Motors And Starters
Motor FLA, running current, starting current, horsepower, torque, overload, and starter sizing calculators.
Sub-topics in this category
The 25 calculators in Motors And Starters grouped into 12 sub-topics by the work each is built for. A calculator appears under every sub-topic it serves, so these groups overlap where the same page answers more than one question.
Motor Output
Motor and equipment output inputs used in load estimates.
-
Locked Rotor Current Calculator
Estimate motor locked-rotor current from full-load current and multiplier.
-
Motor Branch Circuit Protection Calculator
Compare entered motor protection basis with a selected protection rating.
-
Motor Circuit Conductor Size Calculator
Compare entered motor ampacity basis with a selected conductor ampacity.
-
Motor Disconnect Size Calculator
Compare motor disconnect current rating from entered FLA and multiplier.
-
Motor Efficiency Calculator
Estimate motor efficiency from input and output power.
-
Motor Feeder Calculator
Screen entered feeder current from multiple motor running currents.
-
Motor Load Percentage Calculator
Estimate motor operating load percentage from measured input power and rated output.
-
Motor Overload Calculator
Compare a motor overload setting from entered FLA and setting percentage.
-
Motor Slip Calculator
Estimate induction motor slip from synchronous and measured speed.
-
Motor Slip Frequency Calculator
Calculate induction motor slip frequency from supply frequency and slip percent.
-
Motor Synchronous Speed Calculator
Calculate induction motor synchronous speed from frequency and pole count.
-
Motor Torque Calculator
Estimate motor torque from horsepower or kilowatts and speed.
-
Motor Voltage Drop Calculator
Estimate running and starting voltage drop for a motor circuit.
-
NEMA Code Letter Calculator
Estimate NEMA motor code letter from locked-rotor current and horsepower.
-
VFD Dynamic Braking Resistor Calculator
Estimate VFD braking resistor energy, peak power, and duty from entered rotating-load data.
-
VFD Sizing Calculator
Compare VFD output current against entered motor FLA and derating factors.
-
VFD Volts-per-Hertz Calculator
Calculate a VFD base volts-per-hertz reference from motor nameplate voltage and frequency.
Equipment Review
Equipment-data and nameplate review workflows.
-
Locked Rotor Current Calculator
Estimate motor locked-rotor current from full-load current and multiplier.
-
Motor Branch Circuit Protection Calculator
Compare entered motor protection basis with a selected protection rating.
-
Motor Circuit Conductor Size Calculator
Compare entered motor ampacity basis with a selected conductor ampacity.
-
Motor Current Unbalance Calculator
Calculate three-phase motor current unbalance from measured phase currents.
-
Motor Disconnect Size Calculator
Compare motor disconnect current rating from entered FLA and multiplier.
-
Motor Efficiency Calculator
Estimate motor efficiency from input and output power.
-
Motor Feeder Calculator
Screen entered feeder current from multiple motor running currents.
-
Motor Load Percentage Calculator
Estimate motor operating load percentage from measured input power and rated output.
-
Motor Overload Calculator
Compare a motor overload setting from entered FLA and setting percentage.
-
Motor Slip Calculator
Estimate induction motor slip from synchronous and measured speed.
-
Motor Slip Frequency Calculator
Calculate induction motor slip frequency from supply frequency and slip percent.
-
Motor Synchronous Speed Calculator
Calculate induction motor synchronous speed from frequency and pole count.
-
Motor Torque Calculator
Estimate motor torque from horsepower or kilowatts and speed.
-
NEMA Code Letter Calculator
Estimate NEMA motor code letter from locked-rotor current and horsepower.
-
VFD Dynamic Braking Resistor Calculator
Estimate VFD braking resistor energy, peak power, and duty from entered rotating-load data.
-
VFD Volts-per-Hertz Calculator
Calculate a VFD base volts-per-hertz reference from motor nameplate voltage and frequency.
Testing and Measurement
Measured test data, instrument readings, and field measurement calculations.
-
Motor Current Unbalance Calculator
Calculate three-phase motor current unbalance from measured phase currents.
