Motors And Starters

Motor FLA, running current, starting current, horsepower, torque, overload, and starter sizing calculators.

Sub-topics in this category

The 25 calculators in Motors And Starters grouped into 12 sub-topics by the work each is built for. A calculator appears under every sub-topic it serves, so these groups overlap where the same page answers more than one question.

Motor Output

Motor and equipment output inputs used in load estimates.

Equipment Review

Equipment-data and nameplate review workflows.

Testing and Measurement

Measured test data, instrument readings, and field measurement calculations.

Line Current

Line-current and phase-model arithmetic workflows.

Power Electronics

Power-electronics and component behavior screens.

Capacity Margin

Capacity, margin, and preliminary headroom screens.

Engineering Estimate

Formula-backed estimates that require professional verification before final use.

Load Accounting

Transparent connected-load and worksheet accounting workflows.

Energy Cost

Energy-use, rate, and operating-cost calculations.

Fault Current

Preliminary fault-current and short-circuit contribution screens.

Voltage Drop

Voltage-drop and conductor-length calculation workflows.

Voltage Readings

Voltage measurements and voltage-ratio comparison workflows.

What this topic covers

About this category

25 calculators are grouped under Motors And Starters, and the work splits into Motor Output, Equipment Review, Testing and Measurement, Line Current. Every page states the formula it applies, the inputs and units it expects, and the limits of the estimate, so a result can be checked against the adopted code edition and the equipment nameplate before it is used for a design decision.

Written for Electricians, Engineers, Estimators, Inspectors, and Technicians.

Basis cited across this topic: IEEE (1), NEMA (5), NEMA MG-1 (4), NFPA 70 (NEC) (16). Each calculator lists its own source citation and review dates on its page.

Formulas used in this category

The arithmetic the 25 calculators in Motors And Starters apply, in the order it is evaluated. These are calculation summaries, not code text — verify each against the source standard before design use. Full explanations for every topic are in the formula reference index.

