Wire, Raceway And Ampacity
Wire sizing, ampacity derating, conduit fill, cable tray fill, voltage drop, and raceway checks.
Sub-topics in this category
The 38 calculators in Wire, Raceway And Ampacity grouped into 14 sub-topics by the work each is built for. A calculator appears under every sub-topic it serves, so these groups overlap where the same page answers more than one question.
Engineering Estimate
Formula-backed estimates that require professional verification before final use.
-
Ampacity Calculator
Estimate adjusted conductor ampacity.
-
AWG Wire Resistance Calculator
Calculate AWG conductor resistance from wire size material length and temperature.
-
Cable Jacket Diameter Calculator
Calculate cable outside diameter from conductor diameter and entered concentric layer thicknesses.
-
Cable Pull Bend Count Calculator
Calculate cable pull bend count and total bend angle from entered route rows.
-
Cable Tray Fill Calculator
Compare entered cable areas with an entered usable tray area.
-
Cable Tray Separation Calculator
Calculate cable tray width needed for entered cable group widths and separations.
-
Cable Tray Width Calculator
Calculate cable tray width from entered cable envelope, spacing, fill, edge clearance, and selected tray width.
-
Conductor Ampacity Correction Factor Calculator
Apply entered ampacity correction factors to an entered base ampacity.
-
Conductor Current Density Calculator
Calculate conductor current density from current and cross-sectional area.
-
Conductor Resistance Calculator
Calculate conductor resistance from resistivity length and cross-sectional area.
-
Conductor Resistance Temperature Calculator
Adjust conductor resistance for operating temperature using a user-supplied coefficient.
-
Conductor Temperature Rise Calculator
Check conductor temperature rise from entered current and ampacity assumptions.
-
Conductor Weight Calculator
Estimate conductor or cable material weight from verified unit weight and run quantities.
-
Conduit Expansion Movement Calculator
Estimate thermal movement in a long conduit run from entered material and temperature assumptions.
-
Conduit Trade Size Calculator
Screen a conduit trade size from entered conductor area.
-
DC Voltage Drop Calculator
Calculate DC voltage drop as a mode of the voltage-drop workflow.
-
Electrical Duct Bank Concrete Volume Calculator
Estimate concrete quantity from entered electrical duct-bank geometry.
-
Medium Voltage Cable Drop Calculator
Estimate voltage drop and power loss over a medium or high voltage cable run.
-
Raceway Fill Area Calculator
Compare entered raceway inside area with an entered fill percentage and reserved area.
-
Raceway Size Calculator
Compare entered conductor area with an entered raceway area and fill limit.
-
Voltage Drop Calculator
Calculate voltage drop from current length voltage and conductor size or resistance.
-
Voltage Drop Length Calculator
Calculate maximum one-way length from an entered voltage-drop limit.
-
Wire Pull Length Calculator
Evaluate wire pull length for an early planning or field-review decision.
-
Wire Pulling Tension Calculator
Estimate wire pulling tension and sidewall pressure.
Raceway Layout
Conduit, duct-bank, and raceway geometry workflows.
-
Box Fill Calculator
Compare entered box volume allowances without selecting a code table value.
-
Cable Bend Radius Calculator
Estimate minimum cable bend radius from outside diameter and multiplier.
-
Cable Jacket Diameter Calculator
Calculate cable outside diameter from conductor diameter and entered concentric layer thicknesses.
-
Cable Pull Bend Count Calculator
Calculate cable pull bend count and total bend angle from entered route rows.
-
Cable Tray Fill Calculator
Compare entered cable areas with an entered usable tray area.
-
Cable Tray Separation Calculator
Calculate cable tray width needed for entered cable group widths and separations.
-
Cable Tray Width Calculator
Calculate cable tray width from entered cable envelope, spacing, fill, edge clearance, and selected tray width.
-
Conductor Weight Calculator
Estimate conductor or cable material weight from verified unit weight and run quantities.
-
Conduit Body Fill Calculator
Screen conduit body fill against entered area and capacity values.
-
Conduit Expansion Movement Calculator
Estimate thermal movement in a long conduit run from entered material and temperature assumptions.
