Continuous Load Calculator
Use this continuous load workflow for transparent load arithmetic when the current, continuous portion, multiplier, voltage, phase, and available ampacity are already known.
- Continuous current
- A
- Noncontinuous current
- A
- Adjusted current
- A
- Connected load
- VA
- Adjusted load
- VA
- Entered ampacity margin
- A
Calculation details
- Capacity status
- Calculation basis
- Selection boundary
Recent results
Formulas
- Continuous current = load current x continuous percent / 100
- Noncontinuous current = load current - continuous current
- Adjusted current = noncontinuous current + continuous current x continuous multiplier / 100
- Adjusted VA = adjusted current x voltage x phase multiplier
- Ampacity margin = entered ampacity - adjusted current
A continuous load calculator determines the adjusted current created when a defined portion of an electrical load receives a continuous-load multiplier. The adjusted current is the load value used when reviewing conductor ampacity, branch-circuit or feeder loading, overcurrent-device selection, voltage-drop calculations, and related load documentation.
The calculation separates the entered load into its continuous and noncontinuous portions. It applies the Continuous multiplier only to the percentage identified in Continuous portion, then combines both portions into one adjusted current.
This prevents a common load-calculation error: applying the multiplier to the entire load when only part of the load is continuous.
Adjusted Current
Enter Load current as the actual operating current before any continuous-load treatment. Enter Continuous portion to identify what percentage of that current receives the Continuous multiplier.
The calculator returns:
| Result | Electrical meaning |
|---|---|
| Continuous current | The portion of Load current identified as continuous |
| Noncontinuous current | The remaining portion of Load current not multiplied |
| Adjusted current | Continuous current after the multiplier, plus noncontinuous current |
| Connected load | Apparent power represented by the original Load current |
| Adjusted load | Apparent power represented by the Adjusted current |
| Entered ampacity margin | Entered ampacity minus Adjusted current |
For conductor sizing, the Adjusted current is the key result. It is not automatically a final conductor ampacity selection. The selected conductor still has to be evaluated for its allowable ampacity after applicable terminal limitations, insulation temperature rating, ambient-temperature correction, current-carrying-conductor adjustment factors, and installation conditions.
Calculation Method
The calculator uses the following arithmetic:
\(\text{Continuous current} = \text{Load current} \times \left(\frac{\text{Continuous portion}}{100}\right)\)
\(\text{Noncontinuous current} = \text{Load current} - \text{Continuous current}\)
\(\text{Adjusted current} = \left(\text{Continuous current} \times \left(\frac{\text{Continuous multiplier}}{100}\right) \right) + \text{Noncontinuous current}\)
For apparent power, the calculator uses System voltage and the selected Phase:
\(\text{Single-phase VA} = V \times I\)
\(\text{Balanced three-phase VA} = \sqrt{3} \times V \times I\)
The calculator applies the applicable VA equation twice:
- Connected load uses Load current.
- Adjusted load uses Adjusted current.
If Entered ampacity is provided, the available margin is:
\(\text{Entered ampacity margin} = \text{Entered ampacity} - \text{Adjusted current}\)
A positive margin indicates that the entered ampacity exceeds the calculated adjusted current. A zero or negative margin indicates that the entered ampacity does not exceed it.
Calculation Example
For a single-phase load with the following values:
| Input | Value |
|---|---|
| Load current | 32 A |
| Continuous portion | 100% |
| Continuous multiplier | 125% |
| System voltage | 240 V |
| Phase | Single-phase |
| Entered ampacity | 50 A |
All 32 A is identified as continuous:
\(32\text{ A} \times 100\% = 32\text{ A continuous current}\)
There is no noncontinuous portion:
\(32\text{ A} - 32\text{ A} = 0\text{ A noncontinuous current}\)
Apply the 125% multiplier:
\(32\text{ A} \times 125\% = 40\text{ A adjusted current}\)
Calculate apparent power:
\(240\text{ V} \times 32\text{ A} = 7{,}680\text{ VA connected load}\)
\(240\text{ V} \times 40\text{ A} = 9{,}600\text{ VA adjusted load}\)
The entered ampacity margin is:
\(50\text{ A} - 40\text{ A} = 10\text{ A}\)
The resulting values are:
- Continuous current: 32 A
- Noncontinuous current: 0 A
- Adjusted current: 40 A
- Connected load: 7,680 VA
- Adjusted load: 9,600 VA
- Entered ampacity margin: 10 A
Conductor and Raceway Review
Use the adjusted current as a load input when evaluating a branch circuit or feeder. For example, it can be compared with the allowable ampacity of a proposed AWG or kcmil conductor after the installation-specific ampacity review is complete.
The same adjusted current can support related electrical calculations:
- Conductor ampacity comparison after applying the required correction factor and adjustment factor
- Feeder and branch-circuit load schedules
- Voltage-drop calculations using the actual conductor material, conductor size, circuit length, and load current
- Raceway-fill planning after conductor quantity and conductor sizes are selected
- Equipment loading review when the available ampacity is known
- Load comparison for single-phase or balanced three-phase systems
System voltage and Phase affect the VA results, not the adjusted-current arithmetic. A 32 A load with a 100% continuous portion and 125% multiplier produces 40 A adjusted current regardless of whether the VA conversion is single-phase or balanced three-phase.
Field Verification
The calculator performs transparent continuous-load arithmetic from the values entered. Final electrical design and installation decisions require separate verification of the actual load characteristics and applicable requirements.
Confirm the continuous portion from the equipment duty cycle and intended operation. Then verify the conductor’s allowable ampacity using the applicable conductor insulation temperature rating, terminal rating, ambient conditions, number of current-carrying conductors, raceway or cable installation method, and any required correction or adjustment factors.
For three-phase input, select Balanced three-phase only when the VA conversion is appropriate for a balanced line-to-line load. Unbalanced loads, nonlinear loading, neutral loading, motor starting conditions, and equipment-specific instructions require separate engineering or field evaluation. Coordinate the final conductor, overcurrent protection, disconnecting means, and equipment ratings with the adopted electrical code and the AHJ.
FAQs
Does this choose a breaker size?
No. It only applies an entered continuous-load multiplier to entered current. Breaker and conductor selection need separate code and equipment review.
Can the continuous portion be less than 100 percent?
Yes. Enter the portion of the load you want treated as continuous for this arithmetic screen.
What does entered ampacity mean?
It is a comparison value you provide. The calculator does not determine allowable ampacity from a table.