Commercial And Industrial Loads

Three-phase load balance, feeder load, panel schedules, kitchen loads, data-center loads, and industrial demand.

Sub-topics in this category

The 30 calculators in Commercial And Industrial Loads grouped into 18 sub-topics by the work each is built for. A calculator appears under every sub-topic it serves, so these groups overlap where the same page answers more than one question.

Commercial Load

Commercial and industrial connected-load workflows.

Line Current

Line-current and phase-model arithmetic workflows.

Load Accounting

Transparent connected-load and worksheet accounting workflows.

Demand Factor

Explicit demand-factor inputs and load-accounting workflows.

Capacity Margin

Capacity, margin, and preliminary headroom screens.

Engineering Estimate

Formula-backed estimates that require professional verification before final use.

Industrial Load

Industrial equipment inventory and connected-load workflows.

Equipment Review

Equipment-data and nameplate review workflows.

Motor Output

Motor and equipment output inputs used in load estimates.

Lighting Load

Lighting load and connected lighting power workflows.

Power Factor

Power-factor and apparent-power conversion workflows.

Connected Load

Field Verification

Measured field data reduction and verification workflows.

Backup Power

Generator and backup-power planning workflows.

Continuous Load

Harmonics

Harmonic-current and power-quality screening workflows.

Load Blocks

Voltage Drop

Voltage-drop and conductor-length calculation workflows.

What this topic covers

About this category

30 calculators are grouped under Commercial And Industrial Loads, and the work splits into Commercial Load, Line Current, Load Accounting, Demand Factor. Every page states the formula it applies, the inputs and units it expects, and the limits of the estimate, so a result can be checked against the adopted code edition and the equipment nameplate before it is used for a design decision.

Written for Electricians, Engineers, Estimators, Facility Teams, Inspectors, and Technicians.

Basis cited across this topic: IEEE (1), NFPA 70 (NEC) (19). Each calculator lists its own source citation and review dates on its page.

Formulas used in this category

The arithmetic the 30 calculators in Commercial And Industrial Loads apply, in the order it is evaluated. These are calculation summaries, not code text — verify each against the source standard before design use. Full explanations for every topic are in the formula reference index.