-
Conduit Support Spacing Calculator
Screen conduit support intervals and support-point count from an entered rule basis.
-
Conduit Trade Size Calculator
Screen a conduit trade size from entered conductor area.
-
Electrical Duct Bank Concrete Volume Calculator
Estimate concrete quantity from entered electrical duct-bank geometry.
-
Parallel Raceway Ampacity Calculator
Screen entered load current against entered ampacity for parallel raceways.
-
Raceway Fill Area Calculator
Compare entered raceway inside area with an entered fill percentage and reserved area.
-
Raceway Size Calculator
Compare entered conductor area with an entered raceway area and fill limit.
-
Voltage Drop Length Calculator
Calculate maximum one-way length from an entered voltage-drop limit.
-
Wire and Cable Takeoff Calculator
Estimate conductor and cable quantities from an entered run schedule.
-
Wire Pull Length Calculator
Evaluate wire pull length for an early planning or field-review decision.
-
Wire Pulling Tension Calculator
Estimate wire pulling tension and sidewall pressure.
-
Wireway Fill Calculator
Estimate wireway or gutter fill from verified internal area and conductor or cable rows.
Equipment Review
Equipment-data and nameplate review workflows.
-
AWG Wire Resistance Calculator
Calculate AWG conductor resistance from wire size material length and temperature.
-
Cable Bend Radius Calculator
Estimate minimum cable bend radius from outside diameter and multiplier.
-
Conductor Ampacity Correction Factor Calculator
Apply entered ampacity correction factors to an entered base ampacity.
-
Conductor Current Density Calculator
Calculate conductor current density from current and cross-sectional area.
-
Conductor Temperature Rise Calculator
Check conductor temperature rise from entered current and ampacity assumptions.
-
Conduit Body Fill Calculator
Screen conduit body fill against entered area and capacity values.
-
Conduit Trade Size Calculator
Screen a conduit trade size from entered conductor area.
-
Equipment Grounding Conductor Size Calculator
Compare entered equipment grounding conductor areas from a reviewed source.
-
Grounding Electrode Conductor Size Calculator
Compare entered grounding electrode conductor areas from a reviewed source.
-
Parallel Conductor Calculator
Compare current per parallel conductor set with entered ampacity.
-
Parallel Raceway Ampacity Calculator
Screen entered load current against entered ampacity for parallel raceways.
-
Raceway Fill Area Calculator
Compare entered raceway inside area with an entered fill percentage and reserved area.
-
Raceway Size Calculator
Compare entered conductor area with an entered raceway area and fill limit.
-
Terminal Temperature Limit Check Calculator
Screen entered load current against entered terminal ampacity assumptions.
Field Layout
Field layout calculations and measurement workflow support.
-
Box Fill Calculator
Compare entered box volume allowances without selecting a code table value.
-
Cable Bend Radius Calculator
Estimate minimum cable bend radius from outside diameter and multiplier.
-
Cable Jacket Diameter Calculator
Calculate cable outside diameter from conductor diameter and entered concentric layer thicknesses.
-
Cable Pull Bend Count Calculator
Calculate cable pull bend count and total bend angle from entered route rows.
-
Cable Tray Fill Calculator
Compare entered cable areas with an entered usable tray area.
-
Cable Tray Separation Calculator
Calculate cable tray width needed for entered cable group widths and separations.
-
Cable Tray Width Calculator
Calculate cable tray width from entered cable envelope, spacing, fill, edge clearance, and selected tray width.
-
Conduit Expansion Movement Calculator
Estimate thermal movement in a long conduit run from entered material and temperature assumptions.
-
Conduit Support Spacing Calculator
Screen conduit support intervals and support-point count from an entered rule basis.
-
Wire and Cable Takeoff Calculator
Estimate conductor and cable quantities from an entered run schedule.
-
Wire Pull Length Calculator
Evaluate wire pull length for an early planning or field-review decision.
-
Wire Pulling Tension Calculator
Estimate wire pulling tension and sidewall pressure.
-
Wireway Fill Calculator
Estimate wireway or gutter fill from verified internal area and conductor or cable rows.
Capacity Margin
Capacity, margin, and preliminary headroom screens.