Show formula sheet (25 calculators)
Electrical Load Calculator
  • \(u = \frac{\text{Utilization percent}}{100}\)
  • \(I_{\text{estimated}} = I_{\text{load}} \times u\)
  • \(\phi = 1\text{ for single-phase}
  • \ \sqrt{3}\text{ for balanced three-phase}\)
  • \(S = V \times I_{\text{estimated}} \times \phi\)
  • \(P = S \times \mathrm{PF}\)
Full-Load Current Estimate Calculator
  • \(P_{\text{shaft}} = \text{Motor horsepower} \times 746\)
  • \(\eta = \frac{\text{Motor efficiency percent}}{100}\)
  • \(P_{\text{input}} = \frac{P_{\text{shaft}}}{\eta}\)
  • \(S = \frac{P_{\text{input}}}{\mathrm{PF}}\)
  • \(\phi = 1\text{ for single-phase}
  • \ \sqrt{3}\text{ for balanced three-phase}\)
Locked Rotor Current Calculator
  • \(\text{Estimated locked-rotor current} = \text{full-load current} \times \text{locked-rotor multiplier}\)
  • \(\text{Comparison margin} = \text{estimated locked-rotor current} - \text{starting-current reference}\quad\text{when a reference is entered
  • otherwise }0\)
  • \(\text{Comparison ratio} = \begin{cases}\frac{\text{estimated locked-rotor current}}{\text{starting-current reference}},&\text{reference}>0\\0,&\text{reference}=0\end{cases}\)
Motor Branch Circuit Protection Calculator
  • entered reference protection = motor FLA x entered protection factor / 100
  • protection margin = selected protection rating - entered reference protection
  • protection margin percent = protection margin / entered reference protection x 100
Motor Circuit Conductor Size Calculator
  • entered required ampacity = motor FLA x entered ampacity factor / 100
  • ampacity margin = selected conductor ampacity - entered required ampacity
  • ampacity margin percent = ampacity margin / entered required ampacity x 100
Motor Current Calculator
  • \(P_{\text{shaft}} = \text{Motor horsepower} \times 746\)
  • \(\eta = \frac{\text{Efficiency percent}}{100}\)
  • \(P_{\text{input}} = \frac{P_{\text{shaft}}}{\eta}\)
  • \(S = \frac{P_{\text{input}}}{\mathrm{PF}}\)
  • \(\phi = 1\text{ for single-phase}
  • \ \sqrt{3}\text{ for balanced three-phase}\)
Motor Current Unbalance Calculator
  • \(I_{\mathrm{avg}} = \frac{I_A + I_B + I_C}{3}\)
  • \(\Delta I_{\mathrm{max}} = \max(|I_A - I_{\mathrm{avg}}|, |I_B - I_{\mathrm{avg}}|, |I_C - I_{\mathrm{avg}}|)\)
  • \(\mathrm{Unbalance}\% = \frac{\Delta I_{\mathrm{max}}}{I_{\mathrm{avg}}} \times 100\)
  • \(\mathrm{Margin}\% = \mathrm{Reference}\% - \mathrm{Unbalance}\%\)
Motor Disconnect Size Calculator
  • \(\displaystyle I_{\text{required}} = I_{\text{FLA}} \times \frac{p_{\text{disconnect}}}{100}\)
  • \(\displaystyle M_{\text{disconnect}} = I_{\text{entered}} - I_{\text{required}}\)
  • \(\displaystyle S_{\text{motor}} = \frac{V I_{\text{FLA}} k_{\phi}}{1000},\quad k_{\phi}=1\text{ for single-phase and }\sqrt{3}\text{ for balanced three-phase}\)
Motor Efficiency Calculator
  • \(\displaystyle \text{Output power (W)} = \begin{cases}\text{Output power (kW)}\times 1000,&\text{kW input}\\text{Output power (hp)}\times 746,&\text{hp input}\end{cases}\)
  • \(\displaystyle \text{Efficiency (\%)} = \frac{\text{Output power (W)}}{\text{Input power (W)}}\times 100\)
  • \(\displaystyle \text{Losses (W)} = \text{Input power (W)}-\text{Output power (W)}\)
Motor Feeder Calculator
  • total running current = sum of motor running currents
  • largest motor contribution = largest running current x entered largest-motor factor / 100
  • feeder screen current = total running current + largest motor contribution
Motor Load Percentage Calculator
  • \(P_{\mathrm{out}} = P_{\mathrm{in}} \times \eta\)
  • \(\mathrm{Load}\% = \frac{P_{\mathrm{out}}}{P_{\mathrm{rated}}} \times 100\)
  • \(P_{\mathrm{loss}} = P_{\mathrm{in}} - P_{\mathrm{out}}\)
  • \(E_{\mathrm{daily}} = P_{\mathrm{in}} \times t_{\mathrm{daily}}\)
Motor Overload Calculator
  • \(\displaystyle I_{\mathrm{OL}} = I_{\mathrm{FLA}} \times \frac{p_{\mathrm{set}}}{100}\)
  • \(\displaystyle M_{\mathrm{set}} = I_{\mathrm{entered}} - I_{\mathrm{OL}}\)
  • \(\displaystyle S_{\mathrm{motor}} = \frac{V I_{\mathrm{FLA}} k_{\phi}}{1000},\quad k_{\phi}=1\text{ for single-phase and }\sqrt{3}\text{ for balanced three-phase}\)
Motor Power From Current Calculator
  • \(\phi = 1\text{ for single-phase}
  • \ \sqrt{3}\text{ for balanced three-phase}\)
  • \(\eta = \frac{\text{Efficiency percent}}{100}\)
  • \(S = V \times I \times \phi\)
  • \(P_{\text{input}} = S \times \mathrm{PF}\)
  • \(P_{\text{output}} = P_{\text{input}} \times \eta\)
Motor Slip Calculator
  • \(\displaystyle \Delta n = n_{\mathrm{synchronous}} - n_{\mathrm{measured}}\)
  • \(\displaystyle s = \frac{\Delta n}{n_{\mathrm{synchronous}}} \times 100\%\)
Motor Slip Frequency Calculator
  • \(f_{\mathrm{slip}} = f_{\mathrm{supply}} \times \frac{\mathrm{Slip}\%}{100}\)