-
Motor Load Percentage Calculator
Estimate motor operating load percentage from measured input power and rated output.
-
Motor Slip Calculator
Estimate induction motor slip from synchronous and measured speed.
-
Motor Slip Frequency Calculator
Calculate induction motor slip frequency from supply frequency and slip percent.
-
VFD DC Bus Voltage Calculator
Compare VFD DC bus voltage and measured ripple from AC line and drive test readings.
Line Current
Line-current and phase-model arithmetic workflows.
-
Locked Rotor Current Calculator
Estimate motor locked-rotor current from full-load current and multiplier.
-
Motor Current Unbalance Calculator
Calculate three-phase motor current unbalance from measured phase currents.
-
Motor Voltage Drop Calculator
Estimate running and starting voltage drop for a motor circuit.
-
NEMA Code Letter Calculator
Estimate NEMA motor code letter from locked-rotor current and horsepower.
Power Electronics
Power-electronics and component behavior screens.
-
VFD DC Bus Voltage Calculator
Compare VFD DC bus voltage and measured ripple from AC line and drive test readings.
-
VFD Dynamic Braking Resistor Calculator
Estimate VFD braking resistor energy, peak power, and duty from entered rotating-load data.
-
VFD Sizing Calculator
Compare VFD output current against entered motor FLA and derating factors.
-
VFD Volts-per-Hertz Calculator
Calculate a VFD base volts-per-hertz reference from motor nameplate voltage and frequency.
Capacity Margin
Capacity, margin, and preliminary headroom screens.
-
Motor Disconnect Size Calculator
Compare motor disconnect current rating from entered FLA and multiplier.
-
Motor Overload Calculator
Compare a motor overload setting from entered FLA and setting percentage.
-
VFD Sizing Calculator
Compare VFD output current against entered motor FLA and derating factors.
Engineering Estimate
Formula-backed estimates that require professional verification before final use.
-
Motor Synchronous Speed Calculator
Calculate induction motor synchronous speed from frequency and pole count.
-
Motor Torque Calculator
Estimate motor torque from horsepower or kilowatts and speed.
-
VFD Sizing Calculator
Compare VFD output current against entered motor FLA and derating factors.
Load Accounting
Transparent connected-load and worksheet accounting workflows.
-
Motor Circuit Conductor Size Calculator
Compare entered motor ampacity basis with a selected conductor ampacity.
-
Motor Feeder Calculator
Screen entered feeder current from multiple motor running currents.
Energy Cost
Energy-use, rate, and operating-cost calculations.
-
Motor Efficiency Calculator
Estimate motor efficiency from input and output power.
Fault Current
Preliminary fault-current and short-circuit contribution screens.
-
Motor Branch Circuit Protection Calculator
Compare entered motor protection basis with a selected protection rating.
Voltage Drop
Voltage-drop and conductor-length calculation workflows.
-
Motor Voltage Drop Calculator
Estimate running and starting voltage drop for a motor circuit.
Voltage Readings
Voltage measurements and voltage-ratio comparison workflows.
-
VFD DC Bus Voltage Calculator
Compare VFD DC bus voltage and measured ripple from AC line and drive test readings.
What this topic covers
About this category
25 calculators are grouped under Motors And Starters, and the work splits into Motor Output, Equipment Review, Testing and Measurement, Line Current. Every page states the formula it applies, the inputs and units it expects, and the limits of the estimate, so a result can be checked against the adopted code edition and the equipment nameplate before it is used for a design decision.
Written for Electricians, Engineers, Estimators, Inspectors, and Technicians.
Formulas used in this category
The arithmetic the 25 calculators in Motors And Starters apply, in the order it is evaluated. These are calculation summaries, not code text — verify each against the source standard before design use. Full explanations for every topic are in the formula reference index.