-
Box Fill Calculator
Compare entered box volume allowances without selecting a code table value.
-
Cable Tray Fill Calculator
Compare entered cable areas with an entered usable tray area.
-
Cable Tray Width Calculator
Calculate cable tray width from entered cable envelope, spacing, fill, edge clearance, and selected tray width.
-
Conductor Ampacity Correction Factor Calculator
Apply entered ampacity correction factors to an entered base ampacity.
-
Conductor Temperature Rise Calculator
Check conductor temperature rise from entered current and ampacity assumptions.
-
Conduit Body Fill Calculator
Screen conduit body fill against entered area and capacity values.
-
Parallel Conductor Calculator
Compare current per parallel conductor set with entered ampacity.
-
Wireway Fill Calculator
Estimate wireway or gutter fill from verified internal area and conductor or cable rows.
Line Current
Line-current and phase-model arithmetic workflows.
-
Conductor Ampacity Correction Factor Calculator
Apply entered ampacity correction factors to an entered base ampacity.
-
Conductor Current Density Calculator
Calculate conductor current density from current and cross-sectional area.
-
Conductor Temperature Rise Calculator
Check conductor temperature rise from entered current and ampacity assumptions.
-
DC Voltage Drop Calculator
Calculate DC voltage drop as a mode of the voltage-drop workflow.
-
Medium Voltage Cable Drop Calculator
Estimate voltage drop and power loss over a medium or high voltage cable run.
-
Parallel Conductor Calculator
Compare current per parallel conductor set with entered ampacity.
-
Voltage Drop Calculator
Calculate voltage drop from current length voltage and conductor size or resistance.
Field Verification
Measured field data reduction and verification workflows.
-
Conductor Ampacity Correction Factor Calculator
Apply entered ampacity correction factors to an entered base ampacity.
-
Conductor Temperature Rise Calculator
Check conductor temperature rise from entered current and ampacity assumptions.
-
Equipment Grounding Conductor Size Calculator
Compare entered equipment grounding conductor areas from a reviewed source.
-
Grounding Electrode Conductor Size Calculator
Compare entered grounding electrode conductor areas from a reviewed source.
-
Terminal Temperature Limit Check Calculator
Screen entered load current against entered terminal ampacity assumptions.
Voltage Drop
Voltage-drop and conductor-length calculation workflows.
-
AWG Wire Resistance Calculator
Calculate AWG conductor resistance from wire size material length and temperature.
-
DC Voltage Drop Calculator
Calculate DC voltage drop as a mode of the voltage-drop workflow.
-
Medium Voltage Cable Drop Calculator
Estimate voltage drop and power loss over a medium or high voltage cable run.
-
Voltage Drop Calculator
Calculate voltage drop from current length voltage and conductor size or resistance.
-
Voltage Drop Length Calculator
Calculate maximum one-way length from an entered voltage-drop limit.
Load Accounting
Transparent connected-load and worksheet accounting workflows.
-
Parallel Raceway Ampacity Calculator
Screen entered load current against entered ampacity for parallel raceways.
-
Terminal Temperature Limit Check Calculator
Screen entered load current against entered terminal ampacity assumptions.
-
Wire and Cable Takeoff Calculator
Estimate conductor and cable quantities from an entered run schedule.
Conductor Resistance
-
Conductor Resistance Calculator
Calculate conductor resistance from resistivity length and cross-sectional area.
-
Conductor Resistance Temperature Calculator
Adjust conductor resistance for operating temperature using a user-supplied coefficient.
Grounding
Grounding and earth-electrode measurement workflows.
-
Equipment Grounding Conductor Size Calculator
Compare entered equipment grounding conductor areas from a reviewed source.
-
Grounding Electrode Conductor Size Calculator
Compare entered grounding electrode conductor areas from a reviewed source.
Cable Envelope
-
Conductor Weight Calculator
Estimate conductor or cable material weight from verified unit weight and run quantities.
Concrete Encased
Concrete-encased conduit and duct-bank quantity workflows.
-
Electrical Duct Bank Concrete Volume Calculator
Estimate concrete quantity from entered electrical duct-bank geometry.