  • \(\mathrm{Slip}\% = \frac{n_s - n_r}{n_s} \times 100\)
Motor Starter Current Reference Calculator
  • \(r_{\text{overload}} = \frac{\text{Overload reference percentage}}{100}\)
  • \(r_{\text{starter}} = \frac{\text{Starter margin percentage}}{100}\)
  • \(I_{\text{overload reference}} = I_{\text{FLA}} \times r_{\text{overload}}\)
  • \(I_{\text{starting}} = I_{\text{FLA}} \times \text{Starting current multiplier}\)
  • \(I_{\text{starter basis}} = I_{\text{FLA}} \times r_{\text{starter}}\)
  • overload reference ratio = overload reference percentage / 100
Motor Starting Current Calculator
  • \(\text{Starting current} = \text{Full-load current} \times \text{Starting multiplier}\)
  • \(\text{Estimated voltage sag} = \text{Line voltage} \times \frac{\text{Voltage sag percent}}{100}\)
  • \(\text{Remaining voltage reference} = \text{Line voltage} - \text{Estimated voltage sag}\)
  • \(\text{Running current reference} = \text{Full-load current}\)
  • remaining voltage reference = line voltage - estimated voltage sag
  • starting method boundary = starting multiplier is user-supplied
Motor Synchronous Speed Calculator
  • \(n_s = \frac{120 \times f}{P}\)
  • \(n_{\mathrm{actual}} < n_s\ \mathrm{when\ induction\ motor\ slip\ is\ present}\)
Motor Torque Calculator
  • \(\displaystyle P_{\mathrm{hp}} = \begin{cases}P_{\mathrm{entered}},&\text{hp input}\\1.34102209\,P_{\mathrm{entered}},&\text{kW input}\end{cases}\)
  • \(\displaystyle T_{\mathrm{lb\!-\!ft}} = \frac{5252\,P_{\mathrm{hp}}}{n}\)
  • \(\displaystyle T_{\mathrm{N\cdot m}} = 1.3558179483314\,T_{\mathrm{lb\!-\!ft}}\)
Motor Voltage Drop Calculator
  • \(\displaystyle k_{\phi}=2\text{ for single-phase two-conductor}
  • \ \sqrt{3}\text{ for balanced three-phase}\)
  • \(\displaystyle V_{D,\text{running}}=k_{\phi} I_{\text{running}}R\frac{L}{1000}\)
  • \(\displaystyle V_{D,\text{starting}}=k_{\phi} I_{\text{starting}}R\frac{L}{1000}\)
  • \(\displaystyle \text{Voltage-drop (\%)}=\frac{V_D}{V_{\text{system}}}\times100\)
  • \(\displaystyle \text{Remaining voltage}=V_{\text{system}}-V_D\)
NEMA Code Letter Calculator
  • \(\displaystyle k_{\phi}=1\text{ for single-phase}
  • \ \sqrt{3}\text{ for balanced three-phase}\)
  • \(\displaystyle S_{\text{locked-rotor}}=\frac{k_{\phi} V I_{\text{LRA}}}{1000}\)
  • \(\displaystyle \text{kVA per hp}=\frac{S_{\text{locked-rotor}}}{\text{Horsepower}}\)
  • \(\displaystyle \text{Estimated code letter}=\text{matching kVA-per-hp range}\)
VFD DC Bus Voltage Calculator
  • \(V_{\mathrm{DC,\ expected}} = V_{\mathrm{line-line}} \times \mathrm{rectifier\ multiplier}\)
  • \(\mathrm{Bus\ deviation} = \frac{V_{\mathrm{measured\ bus}} - V_{\mathrm{DC,\ expected}}}{V_{\mathrm{DC,\ expected}}} \times 100\%\)
  • \(\mathrm{Ripple\ percent} = \frac{V_{\mathrm{ripple,\ peak-to-peak}}}{V_{\mathrm{measured\ bus}}} \times 100\%\)
VFD Dynamic Braking Resistor Calculator
  • \(\omega = \mathrm{rpm} \times \frac{2\pi}{60}\)
  • \(E_{\mathrm{rotating}} = 0.5J(\omega_{\mathrm{initial}}^2 - \omega_{\mathrm{final}}^2)\)
  • \(E_{\mathrm{resistor}} = E_{\mathrm{rotating}} \times \mathrm{braking\ energy\ fraction}\)
  • \(P_{\mathrm{peak}} = \frac{E_{\mathrm{resistor}}}{t_{\mathrm{deceleration}}}\)
  • \(P_{\mathrm{average}} = \frac{E_{\mathrm{resistor}} \times \mathrm{cycles\ per\ hour}}{3600}\)
  • \(R_{\mathrm{minimum}} = \frac{V_{\mathrm{DC\ bus}}^2}{P_{\mathrm{peak}}}\)
VFD Sizing Calculator
  • \(I_{\mathrm{basis}} = I_{\mathrm{FLA}}\times\frac{M}{100}\)
  • \(I_{\mathrm{required}} = \frac{I_{\mathrm{basis}}}{D/100}\)
  • \(I_{\mathrm{margin}} = I_{\mathrm{VFD}}-I_{\mathrm{required}}\)
  • \(S_{\mathrm{motor}} = \frac{I_{\mathrm{FLA}}\times V\times k_{\phi}}{1000}\,\mathrm{kVA}\)
VFD Volts-per-Hertz Calculator
  • \(\mathrm{Base\ V/Hz} = \frac{\mathrm{rated\ voltage}}{\mathrm{rated\ frequency}}\)
  • \(V_{\mathrm{reference,\ unlimited}} = \mathrm{Base\ V/Hz} \times f_{\mathrm{target}} + V_{\mathrm{boost}}\)
  • \(V_{\mathrm{reference}} = \min(V_{\mathrm{reference,\ unlimited}}, V_{\mathrm{maximum}})\)
  • \(\mathrm{Voltage\ limited\ amount} = \max(0, V_{\mathrm{reference,\ unlimited}} - V_{\mathrm{reference}})\)

Review basis

Motor workflows need nameplate, controller, conductor, protection, and manufacturer data verification.

Everything under Motors And Starters is a calculation from values you enter, not an approval. The pages here cite IEEE, NEMA, and NEMA MG-1 among their basis, so confirm the edition adopted in your jurisdiction against the source text before relying on a number for design or installation.

Where to go next: Motors, Starters And VFD and Power Quality And Transformers and the formula reference, all calculators, or printable worksheets for the same calculations.