary}}\)
  • \(\text{Fault-to-pickup ratio}=\frac{I_{\mathrm{fault}}}{I_{\mathrm{pickup,primary}}}\)
Protective Relay Time Calculator
  • \(M=\frac{I_{\mathrm{fault}}}{I_{\mathrm{pickup}}}\)
  • \(t=\frac{\mathrm{TD}\times K}{M^n-1}\)
  • \(\text{Time margin}=t_{\mathrm{limit}}-t\)
PT Ratio Calculator
  • \(R_{\mathrm{measured}}=\frac{V_{\mathrm{primary}}}{V_{\mathrm{secondary}}}\)
  • \(\text{Ratio error}_{\%}=\frac{R_{\mathrm{measured}}-R_{\mathrm{nominal}}}{R_{\mathrm{nominal}}}\times100\)
Pull Box Sizing Calculator
  • \(\text{Straight-pull reference} = 8D\)
  • \(\text{Angle or U pull reference} = 6D + S_{\text{same-wall}}\)
  • \(\text{Controlling reference} = \max(\text{straight reference}, \text{angle/U reference})\)
  • straight-pull reference = 8 x largest raceway size
  • angle or U pull reference = 6 x largest raceway size + same-wall raceway sum
  • controlling screening reference = straight reference for straight pulls
Resistance Measurement Error Calculator
  • \(\text{Signed error}=\text{Measured resistance}-\text{Reference resistance}\)
  • \(\text{Absolute error}=\left|\text{Measured resistance}-\text{Reference resistance}\right|\)
  • \(\text{Signed error percent}=\text{Signed error}/\text{Reference resistance}\times100\)
  • \(\text{Absolute error percent}=\left|\text{Signed error percent}\right|\)
Restricted Approach Boundary Calculator
  • \(\text{Reference distance in}=\text{Recorded reference distance converted to inches}\)
  • \(\text{Entered distance in}=\text{Entered distance converted to inches}\)
  • \(\text{Distance difference}=\text{Entered distance in}-\text{Reference distance in}\)
SCCR Calculator
  • \(\text{SCCR margin}=\text{Component SCCR}-\text{Available fault current}\)
  • \(\text{Available fault current percent}=\text{Available fault current}/\text{Component SCCR}\times100\)
Shock Risk Screen Calculator
  • \(\text{Recorded factors}=\text{Count of rows marked recorded}\)
  • \(\text{Missing factors}=\text{Count of rows marked missing}\)
  • \(\text{Unknown factors}=\text{Count of rows marked unknown}\)
  • \(\text{Required missing factors}=\text{Count of required rows marked missing}\)
  • \(\text{Factor completeness}=\text{Recorded factors}/\text{Total factors}\times100\%\)
  • \(\text{Review note is complete only when missing and unknown counts are zero}\)
Short-Circuit Current Calculator
  • \(I_{\text{AFC}} = \frac{V}{Z}\)
  • \(I_{\text{adjusted}} = I_{\text{AFC}} \times M\)
  • \(I_{\text{AFC,kA}} = \frac{I_{\text{AFC}}}{1000}\)
  • \(I_{\text{adjusted,kA}} = \frac{I_{\text{adjusted}}}{1000}\)
  • \(\%Z_{100\text{ A}} = \frac{100\text{ A} \times Z}{V} \times 100\)
  • available fault current = source voltage / total impedance
Step And Touch Voltage Screen Calculator
  • \(\text{Grid potential rise} = \text{Fault current} \times \text{Grid resistance}\)
  • \(\text{Step voltage} = \text{Grid potential rise} \times \frac{\text{Step fraction}}{100}\)
  • \(\text{Touch voltage} = \text{Grid potential rise} \times \frac{\text{Touch fraction}}{100}\)
  • \(\text{Margin} = \text{Entered limit} - \text{Screened voltage}\)
Test Lead Correction Calculator