Temperature Effects
-
Conductor Resistance Temperature Calculator
Adjust conductor resistance for operating temperature using a user-supplied coefficient.
What this topic covers
About this category
38 calculators are grouped under Wire, Raceway And Ampacity, and the work splits into Engineering Estimate, Raceway Layout, Equipment Review, Field Layout. Every page states the formula it applies, the inputs and units it expects, and the limits of the estimate, so a result can be checked against the adopted code edition and the equipment nameplate before it is used for a design decision.
Written for Electricians, Engineers, Estimators, Facility Teams, Inspectors, and Technicians.
Formulas used in this category
The arithmetic the 38 calculators in Wire, Raceway And Ampacity apply, in the order it is evaluated. These are calculation summaries, not code text — verify each against the source standard before design use. Full explanations for every topic are in the formula reference index.
Show formula sheet (38 calculators)
- Ampacity Calculator
-
- \(I_{\mathrm{adjusted}} = I_{\mathrm{base}} \times F_{\mathrm{adjustment}} \times F_{\mathrm{temperature}}\)
- \(F_{\mathrm{combined}} = F_{\mathrm{adjustment}} \times F_{\mathrm{temperature}}\)
- \(\mathrm{Total\ factor\ percent} = F_{\mathrm{adjustment}} \times F_{\mathrm{temperature}} \times 100\%\)
- \(\mathrm{Conductor\ count} \ge 4 \Rightarrow \mathrm{review\ flag\ only}\)
- \(\mathrm{No\ conductor\ size\ or\ code-compliant\ final\ selection\ is\ made}\)
- conductor count is a review flag only
- AWG Wire Resistance Calculator
-
- \(K=\text{material resistance constant},\quad \alpha=\text{temperature coefficient},\quad \Delta T=T-20^\circ\mathrm{C}\)
- \(L=\text{one-way conductor length},\quad N=\text{conductors included in the resistance path}\)
- \(d_{\text{in}} = 0.005 \times 92^{(36-\mathrm{AWG})/39}\)
- \(d_{\text{mil}} = 1000 \times d_{\text{in}}\)
- \(\mathrm{CM} = d_{\text{mil}}^2\)
- \(R_{20} = \frac{K \times 1000}{\mathrm{CM}}\)
- Box Fill Calculator
-
- \(V_{\mathrm{conductors}} = N_{\mathrm{conductors}} \times V_{\mathrm{allowance}}\)
- \(V_{\mathrm{fill}} = V_{\mathrm{conductors}} + V_{\mathrm{device}} + V_{\mathrm{clamp}} + V_{\mathrm{grounding}}\)
- \(V_{\mathrm{remaining}} = V_{\mathrm{box}} - V_{\mathrm{fill}}\)
- \(\mathrm{fill\ percent} = \frac{V_{\mathrm{fill}}}{V_{\mathrm{box}}} \times 100\)
- Cable Bend Radius Calculator
-
- \(D_{\text{cable}}=\text{cable outside diameter},\quad M_{\text{bend}}=\text{bend-radius multiplier},\quad \theta=\text{bend angle}\)
- \(R_{\min} = D_{\text{cable}} \times M_{\text{bend}}\)
- \(D_{\text{bend}} = 2 \times R_{\min}\)
- \(L_{\text{arc}} = R_{\min} \times \frac{\theta}{360} \times 2\pi\)
- Cable Jacket Diameter Calculator
-
- \(t_{\mathrm{layer}} = t_{\mathrm{insulation}} + t_{\mathrm{shield/tape}} + t_{\mathrm{jacket}}\)
- \(D_{\mathrm{nominal}} = D_{\mathrm{conductor}} + 2t_{\mathrm{layer}}\)
- \(D_{\mathrm{planning}} = D_{\mathrm{nominal}} \times \left(1 + \frac{T_{\%}}{100}\right)\)
- \(A = \pi\left(\frac{D}{2}\right)^2\)