Show formula sheet (30 calculators)
Commercial Data Center Load Calculator
  • \(P_{\mathrm{IT}} = N_{\mathrm{rack}} \times P_{\mathrm{rack}} \times \frac{u}{100}\)
  • \(P_{\mathrm{facility}} = P_{\mathrm{IT}} \times \mathrm{PUE}\)
  • \(P_{\mathrm{UPS,in}} = \frac{P_{\mathrm{facility}}}{\eta_{\mathrm{UPS}}}\)
  • \(S_{\mathrm{facility}} = \frac{P_{\mathrm{facility}}}{\mathrm{PF}}\)
  • \(P_{\mathrm{growth}} = P_{\mathrm{facility}}\left(1+\frac{g}{100}\right)\)
Commercial Elevator Load Calculator
  • \(P_{\mathrm{input}} = \frac{P_{\mathrm{motor}}}{\eta/100}\)
  • \(S_{\mathrm{duty}} = \frac{P_{\mathrm{input}}}{\mathrm{PF}} \times \frac{D_{\%}}{100}\)
  • \(I_{\mathrm{duty}} = \frac{1000S_{\mathrm{duty}}}{k_{\mathrm{phase}}V}\)
Commercial Fan Load Calculator
  • \(P_{\mathrm{air,hp}} = Q_{\mathrm{CFM}} \times \Delta p_{\mathrm{in.w.g.}} \times 0.00015744 \times \frac{\rho}{0.075}\)
  • \(P_{\mathrm{shaft,hp}} = \frac{P_{\mathrm{air,hp}}}{\eta_{\mathrm{fan}}}\)
  • \(P_{\mathrm{input,hp}} = \frac{P_{\mathrm{shaft,hp}}}{\eta_{\mathrm{motor}}\eta_{\mathrm{drive}}}\)
  • \(P_{\mathrm{input,kW}} = 0.745699872P_{\mathrm{input,hp}}\)
  • \(I = \frac{1000P_{\mathrm{input,kW}}}{k_{\phi}V\mathrm{PF}}\)
Commercial Feeder Voltage Drop Calculator
  • \(R_{\mathrm{one-way}} = R_{1000\mathrm{ft}} \times \frac{L_{\mathrm{one-way}}}{1000}\)
  • \(\Delta V_{1\phi} = 2IR_{\mathrm{one-way}}\)
  • \(\Delta V_{3\phi} = \sqrt{3}IR_{\mathrm{one-way}}\)
  • \(\Delta V_{\%} = \frac{\Delta V}{V_{\mathrm{system}}} \times 100\)
  • \(k_{\mathrm{loss}} = 2\ \text{for single-phase}\)
  • \(k_{\mathrm{loss}} = 3\ \text{for balanced three-phase}\)
Commercial HVAC Load Calculator
  • \(I_{\mathrm{heater}} = \frac{1000P_{\mathrm{heater,kW}}}{k_{\phi}V}\)
  • \(I_{\mathrm{MCA,est}} = 1.25I_{\mathrm{largest}} + I_{\mathrm{other}} + I_{\mathrm{heater}}\)
  • \(I_{\mathrm{load}} = I_{\mathrm{largest}} + I_{\mathrm{other}} + I_{\mathrm{heater}}\)
  • \(S_{\mathrm{load}} = \frac{k_{\phi}VI_{\mathrm{load}}}{1000}\)
  • \(\text{No final MCA, MOCP, conductor, breaker, listing, or code result is selected.}\)
Commercial Kitchen Load Calculator
  • \(S_{\mathrm{factor}} = S_{\mathrm{connected}} \times f_{\mathrm{demand}}\)
  • \(S_{\mathrm{floor}} = S_{\mathrm{largest,1}} + S_{\mathrm{largest,2}}\)
  • \(S_{\mathrm{selected}} = \max(S_{\mathrm{factor}}, S_{\mathrm{floor}})\)
  • \(\text{No universal Table 220.56 factor or code-compliance result is selected.}\)
Commercial Lighting Demand Calculator
  • \(V\!A_{\mathrm{connected}} = \sum_i V\!A_i\)
  • \(D_i = \frac{V\!A_iF_{i,\%}}{100}\)
  • \(A_i = D_i\left(\frac{C_{i,\%}}{100}-1\right)\)
  • \(V\!A_{\mathrm{demand}} = \sum_i D_i\)
  • \(V\!A_{\mathrm{continuous}} = \sum_i A_i\)
  • \(V\!A_{\mathrm{adjusted}} = V\!A_{\mathrm{demand}} + V\!A_{\mathrm{continuous}}\)
Commercial Load Calculator
  • \(\text{Block demand VA} = \text{connected VA} \times \frac{\text{demand factor (\%)}}{100}\)
  • \(\text{Block continuous adder VA} = \text{block demand VA} \times \left(\frac{\text{continuous multiplier (\%)}}{100} - 1\right)\)