Show formula sheet (25 calculators)
- Electrical Load Calculator
-
- \(u = \frac{\text{Utilization percent}}{100}\)
- \(I_{\text{estimated}} = I_{\text{load}} \times u\)
- \(\phi = 1\text{ for single-phase}
- \ \sqrt{3}\text{ for balanced three-phase}\)
- \(S = V \times I_{\text{estimated}} \times \phi\)
- \(P = S \times \mathrm{PF}\)
- Full-Load Current Estimate Calculator
-
- \(P_{\text{shaft}} = \text{Motor horsepower} \times 746\)
- \(\eta = \frac{\text{Motor efficiency percent}}{100}\)
- \(P_{\text{input}} = \frac{P_{\text{shaft}}}{\eta}\)
- \(S = \frac{P_{\text{input}}}{\mathrm{PF}}\)
- \(\phi = 1\text{ for single-phase}
- \ \sqrt{3}\text{ for balanced three-phase}\)
- Locked Rotor Current Calculator
-
- \(\text{Estimated locked-rotor current} = \text{full-load current} \times \text{locked-rotor multiplier}\)
- \(\text{Comparison margin} = \text{estimated locked-rotor current} - \text{starting-current reference}\quad\text{when a reference is entered
- otherwise }0\)
- \(\text{Comparison ratio} = \begin{cases}\frac{\text{estimated locked-rotor current}}{\text{starting-current reference}},&\text{reference}>0\\0,&\text{reference}=0\end{cases}\)
- Motor Branch Circuit Protection Calculator
-
- entered reference protection = motor FLA x entered protection factor / 100
- protection margin = selected protection rating - entered reference protection
- protection margin percent = protection margin / entered reference protection x 100
- Motor Circuit Conductor Size Calculator
-
- entered required ampacity = motor FLA x entered ampacity factor / 100
- ampacity margin = selected conductor ampacity - entered required ampacity
- ampacity margin percent = ampacity margin / entered required ampacity x 100
- Motor Current Calculator
-
- \(P_{\text{shaft}} = \text{Motor horsepower} \times 746\)
- \(\eta = \frac{\text{Efficiency percent}}{100}\)
- \(P_{\text{input}} = \frac{P_{\text{shaft}}}{\eta}\)
- \(S = \frac{P_{\text{input}}}{\mathrm{PF}}\)
- \(\phi = 1\text{ for single-phase}
- \ \sqrt{3}\text{ for balanced three-phase}\)
- Motor Current Unbalance Calculator
-
- \(I_{\mathrm{avg}} = \frac{I_A + I_B + I_C}{3}\)
- \(\Delta I_{\mathrm{max}} = \max(|I_A - I_{\mathrm{avg}}|, |I_B - I_{\mathrm{avg}}|, |I_C - I_{\mathrm{avg}}|)\)
- \(\mathrm{Unbalance}\% = \frac{\Delta I_{\mathrm{max}}}{I_{\mathrm{avg}}} \times 100\)
- \(\mathrm{Margin}\% = \mathrm{Reference}\% - \mathrm{Unbalance}\%\)
- Motor Disconnect Size Calculator
-
- \(\displaystyle I_{\text{required}} = I_{\text{FLA}} \times \frac{p_{\text{disconnect}}}{100}\)
- \(\displaystyle M_{\text{disconnect}} = I_{\text{entered}} - I_{\text{required}}\)
- \(\displaystyle S_{\text{motor}} = \frac{V I_{\text{FLA}} k_{\phi}}{1000},\quad k_{\phi}=1\text{ for single-phase and }\sqrt{3}\text{ for balanced three-phase}\)
- Motor Efficiency Calculator
-
- \(\displaystyle \text{Output power (W)} = \begin{cases}\text{Output power (kW)}\times 1000,&\text{kW input}\\text{Output power (hp)}\times 746,&\text{hp input}\end{cases}\)
- \(\displaystyle \text{Efficiency (\%)} = \frac{\text{Output power (W)}}{\text{Input power (W)}}\times 100\)