- Cable Pull Bend Count Calculator
-
- \(\theta_{\mathrm{row}} = \theta_{\mathrm{bend}} \times N_{\mathrm{bend}}\)
- \(\theta_{\mathrm{total}} = \sum \theta_{\mathrm{row}}\)
- \(\theta_{\mathrm{remaining}} = \theta_{\mathrm{limit}} - \theta_{\mathrm{total}}\)
- Cable Tray Fill Calculator
-
- \(A_{\mathrm{occupied}} = \sum\left(A_{\mathrm{cable}} \times N_{\mathrm{cable}}\right)\)
- \(\mathrm{fill\ percent} = \frac{A_{\mathrm{occupied}}}{A_{\mathrm{tray}}} \times 100\)
- \(A_{\mathrm{limit}} = A_{\mathrm{tray}} \times \frac{L_{\%}}{100}\)
- \(M_{\mathrm{fill}} = A_{\mathrm{limit}} - A_{\mathrm{occupied}}\)
- Cable Tray Separation Calculator
-
- \(S_{\mathrm{total}} = (N_{\mathrm{groups}} - 1) \times S_{\mathrm{minimum}}\)
- \(W_{\mathrm{required}} = N_{\mathrm{groups}} \times W_{\mathrm{group}} + S_{\mathrm{total}} + 2C_{\mathrm{edge}}\)
- \(M_{\mathrm{tray}} = W_{\mathrm{usable}} - W_{\mathrm{required}}\)
- Cable Tray Width Calculator
-
- \(W_{\mathrm{planned}} = W_{\mathrm{cable}}\left(1 + \frac{S_{\mathrm{allowance}}}{100}\right)\)
- \(W_{\mathrm{usable}} = \frac{W_{\mathrm{planned}}}{F_{\mathrm{usable}}/100}\)
- \(W_{\mathrm{minimum}} = W_{\mathrm{usable}} + 2E_{\mathrm{edge}}\)
- \(M_{\mathrm{width}} = W_{\mathrm{selected}} - W_{\mathrm{minimum}}\)
- Conductor Ampacity Correction Factor Calculator
-
- \(F_{\mathrm{total}} = F_{\mathrm{ambient}} \times F_{\mathrm{conductor-count}}\)
- \(I_{\mathrm{adjusted}} = I_{\mathrm{base}} \times F_{\mathrm{total}}\)
- \(M_I = I_{\mathrm{adjusted}} - I_{\mathrm{load}}\)
- \(U_{\%} = \frac{I_{\mathrm{load}}}{I_{\mathrm{adjusted}}} \times 100\)
- Conductor Current Density Calculator
-
- \(J_{\mathrm{A/mm^2}} = \frac{I}{A}\)
- \(J_{\mathrm{A/cm^2}} = 100J_{\mathrm{A/mm^2}}\)
- Conductor Resistance Calculator
-
- \(R = \rho\frac{L}{A}\)
- \(G = \frac{1}{R}\quad\text{when }R>0\)
- Conductor Resistance Temperature Calculator
-
- \(\Delta T = T_2 - T_1\)
- \(R_2 = R_1 \left[1 + \alpha(T_2 - T_1)\right]\)
- \(\text{Resistance change (\%)} = \left(\frac{R_2}{R_1} - 1\right) \times 100\%\)
- Conductor Temperature Rise Calculator
-
- \(r = \frac{I}{I_{\mathrm{reference}}}\)
- \(\Delta T_{\mathrm{allowable}} = T_{\mathrm{rating}} - T_{\mathrm{ambient}}\)
- \(\Delta T_{\mathrm{estimated}} = \Delta T_{\mathrm{allowable}} \times r^2\)
- \(T_{\mathrm{operating}} = T_{\mathrm{ambient}} + \Delta T_{\mathrm{estimated}}\)
- Conductor Weight Calculator
-
- \(w_{\mathrm{ft}} = \frac{w_{\mathrm{1000ft}}}{1000}\)
- \(W_{\mathrm{row}} = w_{\mathrm{ft}}Lqr\)
- \(W_{\mathrm{waste}} = W_{\mathrm{net}}\frac{w_{\%}}{100}\)
- \(W_{\mathrm{planning}} = W_{\mathrm{net}} + W_{\mathrm{waste}}\)
- \(W_{\mathrm{gross}} = W_{\mathrm{planning}} + W_{\mathrm{tare}}\)
- Conduit Body Fill Calculator
-
- \(\text{Total conductor area} = \text{area per conductor} \times \text{conductor count}\)
- \(\text{Required area} = \text{total conductor area} + \text{splice/device allowance}\)
- \(\text{Fill percent} = \frac{\text{required area}}{\text{conduit body capacity}} \times 100\%\)