  • \(\text{Adjusted load VA} = \sum_i \text{block demand VA}_i + \sum_i \text{block continuous adder VA}_i\)
  • \(\text{Phase multiplier} = 1 \text{ for single-phase, } \sqrt{3} \text{ for balanced three-phase}\)
  • \(\text{Line current} = \frac{\text{adjusted load VA}}{\text{phase multiplier} \times \text{system voltage}}\)
  • \(\text{Effective demand (\%)} = \frac{\text{adjusted load VA}}{\text{connected load VA}} \times 100\)
Commercial Load Diversity Calculator
  • \(P_{\mathrm{connected}} = P_A + P_B + P_C + P_D\)
  • \(P_{\mathrm{diversified}} = P_{\mathrm{connected}} \times \frac{D_{\%}}{100}\)
  • \(P_{\mathrm{reduction}} = P_{\mathrm{connected}} - P_{\mathrm{diversified}}\)
  • \(M_{\mathrm{capacity}} = P_{\mathrm{capacity}} - P_{\mathrm{diversified}}\)
Commercial Neutral Diversity Calculator
  • \(I_{\mathrm{N,linear}} = \sqrt{I_A^2 + I_B^2 + I_C^2 - I_AI_B - I_BI_C - I_CI_A}\)
  • \(I_{\mathrm{N,diversified}} = I_{\mathrm{N,linear}} \times \frac{D_{\%}}{100}\)
  • \(I_{\mathrm{avg}} = \frac{I_A + I_B + I_C}{3}\)
  • \(\Delta I_{\max} = \max\left(\left|I_A-I_{\mathrm{avg}}\right|,\left|I_B-I_{\mathrm{avg}}\right|,\left|I_C-I_{\mathrm{avg}}\right|\right)\)
  • \(U_{\%} = \frac{\Delta I_{\max}}{I_{\mathrm{avg}}} \times 100\)
Commercial Office Load Calculator
  • \(V\!A_{\mathrm{connected}} = \sum_i V\!A_i\)
  • \(D_i = \frac{V\!A_iF_{i,\%}}{100}\)
  • \(A_i = D_i\left(\frac{C_{i,\%}}{100}-1\right)\)
  • \(V\!A_{\mathrm{demand}} = \sum_i D_i\)
  • \(V\!A_{\mathrm{continuous}} = \sum_i A_i\)
  • \(V\!A_{\mathrm{adjusted}} = V\!A_{\mathrm{demand}} + V\!A_{\mathrm{continuous}}\)
Commercial Panel Capacity Calculator
  • \(S_{1\phi} = I_{\mathrm{panel}}V\)
  • \(S_{3\phi} = I_{\mathrm{panel}}V\sqrt{3}\)
  • \(I_{\mathrm{load}} = \frac{V\!A_{\mathrm{connected}}}{Vk_{\mathrm{phase}}}\)
  • \(U_{\%} = \frac{V\!A_{\mathrm{connected}}}{S_{\mathrm{rated}}} \times 100\)
  • \(M_{\mathrm{capacity}} = S_{\mathrm{rated}} - V\!A_{\mathrm{connected}}\)
Commercial Phase Allocation Calculator
  • \(V\!A_{\mathrm{total}} = V\!A_A + V\!A_B + V\!A_C\)
  • \(V\!A_{\mathrm{avg}} = \frac{V\!A_{\mathrm{total}}}{3}\)
  • \(U_{\%} = \frac{\Delta V\!A_{\max}}{V\!A_{\mathrm{avg}}} \times 100\)
  • \(V\!A_{\mathrm{transfer}} = \frac{V\!A_{\max} - V\!A_{\min}}{2}\)
  • \(I_{\mathrm{phase}} = \frac{V\!A_{\mathrm{phase}}}{V}\)
Commercial Pump Load Calculator
  • \(P_{\mathrm{hydraulic,hp}} = \frac{Q_{\mathrm{GPM}}\times \mathrm{SG}\times H_{\mathrm{ft}}}{3960}\)
  • \(P_{\mathrm{shaft,hp}} = \frac{P_{\mathrm{hydraulic,hp}}}{\eta_{\mathrm{pump}}}\)
  • \(P_{\mathrm{input,hp}} = \frac{P_{\mathrm{shaft,hp}}}{\eta_{\mathrm{motor}}\eta_{\mathrm{drive}}}\)
  • \(P_{\mathrm{input,kW}} = 0.745699872P_{\mathrm{input,hp}}\)
  • \(I = \frac{1000P_{\mathrm{input,kW}}}{k_{\phi}V\mathrm{PF}}\)
Commercial Receptacle Demand Calculator
  • \(D_i = S_i \times \frac{F_{d,i}}{100}\)
  • \(A_i = D_i \times \left(\frac{F_{c,i}}{100} - 1\right)\)
  • \(S_{\mathrm{adjusted}} = \sum_i \left(D_i + A_i\right)\)
  • \(I = \frac{S_{\mathrm{adjusted}}}{V k_{\mathrm{phase}}}\)
Commercial Retail Load Calculator
  • \(D_i = S_i \times \frac{F_{d,i}}{100}\)