  • \(\text{Corrected resistance} = \text{Measured resistance} - \text{Lead resistance}\)
  • \(\text{Reference margin} = \text{Reference threshold} - \text{Corrected resistance}\)
  • \(\text{Lead share percent} = \frac{\text{Lead resistance}}{\text{Measured resistance}} \times 100\)
Thermal Scan Temperature Difference Calculator
  • \(\text{Ambient rise} = \text{Measured component temperature} - \text{Ambient temperature}\)
  • \(\text{Reference delta} = \text{Measured component temperature} - \text{Reference component temperature}\)
  • \(\text{Absolute reference delta} = \left|\text{Reference delta}\right|\)
  • \(\text{Threshold margin} = \text{Entered review threshold} - \text{Absolute reference delta}\)
Touch Voltage Safety Screen Calculator
  • \(\text{Touch voltage} = \text{Fault current} \times \text{Grid resistance} \times \frac{\text{Touch fraction}}{100}\)
  • \(\text{Entered comparison margin} = \text{Entered comparison value} - \text{Touch voltage}\)
Transformer Turns-Ratio Test Calculator
  • \(R_{\mathrm{expected}} = \frac{V_{\mathrm{primary,\ expected}}}{V_{\mathrm{secondary,\ expected}}}\)
  • \(R_{\mathrm{measured}} = \frac{V_{\mathrm{primary,\ measured}}}{V_{\mathrm{secondary,\ measured}}}\)
  • \(\mathrm{Deviation} = \frac{R_{\mathrm{measured}} - R_{\mathrm{expected}}}{R_{\mathrm{expected}}} \times 100\%\)
  • \(\mathrm{Reference\ margin} = \mathrm{entered\ reference} - |\mathrm{deviation}|\)
Transformer Winding Resistance Temperature Calculator
  • \(\Delta T = T_{\mathrm{reference}} - T_{\mathrm{measured}}\)
  • \(R_{\mathrm{reference}} = R_{\mathrm{measured}} \times (1 + \alpha \Delta T)\)
  • \(\mathrm{Resistance\ ratio} = \frac{R_{\mathrm{reference}}}{R_{\mathrm{measured}}}\)
  • \(\mathrm{Comparison\ difference} = R_{\mathrm{reference}} - R_{\mathrm{comparison}}\)
Voltage Presence Check Calculator
  • \(\lvert V_{\mathrm{measured}}\rvert = \operatorname{abs}(V_{\mathrm{measured}})\)
  • \(\text{Threshold margin} = V_{\mathrm{threshold}} - \lvert V_{\mathrm{measured}}\rvert\)
  • \(\text{Percent of nominal} = \frac{\lvert V_{\mathrm{measured}}\rvert}{V_{\mathrm{nominal}}}\times 100\)
Three-Phase Voltage Unbalance Calculator
  • \(V_{\mathrm{avg}} = \frac{V_{AB} + V_{BC} + V_{CA}}{3}\)
  • \(\mathrm{Maximum\ deviation} = \max\left(|V_{AB}-V_{\mathrm{avg}}|, |V_{BC}-V_{\mathrm{avg}}|, |V_{CA}-V_{\mathrm{avg}}|\right)\)
  • \(\mathrm{Voltage\ unbalance} = \frac{\mathrm{maximum\ deviation}}{V_{\mathrm{avg}}} \times 100\%\)
  • \(\mathrm{Reference\ margin} = \mathrm{entered\ reference} - \mathrm{calculated\ unbalance}\)

Review basis

Testing and protection workflows require calibrated instruments, site conditions, and adopted standard verification.

Everything under Testing, Protection And Grounding is a calculation from values you enter, not an approval. The pages here cite ANSI C57, IEC, and IEEE among their basis, so confirm the edition adopted in your jurisdiction against the source text before relying on a number for design or installation.

Where to go next: the formula reference, all calculators, or printable worksheets for the same calculations.