- \(\text{Spare area} = \text{conduit body capacity} - \text{required area}\)
- Conduit Expansion Movement Calculator
-
- \(\Delta T = T_{\mathrm{operating}} - T_{\mathrm{installation}}\)
- \(\Delta L = \alpha L\Delta T\)
- \(n_{\mathrm{fitting}} = \left\lceil\frac{|\Delta L|}{m_{\mathrm{fitting}}}\right\rceil\)
- \(\overline{m} = \frac{|\Delta L|}{n_{\mathrm{fitting}}}\quad\text{when }n_{\mathrm{fitting}}>0\)
- Conduit Fill Calculator
-
- total conductor area = conductor area per conductor x conductor count
- fill ratio percent = total conductor area / raceway internal area x 100
- remaining raceway area = raceway internal area - total conductor area
- 40% screening area limit = raceway internal area x 0.40 when conductor count >= 3
- 40% screening margin = 40% screening area limit - total conductor area
- passes 40% screening estimate = fill ratio percent <= 40 when conductor count >= 3
- Conduit Support Spacing Calculator
-
- \(L_{\mathrm{span}} = \max(L_{\mathrm{run}} - L_{\mathrm{end}}, 0)\)
- \(n_{\mathrm{intermediate}} = \left\lceil\frac{L_{\mathrm{span}}}{s_{\max}}\right\rceil\)
- \(n_{\mathrm{total}} = n_{\mathrm{end}} + n_{\mathrm{intermediate}} + n_{\mathrm{fitting}}\)
- \(L_{\mathrm{last}} = L_{\mathrm{span}} - (n_{\mathrm{intermediate}}-1)s_{\max}\quad\text{when }L_{\mathrm{span}}>0\)
- Conduit Trade Size Calculator
-
- total conductor area = conductor count x area per conductor
- conduit internal area = pi x (inside diameter / 2)^2
- fill percent = total conductor area / conduit internal area x 100
- required inside diameter = 2 x sqrt(total conductor area / (fill limit / 100) / pi)
- fill margin = entered fill limit - calculated fill percent
- DC Voltage Drop Calculator
-
- voltage drop = 2 x current x one-way length x resistance per 1000 ft / 1000
- voltage drop percent = voltage drop / system voltage x 100
- entered margin = entered drop limit percent - voltage drop percent
- Electrical Duct Bank Concrete Volume Calculator
-
- \(W_{\mathrm{gross}} = n_{\mathrm{row}}d + (n_{\mathrm{row}} - 1)s_h + 2c\)
- \(H_{\mathrm{gross}} = n_{\mathrm{rows}}d + (n_{\mathrm{rows}} - 1)s_v + 2c\)
- \(V_{\mathrm{envelope}} = \frac{W_{\mathrm{gross}}H_{\mathrm{gross}}L}{1728}\)
- \(V_{\mathrm{void}} = \frac{\pi\left(d/2\right)^2n_{\mathrm{total}}L}{1728}\)
- \(V_{\mathrm{concrete}} = V_{\mathrm{envelope}} - V_{\mathrm{void}}\)
- \(V_{\mathrm{order}} = V_{\mathrm{concrete}}\left(1 + \frac{w}{100}\right)\)
- Equipment Grounding Conductor Size Calculator
-
- area margin = selected area - entered required area
- area margin percent = area margin / entered required area x 100
- source status = source reference is present
- Grounding Electrode Conductor Size Calculator
-
- area margin = selected area - entered required area
- area margin percent = area margin / entered required area x 100
- source status = source reference is present
- Medium Voltage Cable Drop Calculator
-
- \(Z_{\mathrm{proj}} = R\cos\phi + X\sin\phi\)
- \(V_{\mathrm{drop}} = k \times I \times L_{\mathrm{used}} \times \frac{Z_{\mathrm{proj}}}{1000}\)