- \(\displaystyle \text{Losses (W)} = \text{Input power (W)}-\text{Output power (W)}\)
- Motor Feeder Calculator
-
- total running current = sum of motor running currents
- largest motor contribution = largest running current x entered largest-motor factor / 100
- feeder screen current = total running current + largest motor contribution
- Motor Load Percentage Calculator
-
- \(P_{\mathrm{out}} = P_{\mathrm{in}} \times \eta\)
- \(\mathrm{Load}\% = \frac{P_{\mathrm{out}}}{P_{\mathrm{rated}}} \times 100\)
- \(P_{\mathrm{loss}} = P_{\mathrm{in}} - P_{\mathrm{out}}\)
- \(E_{\mathrm{daily}} = P_{\mathrm{in}} \times t_{\mathrm{daily}}\)
- Motor Overload Calculator
-
- \(\displaystyle I_{\mathrm{OL}} = I_{\mathrm{FLA}} \times \frac{p_{\mathrm{set}}}{100}\)
- \(\displaystyle M_{\mathrm{set}} = I_{\mathrm{entered}} - I_{\mathrm{OL}}\)
- \(\displaystyle S_{\mathrm{motor}} = \frac{V I_{\mathrm{FLA}} k_{\phi}}{1000},\quad k_{\phi}=1\text{ for single-phase and }\sqrt{3}\text{ for balanced three-phase}\)
- Motor Power From Current Calculator
-
- \(\phi = 1\text{ for single-phase}
- \ \sqrt{3}\text{ for balanced three-phase}\)
- \(\eta = \frac{\text{Efficiency percent}}{100}\)
- \(S = V \times I \times \phi\)
- \(P_{\text{input}} = S \times \mathrm{PF}\)
- \(P_{\text{output}} = P_{\text{input}} \times \eta\)
- Motor Slip Calculator
-
- \(\displaystyle \Delta n = n_{\mathrm{synchronous}} - n_{\mathrm{measured}}\)
- \(\displaystyle s = \frac{\Delta n}{n_{\mathrm{synchronous}}} \times 100\%\)
- Motor Slip Frequency Calculator
-
- \(f_{\mathrm{slip}} = f_{\mathrm{supply}} \times \frac{\mathrm{Slip}\%}{100}\)
- \(\mathrm{Slip}\% = \frac{n_s - n_r}{n_s} \times 100\)
- Motor Starter Current Reference Calculator
-
- \(r_{\text{overload}} = \frac{\text{Overload reference percentage}}{100}\)
- \(r_{\text{starter}} = \frac{\text{Starter margin percentage}}{100}\)
- \(I_{\text{overload reference}} = I_{\text{FLA}} \times r_{\text{overload}}\)
- \(I_{\text{starting}} = I_{\text{FLA}} \times \text{Starting current multiplier}\)
- \(I_{\text{starter basis}} = I_{\text{FLA}} \times r_{\text{starter}}\)
- overload reference ratio = overload reference percentage / 100
- Motor Starting Current Calculator
-
- \(\text{Starting current} = \text{Full-load current} \times \text{Starting multiplier}\)
- \(\text{Estimated voltage sag} = \text{Line voltage} \times \frac{\text{Voltage sag percent}}{100}\)
- \(\text{Remaining voltage reference} = \text{Line voltage} - \text{Estimated voltage sag}\)
- \(\text{Running current reference} = \text{Full-load current}\)
- remaining voltage reference = line voltage - estimated voltage sag
- starting method boundary = starting multiplier is user-supplied
- Motor Synchronous Speed Calculator
-
- \(n_s = \frac{120 \times f}{P}\)
- \(n_{\mathrm{actual}} < n_s\ \mathrm{when\ induction\ motor\ slip\ is\ present}\)
- Motor Torque Calculator
-
- \(\displaystyle P_{\mathrm{hp}} = \begin{cases}P_{\mathrm{entered}},&\text{hp input}\\1.34102209\,P_{\mathrm{entered}},&\text{kW input}\end{cases}\)
