Medium Voltage Cable Drop Calculator
Calculate voltage drop, receiving-end voltage, maximum route length at an entered limit, and I-squared-R loss on a medium or high voltage cable run from resistance, reactance, and power factor.
- Voltage drop
- V
- Voltage drop
- %
- Receiving-end voltage
- V
- Limit comparison
- Maximum one-way route at the limit
- m
- Conductor length used
- m
- Impedance used
- ohm/km
- Cable loss
- W
- Cable loss
- %
- System voltage
- V
- Phase multiplier
- x
Calculation details
- Cable basis
- Calculation basis
- Review boundary
Recent results
Engineering notes
Code basis, calculation assumptions, and field-verification limits behind this calculator's result.
- Cable basis
- Reactance is included, so the result follows the R cos(phi) + X sin(phi) projection. Entered conductor size is a label for the record only; every number here comes from the resistance and reactance you entered.
- Calculation basis
- Three-phase uses sqrt(3) and the one-way route per phase; single-phase uses 2 and twice the one-way length. Voltage drop equals that product times (R cos(phi) + X sin(phi)) per km, multiplied by the route and divided by 1000.
- Review boundary
- Arithmetic for voltage drop and I-squared-R loss only. Short-circuit withstand, thermal rating and dielectric losses, screen or earthing arrangement, installation method, and the edition adopted by the local authority remain outside this calculation.
Formulas
- \(Z_{\mathrm{proj}} = R\cos\phi + X\sin\phi\)
- \(V_{\mathrm{drop}} = k \times I \times L_{\mathrm{used}} \times \frac{Z_{\mathrm{proj}}}{1000}\)
- \(V_{\mathrm{far}} = V_{\mathrm{system}} - V_{\mathrm{drop}}\)
- \(\mathrm{Drop\ percent} = \frac{V_{\mathrm{drop}}}{V_{\mathrm{system}}} \times 100\%\)
- \(P_{\mathrm{loss}} = n \times I^{2} \times R \times \frac{L_{\mathrm{used}}}{1000}\)
What this estimate covers
This page covers the voltage a medium or high voltage cable run actually drops, and the loss it carries. It does not size the cable: enter the resistance and reactance from the manufacturer datasheet for the size, laying condition, and temperature you are checking.
Why R and X are entered rather than looked up
Medium voltage cable is specified in millimetres squared, not AWG, and its resistance and reactance depend on conductor material, screen arrangement, laying condition, and temperature. A built-in table would be wrong for most installations, so the inputs are the datasheet figures and the size field is a label for the record.
Worked example
Three-phase 11 kV at 100 A over 300 m with 0.443 ohm per km resistance, 0.08 ohm per km reactance, and 0.9 power factor gives a 22.53 V drop, which is 0.205 percent, leaves 10977.47 V at the far end, and allows about 7324 m of route at a 5 percent limit.
Review boundary
Short-circuit withstand, thermal rating, dielectric and screen losses, earthing arrangement, and installation method are outside this arithmetic. Sizing an MV feeder needs all of those together with the edition adopted by the local authority.
HV and MV cable voltage drop formula
For a balanced three-phase cable run, voltage drop is the line current multiplied by the route length and the effective impedance, with the √3 phase multiplier. The effective impedance uses the cable resistance and reactance at the operating power factor.
\(\displaystyle V_{\text{drop}} = \sqrt{3} \times I \times L \times (R\cos\phi + X\sin\phi)\)
The percentage drop divides that value by the nominal line voltage. The receiving-end voltage is the sending-end voltage minus the drop, and the loss is the current squared multiplied by the resistance over the route.
What to enter for R and X
Medium voltage and high voltage cable is usually specified in square millimetres, not AWG, and the resistance and reactance change with conductor material, screen arrangement, laying formation, spacing, and operating temperature. Use the manufacturer datasheet or the cable schedule for the actual cable, not a generic AWG table.
- Resistance R — the AC resistance at the operating temperature, in ohms per kilometre or ohms per 1,000 ft.
- Reactance X — the cable reactance for the installation arrangement, in the same length unit.
- Power factor — the load displacement power factor used in the R cos φ + X sin φ term.
- Route length — the one-way cable route, not the total conductor length.
HV cable size and voltage drop
A larger conductor reduces resistance and voltage drop, but it also changes capacitance, charging current, screen losses, and short-circuit withstand. Voltage drop is only one screen. Cable size still has to satisfy ampacity, thermal short-circuit withstand, installation method, and the local network operator’s requirements.
Common questions
Can this calculator size an HV cable?
No. It checks voltage drop and I²R loss for the R and X you enter. It does not select a cable size, insulation level, screen, or termination.
Why not use a built-in cable table?
Because MV and HV cable R and X depend on the actual cable construction and laying condition. A table would be wrong for most projects, so the datasheet values are entered directly.
Does charging current matter on long HV runs?
It can. This screen uses the entered load current and does not model cable charging current, so long runs need a fuller cable study.
Related cable calculators
- Medium voltage cable drop calculator — this page, for MV and HV cable voltage drop.
- Voltage drop calculator — low-voltage conductor voltage drop with NEC Table 8 resistance.
- Conductor resistance calculator — convert resistance to the length and temperature basis you need.
FAQs
Does this size the cable?
No. It calculates what a given cable does over a given route. Choosing the size needs short-circuit withstand, thermal rating, and installation method as well, then a check that the sized cable still meets the drop limit.
Where do I get resistance and reactance?
From the manufacturer datasheet for the actual size, conductor and screen arrangement, laying condition, and temperature. Medium voltage cable properties vary far more between products than low voltage ones, so a generic table would mislead.
What limit should I use?
Enter the limit your specification requires. Five percent is common for internal distribution, but the binding value comes from the design standard adopted for the installation and any utility requirement.
What is the size field for?
It records the conductor size on the result so you can include it in your own documentation. The calculation uses the resistance and reactance you entered, not the size.