  • \(A_i = D_i \times \left(\frac{F_{c,i}}{100} - 1\right)\)
  • \(S_{\mathrm{adjusted}} = \sum_i \left(D_i + A_i\right)\)
  • \(I = \frac{S_{\mathrm{adjusted}}}{V k_{\mathrm{phase}}}\)
Commercial Tenant Load Calculator
  • \(P_{\mathrm{connected}} = P_{\mathrm{lighting}} + P_{\mathrm{receptacle}} + P_{\mathrm{HVAC}} + P_{\mathrm{process}} + P_{\mathrm{kitchen}}\)
  • \(P_{\mathrm{demand}} = P_{\mathrm{connected}} \times \frac{D_{\mathrm{tenant}}}{100}\)
  • \(M_{\mathrm{capacity}} = P_{\mathrm{entered\ capacity}} - P_{\mathrm{demand}}\)
Commercial Warehouse Load Calculator
  • \(D_i = S_i \times \frac{F_{d,i}}{100}\)
  • \(A_i = D_i \times \left(\frac{F_{c,i}}{100} - 1\right)\)
  • \(S_{\mathrm{adjusted}} = \sum_i \left(D_i + A_i\right)\)
  • \(I = \frac{S_{\mathrm{adjusted}}}{V k_{\mathrm{phase}}}\)
Continuous Load Calculator
  • \(\text{Continuous current} = \text{load current} \times \frac{\text{continuous portion (\%)}}{100}\)
  • \(\text{Noncontinuous current} = \text{load current} - \text{continuous current}\)
  • \(\text{Adjusted current} = \text{noncontinuous current} + \text{continuous current} \times \frac{\text{multiplier (\%)}}{100}\)
  • \(\text{Phase multiplier} = 1 \text{ for single-phase, } \sqrt{3} \text{ for balanced three-phase}\)
  • \(\text{Adjusted VA} = \text{adjusted current} \times \text{voltage} \times \text{phase multiplier}\)
  • \(\text{Ampacity margin} = \text{entered ampacity} - \text{adjusted current}\)
Demand Factor Calculator
  • factored load = connected load x entered demand factor / 100
  • entered-factor demand = factored load + fixed allowance
  • diversity allowance = connected load - entered-factor demand
Feeder Load Calculator
  • \(\text{Demand load (VA)} = \text{connected load} \times \frac{\text{demand factor (\%)}}{100}\)
  • \(\text{Continuous adder (VA)} = \text{continuous load} \times \left(\frac{\text{continuous multiplier (\%)}}{100} - 1\right)\)
  • \(\text{Adjusted feeder load (VA)} = \text{demand load} + \text{continuous adder}\)
  • \(\text{Feeder current} = \frac{\text{adjusted feeder load}}{\text{phase multiplier} \times \text{voltage}}\)
Industrial Branch Load Calculator
  • adjusted VA = connected VA x demand / 100 x max(1, continuous / 100)
  • current = adjusted VA / (phase multiplier x voltage)
Industrial Connected Load Calculator
  • \(P_{\mathrm{row}} = N_{\mathrm{row}}\times P_{\mathrm{unit}}\)
  • \(S_{\mathrm{row}} = \frac{P_{\mathrm{row}}}{\mathrm{PF}}\)
  • \(P_{\mathrm{total}} = \sum_i P_{\mathrm{row},i}\)
  • \(S_{\mathrm{total}} = \sum_i S_{\mathrm{row},i}\)
  • \(I_{\mathrm{screen}} = \frac{S_{\mathrm{total}}\times 1000}{m_{\mathrm{phase}}V}\)
Industrial Demand Load Calculator
  • connected industrial load = process + motor + heating + support loads
  • coincident demand = sum(each load block x its demand percent / 100)
  • largest load block = maximum entered load block
  • capacity margin = entered capacity - coincident demand
Industrial Feeder Capacity Calculator
  • adjusted VA = connected VA x demand / 100
  • feeder current = adjusted VA / (phase multiplier x voltage)
