A VFD sizing and cable-length review runs in a fixed order: the motor, then the drive, then the route to the motor. Confirm that the drive can supply the current the application actually needs, that the drive-to-motor run sits inside the limit published for that drive, and that the harmonic question is routed to the right page. Doing them out of order is how a correctly sized drive still trips on a long motor lead.
Step 1: Size the drive from motor current
Start with motor nameplate FLA, not horsepower. A drive is sold by output current, and two motors of the same horsepower can carry different full-load amps. Apply the application multiplier next: a centrifugal pump or fan with variable-torque load needs less margin than a conveyor, hoist, or any load that starts under load. Then divide by the derating factor for the installed conditions.
\(\displaystyle I_{\mathrm{basis}} = I_{\mathrm{FLA}} \times \frac{M}{100}\)
\(\displaystyle I_{\mathrm{required}} = \frac{I_{\mathrm{basis}}}{D/100}\)
\(\displaystyle I_{\mathrm{margin}} = I_{\mathrm{VFD}} - I_{\mathrm{required}}\)
For a 42 A motor with a 110% application multiplier and a 90% derating factor, the required output current is \(42 \times 1.10 = 46.2\text{ A}\), divided by 0.90, which gives 51.33 A. A 60 A drive clears that by 8.67 A, which the VFD sizing calculator reports as the entered-drive margin together with a within-rating or over-rating comparison.
Three things to check against the drive data sheet before that margin is accepted.
- Derating conditions. The derating table is usually stated for one carrier frequency and one ambient temperature. A 40 C panel at 4 kHz and a 50 C panel at 8 kHz are not the same derating.
- Altitude. Altitude derating stacks on top of the temperature derating and is easy to miss on a rooftop or mezzanine install.
- Duty rating. The published output current is often a normal-duty figure. Heavy-duty ratings on the same frame are lower.
If the motor is older or has been rewound, treat nameplate FLA as a starting point and confirm the actual running current under load. A motor already sitting at 95% of nameplate FLA leaves the drive nothing to work with. The motor current calculator covers the running current from nameplate data, and the motor starting current calculator covers the inrush the drive has to ride through on a direct-on-line comparison.
Step 2: Compare the motor lead length against the drive limit
Cable length between a drive and its motor is a limit published by the drive manufacturer, not a rule of thumb. Fast output switching means the motor terminals can see a peak voltage well above the DC bus, because the pulse reflects at the motor end of the cable. The practical consequences are winding stress on a motor that is not inverter-duty rated, and nuisance overcurrent trips from cable charging current.
\(\displaystyle L_{\mathrm{margin}} = L_{\mathrm{max}} - L_{\mathrm{actual}}\)
\(\displaystyle \mathrm{Limit\ used} = \frac{L_{\mathrm{actual}}}{L_{\mathrm{max}}} \times 100\)
A 150 ft one-way run against a 200 ft manufacturer maximum leaves 50 ft of margin and puts the installation at 75% of the limit. The VFD cable length calculator records the drive model and manual revision alongside those two numbers, because the limit only means something with the conditions attached.
Record these with the result.
| Field | Why it is part of the record |
|---|---|
| One-way length | A 150 ft run consumes 150 ft of limit, not 300 ft of conductor |
| Cable construction | Shielded VFD cable and standard tray cable have different published limits |
| Switching frequency | Raising 4 kHz to 8 kHz normally shortens the permitted lead |
| Output filter or reactor | A dv/dt or sine filter changes the limit, usually upward |
| Motor insulation class | An inverter-duty motor is rated for the pulse stress; a standard motor is not |
If the run is over the limit, the options in order of cost are: lower the switching frequency, add an output reactor or dv/dt filter, move the drive closer to the motor, or change the motor to an inverter-duty unit. Shortening the number in the record is not one of them, because the reflected wave does not read the record.
Step 3: Route the harmonics question separately
Harmonics from a drive are a system question, not a cable-length question. One small drive on a stiff supply is rarely an issue. Several drives on one bus, or a drive fed from a generator or from a transformer already near its rating, is a different review. Keep the three questions apart.
- Drive-to-motor cable length is answered by the manufacturer limit and the cable length calculator above.
- Line-side harmonic current depends on the drive harmonic data and the supply impedance, and belongs on the VFD harmonic current calculator.
- Transformer heating from harmonics needs its own review, because harmonic currents heat a transformer beyond what its kVA rating implies. See harmonics, K-factor and transformer heating.
Combining those three into one “VFD sizing” question is the most common way the wrong number ends up in the record.
What to record before the drive is ordered
A defensible sizing record has these fields filled in, each with its source:
- Motor nameplate FLA, voltage, phase, service factor, and insulation class.
- Application type, the multiplier used, and the reason for it.
- Ambient temperature at the drive, altitude, carrier frequency, and enclosure type.
- Required output current, entered drive rating, and the resulting margin.
- Drive model and manual revision used for the cable-length limit.
- Actual one-way motor lead length, cable construction, and the limit percentage used.
- Output filter or reactor fitted, if any.
- Whether a line-side harmonic review was required, and its outcome.
That record is what makes the next review cheap. When a drive is replaced or a motor is swapped, only the fields that changed need re-checking, and the margin either still holds or it does not.
Where the numbers come from
Every value above is arithmetic on entered data or a figure published by the drive manufacturer. This site quotes no generic cable-length rule, because no generic rule is defensible: the limit is a property of one drive’s switching behaviour and one cable construction. Confirm the limit against the manual revision in front of you, and confirm the motor’s suitability for inverter duty against its nameplate rather than its age.
The related checks are the VFD volts-per-hertz calculator for the voltage a given frequency should produce, VFD DC bus voltage for the DC link under the same conditions, the dynamic braking resistor calculator when the load has to stop faster than coasting allows, and the motor overload calculator for the trip setting that protects the motor once the drive is running it.