- \(V_{\mathrm{far}} = V_{\mathrm{system}} - V_{\mathrm{drop}}\)
- \(\mathrm{Drop\ percent} = \frac{V_{\mathrm{drop}}}{V_{\mathrm{system}}} \times 100\%\)
- \(P_{\mathrm{loss}} = n \times I^{2} \times R \times \frac{L_{\mathrm{used}}}{1000}\)
- Parallel Conductor Calculator
-
- \(\displaystyle I_{\text{ideal,set}}=\frac{I_{\text{total}}}{N_{\text{sets}}}\)
- \(\displaystyle I_{\text{highest,set}}=I_{\text{ideal,set}}\left(1+\frac{\text{Mismatch (\%)}}{100}\right)\)
- \(\displaystyle I_{\text{ampacity,total}}=N_{\text{sets}}\times I_{\text{ampacity,set}}\)
- \(\displaystyle M_{\text{highest,set}}=I_{\text{ampacity,set}}-I_{\text{highest,set}}\)
- Parallel Raceway Ampacity Calculator
-
- current per raceway = total load current / parallel raceway count
- adjusted ampacity per raceway = entered ampacity per raceway x adjustment factor
- total adjusted ampacity = adjusted ampacity per raceway x parallel raceway count
- ampacity margin = total adjusted ampacity - total load current
- Raceway Fill Area Calculator
-
- \(A_{\mathrm{allowable}}=A_{\mathrm{raceway}}\times\frac{\text{fill percent}}{100}\)
- \(A_{\mathrm{available}}=A_{\mathrm{allowable}}-A_{\mathrm{reserved}}\)
- \(\text{Reserved share}_{\%}=\frac{A_{\mathrm{reserved}}}{A_{\mathrm{allowable}}}\times100\)
- Raceway Size Calculator
-
- \(A_{\mathrm{required}}=\frac{A_{\mathrm{conductors}}}{\text{fill limit}/100}\)
- \(A_{\mathrm{margin}}=A_{\mathrm{selected}}-A_{\mathrm{required}}\)
- \(\text{Fill at selected area}_{\%}=\frac{A_{\mathrm{conductors}}}{A_{\mathrm{selected}}}\times100\)
- Terminal Temperature Limit Check Calculator
-
- \(\text{Continuous current} = \text{Load current} \times \frac{\text{Continuous load share}}{100}\)
- \(\text{Required ampacity} = \text{Noncontinuous current} + \text{Continuous current} \times \frac{\text{Continuous-load multiplier}}{100}\)
- \(\text{Required ampacity with spare} = \text{Required ampacity} \times \left(1 + \frac{\text{Spare margin}}{100}\right)\)
- \(\text{Terminal margin} = \text{Entered terminal ampacity} - \text{Required ampacity with spare}\)
- Voltage Drop Calculator
-
- \(m = 2\text{ for single-phase or DC two-wire}
- \ \sqrt{3}\text{ for balanced three-phase}\)
- \(R_{op} = R_{75} \times [1 + \alpha(T_{op} - 75)]\)
- \(Z_{eff} = R_{op} \times PF + X \times \sin(\cos^{-1} PF)\)
- \(\Delta V = \frac{m \times I \times L \times Z_{eff}}{1000}\)
- \(\Delta V_{\%} = \frac{\Delta V}{V_{\text{system}}} \times 100\%\)
- Voltage Drop Length Calculator
-
- \(V_{\mathrm{allowable}} = V_{\mathrm{system}}\times \frac{p_{\mathrm{drop}}}{100}\)
- \(L_{\mathrm{max,one-way}} = \frac{V_{\mathrm{allowable}}\times 1000}{k_{\mathrm{phase}} I R_{1000}}\)
- \(k_{\mathrm{phase}} = 2\text{ for single-phase or DC}
- \ \sqrt{3}\text{ for three-phase}\)
- Wire and Cable Takeoff Calculator
-
- \(\mathrm{Base\ row\ length} = \mathrm{route\ length} + \mathrm{drop\ allowance} + \mathrm{termination\ allowance}\)
- \(\mathrm{Row\ quantity} = \mathrm{base\ row\ length} \times \mathrm{conductor\ or\ cable\ quantity} \times \mathrm{parallel\ runs}\)