  • utilization = feeder current / entered capacity x 100
Lighting Load Calculator
  • \(\text{Connected lighting VA} = \text{area} \times \text{VA per square foot}\)
  • \(\text{Demand lighting VA} = \text{connected lighting VA} \times \frac{\text{demand factor (\%)}}{100}\)
  • \(\text{Adjusted lighting VA} = \text{demand lighting VA} \times \frac{\text{continuous multiplier (\%)}}{100}\)
  • \(\text{Lighting current} = \frac{\text{adjusted lighting VA}}{\text{phase multiplier} \times \text{voltage}}\)
  • \(\text{Phase multiplier} = 1\text{ for single-phase, or }\sqrt{3}\text{ for balanced three-phase}\)
Neutral Load Calculator
  • \(\displaystyle I_N=|I_A-I_B|\quad\text{for split-phase three-wire}\)
  • \(\displaystyle I_N=\sqrt{I_A^2+I_B^2+I_C^2-I_A\cdot I_B-I_B\cdot I_C-I_C\cdot I_A}\quad\text{for linear three-phase wye}\)
  • \(\displaystyle I_{\text{avg}}=\frac{\sum I_{\text{modeled}}}{N_{\text{modeled}}}\)
  • \(\displaystyle I_{\text{deviation}}=\max|I_{\text{phase}}-I_{\text{avg}}|\)
  • \(\displaystyle \text{Unbalance (\%)}=\frac{I_{\text{deviation}}}{I_{\text{avg}}}\times100\)
Panel Schedule Calculator
  • \(\displaystyle \text{Connected load (VA)}=\sum \text{row VA}\)
  • \(\displaystyle VA_{\phi,\mathrm{add}}=\begin{cases}VA_{\mathrm{row}},&\text{one selected phase}\\VA_{\mathrm{row}}/2,&\text{two selected phases}\\VA_{\mathrm{row}}/3,&\text{three selected phases}\end{cases}\)
  • \(\displaystyle \text{Imbalance (\%)}=\frac{\text{largest phase deviation}}{\text{average phase VA}}\times100\)
  • \(\displaystyle I_{\text{max}}=\frac{\text{largest phase VA}}{V_{\text{phase}}}\)
  • \(\displaystyle \text{Remaining spaces}=\text{Panel spaces}-\sum\text{entered poles}\)
Receptacle Load Calculator
  • \(\mathrm{VA}_{\mathrm{connected}} = N_{\mathrm{receptacles}} \times \mathrm{VA}_{\mathrm{per\ receptacle}}\)
  • \(\mathrm{VA}_{\mathrm{demand}} = \mathrm{VA}_{\mathrm{connected}} \times \frac{D}{100}\)
  • \(I = \frac{\mathrm{VA}_{\mathrm{demand}}}{mV}\)
  • \(m=1\ \text{for single-phase}
  • \quad m=\sqrt{3}\ \text{for balanced three-phase}\)
Three-Phase Load Balance Calculator
  • \(\text{Total load} = \text{Phase A load} + \text{Phase B load} + \text{Phase C load}\)
  • \(\text{Average phase load} = \frac{\text{Total load}}{3}\)
  • \(\text{Maximum deviation} = \max\left(\left|A-\text{Average}\right|,\left|B-\text{Average}\right|,\left|C-\text{Average}\right|\right)\)
  • \(\text{Imbalance} = \frac{\text{Maximum deviation}}{\text{Average phase load}} \times 100\%\)
  • \(\text{Suggested transfer} = \frac{\text{Maximum phase load}-\text{Minimum phase load}}{2}\)

Review basis

Commercial and industrial load workflows are preliminary arithmetic. Confirm phase balance, demand treatment, equipment data, protection, neutral effects, utility requirements, and adopted code before final design.

Everything under Commercial And Industrial Loads is a calculation from values you enter, not an approval. The pages here cite IEEE and NFPA 70 (NEC) among their basis, so confirm the edition adopted in your jurisdiction against the source text before relying on a number for design or installation.