Leakage Current Screen Calculator
Compare entered leakage current with a documented reference and express it as a share of entered load current without embedding a safety limit.
- Leakage margin
- mA
- Leakage percent of load
- %
- Reference comparison
- Load current used
- A
Calculation details
- Calculation basis
- Testing boundary
Recent results
Formulas
- leakage margin = entered leakage reference - measured leakage current
- leakage percent of load = measured leakage current / load current x 100
- status = within reference when measured leakage current is less than or equal to the entered reference
The Leakage Current Screen Calculator compares an entered Measured leakage current against an entered Reference leakage current. It produces the remaining Leakage margin, identifies whether the measured value is within that entered reference, and expresses leakage current as a percentage of the entered Load current.
This calculation supports maintenance records, troubleshooting documentation, commissioning worksheets, and comparison testing where a procedure, prior measurement, or equipment record supplies the reference value. It does not establish an acceptable leakage-current limit; the reference is entered by the user.
The calculator uses these fields:
| Field | Electrical use |
|---|---|
| Measured leakage current | Leakage current measured during the applicable test, entered in mA |
| Reference leakage current | Comparison value from the applicable procedure or documented reference, entered in mA |
| Load current | Circuit or equipment load current used to express leakage as a percentage, entered in A |
Leakage Margin and Reference Comparison
Leakage margin is the numerical difference between the entered reference leakage current and the measured leakage current:
\(\displaystyle \text{leakage margin} = \text{entered leakage reference} - \text{measured leakage current}\)
A positive margin means the measured leakage current is below the entered reference. A zero margin means the measured value equals the reference. A negative margin indicates that the measured leakage current exceeds the entered reference.
The calculator determines Reference comparison as follows:
\(\displaystyle \text{within reference when measured leakage current} \leq \text{entered reference leakage current}\)
The status is a comparison result, not a determination of equipment safety, shock risk, product compliance, or suitability for energization.
Leakage Percent of Load
The Leakage percent of load places the measured leakage current in relation to the entered load current:
\(\displaystyle \text{leakage percent of load} = \frac{\text{measured leakage current}} {\text{load current}} \times 100\)
Both values must be expressed in the same current unit before division. Because Measured leakage current is entered in mA and Load current is entered in A, convert milliamperes to amperes for the percentage calculation:
\(\displaystyle 2.4\text{ mA} = 0.0024\text{ A}\)
This percentage is context for the recorded operating load. It is not an ampacity calculation, branch-circuit loading calculation, feeder sizing result, voltage-drop result, or conductor-sizing determination.
Calculation Example
Enter the following values:
| Input | Entered value |
|---|---|
| Measured leakage current | 2.4 mA |
| Reference leakage current | 3.5 mA |
| Load current | 12 A |
The leakage margin is:
\(\displaystyle 3.5\text{ mA} - 2.4\text{ mA} = 1.1\text{ mA}\)
The leakage percentage of load is:
\(\displaystyle \frac{0.0024\text{ A}}{12\text{ A}} \times 100 = 0.02\%\)
The resulting worksheet output is:
| Result | Value |
|---|---|
| Leakage margin | 1.1 mA |
| Leakage percent of load | 0.02% |
| Reference comparison | Within entered reference |
| Load current used | 12 A |
Test Boundary and Field Verification
The worksheet performs arithmetic only: it compares the entered measurement to the entered reference and calculates the percentage relationship to load current. It does not provide a safety approval, product-compliance conclusion, shock-risk result, or energization decision.
Field decisions require the applicable test method, equipment documentation, maintenance procedure, measurement conditions, instrument suitability, and any requirements enforced by the AHJ or other governing authority. A measured leakage value can be meaningfully compared only when the reference and test conditions are appropriate to the equipment and procedure being documented.
FAQs
Does this define a leakage-current limit?
No. You enter the comparison value. Applicable product standards, procedures, and qualified review determine limits.
Why show leakage as a percent of load?
The percentage is context only. It does not replace a leakage-current test method or safety criterion.