- \(\mathrm{Quantity\ before\ waste} = \sum \mathrm{row\ quantities}\)
- \(\mathrm{Waste\ allowance} = \mathrm{quantity\ before\ waste} \times \frac{\mathrm{waste\ percent}}{100}\)
- \(\mathrm{Recommended\ planning\ quantity} = \mathrm{quantity\ before\ waste} + \mathrm{waste\ allowance}\)
- Wire Derating Calculator
-
- \(F_{\mathrm{combined}} = F_{\mathrm{ambient}} \times F_{\mathrm{bundling}}\)
- \(A_{\mathrm{adjusted}} = A_{\mathrm{base}} \times F_{\mathrm{combined}}\)
- \(F_{\mathrm{combined,percent}} = F_{\mathrm{combined}} \times 100\)
- conductor count is a review flag only
- it does not automatically select a bundling factor
- final selection boundary = no code-compliant conductor or wire size selection is made by this calculator
- Wire Pull Length Calculator
-
- \(\text{Total straight length} = \sum \text{entered straight lengths}\)
- \(\text{Total bend allowance} = \sum \text{entered bend allowances}\)
- \(\text{Estimated pull length} = \text{Total straight length} + \text{Total bend allowance}\)
- Wire Pulling Tension Calculator
-
- \(W_{\mathrm{total}} = N \times w_{\mathrm{1000ft}} \times \frac{L_{\mathrm{ft}}}{1000}\)
- \(T_{\mathrm{friction}} = W_{\mathrm{total}} \times \mu\)
- \(T_{\mathrm{pull}} = T_{\mathrm{start}} + T_{\mathrm{friction}}\)
- \(r_{\mathrm{ft}} = \frac{r_{\mathrm{in}}}{12}\)
- \(P_{\mathrm{sidewall}} = \frac{T_{\mathrm{pull}}}{r_{\mathrm{ft}}}\)
- \(T_{\mathrm{per\ conductor}} = \frac{T_{\mathrm{pull}}}{N}\)
- Wire Size Calculator | Voltage-Drop Review
-
- \(\ell_{\mathrm{loop}} = \frac{2L_{\mathrm{one\text{-}way}}}{1000}\)
- \(\Delta V = I \times \ell_{\mathrm{loop}} \times R_{1000}\)
- \(\Delta V_{\mathrm{percent}} = \frac{\Delta V}{V_{\mathrm{system}}} \times 100\)
- \(\Delta V_{\mathrm{allowable}} = V_{\mathrm{system}} \times \frac{p_{\mathrm{allowable}}}{100}\)
- \(R_{\mathrm{max},1000} = \frac{\Delta V_{\mathrm{allowable}}}{I \times \ell_{\mathrm{loop}}}\)
- \(M_{\mathrm{pp}} = p_{\mathrm{allowable}} - \Delta V_{\mathrm{percent}}\)
- Wireway Fill Calculator
-
- \(\mathrm{Row\ occupied\ area} = \mathrm{area\ per\ conductor\ or\ cable} \times \mathrm{quantity}\)
- \(\mathrm{Occupied\ area} = \sum \mathrm{row\ occupied\ areas}\)
- \(\mathrm{Fill\ percentage} = \frac{\mathrm{occupied\ area}}{\mathrm{verified\ internal\ area}} \times 100\%\)
- \(\mathrm{Entered\ limit\ area} = \mathrm{verified\ internal\ area} \times \frac{\mathrm{entered\ fill\ limit}}{100}\)
- \(\mathrm{Fill\ margin} = \mathrm{entered\ limit\ area} - \mathrm{occupied\ area}\)
- \(\mathrm{Fill\ comparison}: \mathrm{compare\ fill\ percentage\ with\ the\ entered\ fill\ limit}\)
Review basis
Sizing workflows need code-edition, conductor, temperature, raceway, and local inspection verification.
Everything under Wire, Raceway And Ampacity is a calculation from values you enter, not an approval. The pages here cite BS 7671, IEC 60364, and IEEE among their basis, so confirm the edition adopted in your jurisdiction against the source text before relying on a number for design or installation.