- \(\displaystyle T_{\mathrm{lb\!-\!ft}} = \frac{5252\,P_{\mathrm{hp}}}{n}\)
- \(\displaystyle T_{\mathrm{N\cdot m}} = 1.3558179483314\,T_{\mathrm{lb\!-\!ft}}\)
- Motor Voltage Drop Calculator
-
- \(\displaystyle k_{\phi}=2\text{ for single-phase two-conductor}
- \ \sqrt{3}\text{ for balanced three-phase}\)
- \(\displaystyle V_{D,\text{running}}=k_{\phi} I_{\text{running}}R\frac{L}{1000}\)
- \(\displaystyle V_{D,\text{starting}}=k_{\phi} I_{\text{starting}}R\frac{L}{1000}\)
- \(\displaystyle \text{Voltage-drop (\%)}=\frac{V_D}{V_{\text{system}}}\times100\)
- \(\displaystyle \text{Remaining voltage}=V_{\text{system}}-V_D\)
- NEMA Code Letter Calculator
-
- \(\displaystyle k_{\phi}=1\text{ for single-phase}
- \ \sqrt{3}\text{ for balanced three-phase}\)
- \(\displaystyle S_{\text{locked-rotor}}=\frac{k_{\phi} V I_{\text{LRA}}}{1000}\)
- \(\displaystyle \text{kVA per hp}=\frac{S_{\text{locked-rotor}}}{\text{Horsepower}}\)
- \(\displaystyle \text{Estimated code letter}=\text{matching kVA-per-hp range}\)
- VFD DC Bus Voltage Calculator
-
- \(V_{\mathrm{DC,\ expected}} = V_{\mathrm{line-line}} \times \mathrm{rectifier\ multiplier}\)
- \(\mathrm{Bus\ deviation} = \frac{V_{\mathrm{measured\ bus}} - V_{\mathrm{DC,\ expected}}}{V_{\mathrm{DC,\ expected}}} \times 100\%\)
- \(\mathrm{Ripple\ percent} = \frac{V_{\mathrm{ripple,\ peak-to-peak}}}{V_{\mathrm{measured\ bus}}} \times 100\%\)
- VFD Dynamic Braking Resistor Calculator
-
- \(\omega = \mathrm{rpm} \times \frac{2\pi}{60}\)
- \(E_{\mathrm{rotating}} = 0.5J(\omega_{\mathrm{initial}}^2 - \omega_{\mathrm{final}}^2)\)
- \(E_{\mathrm{resistor}} = E_{\mathrm{rotating}} \times \mathrm{braking\ energy\ fraction}\)
- \(P_{\mathrm{peak}} = \frac{E_{\mathrm{resistor}}}{t_{\mathrm{deceleration}}}\)
- \(P_{\mathrm{average}} = \frac{E_{\mathrm{resistor}} \times \mathrm{cycles\ per\ hour}}{3600}\)
- \(R_{\mathrm{minimum}} = \frac{V_{\mathrm{DC\ bus}}^2}{P_{\mathrm{peak}}}\)
- VFD Sizing Calculator
-
- \(I_{\mathrm{basis}} = I_{\mathrm{FLA}}\times\frac{M}{100}\)
- \(I_{\mathrm{required}} = \frac{I_{\mathrm{basis}}}{D/100}\)
- \(I_{\mathrm{margin}} = I_{\mathrm{VFD}}-I_{\mathrm{required}}\)
- \(S_{\mathrm{motor}} = \frac{I_{\mathrm{FLA}}\times V\times k_{\phi}}{1000}\,\mathrm{kVA}\)
- VFD Volts-per-Hertz Calculator
-
- \(\mathrm{Base\ V/Hz} = \frac{\mathrm{rated\ voltage}}{\mathrm{rated\ frequency}}\)
- \(V_{\mathrm{reference,\ unlimited}} = \mathrm{Base\ V/Hz} \times f_{\mathrm{target}} + V_{\mathrm{boost}}\)
- \(V_{\mathrm{reference}} = \min(V_{\mathrm{reference,\ unlimited}}, V_{\mathrm{maximum}})\)
- \(\mathrm{Voltage\ limited\ amount} = \max(0, V_{\mathrm{reference,\ unlimited}} - V_{\mathrm{reference}})\)
Review basis
Motor workflows need nameplate, controller, conductor, protection, and manufacturer data verification.
Everything under Motors And Starters is a calculation from values you enter, not an approval. The pages here cite IEEE, NEMA, and NEMA MG-1 among their basis, so confirm the edition adopted in your jurisdiction against the source text before relying on a number for design or installation.