Transformer Current Calculator

Use this transformer current workflow to convert kVA into primary and secondary current estimates. It is not conductor, breaker, fuse, or equipment selection.

  • Updated August 22, 2026
Inputs
Result

Formulas

  • Transformer VA = kVA x 1000
  • Single-phase current = VA / volts
  • Three-phase current = VA / (sqrt(3) x volts)

A transformer current calculator converts a transformer’s apparent power rating in kVA into estimated primary and secondary line current. The result establishes the electrical loading basis for the transformer supply and output conductors, feeder review, disconnect and overcurrent-protection evaluation, voltage-drop calculations, raceway-fill planning, and equipment load coordination.

The calculator reports the current associated with the entered Transformer size, Primary voltage, Secondary voltage, and Phase. It calculates electrical current only. It does not select conductors, AWG or kcmil sizes, breakers, fuses, disconnects, bus ratings, or other equipment.

Primary and Secondary Current

A transformer transfers apparent power from one voltage level to another. When voltage decreases, current increases proportionally for the same kVA; when voltage increases, current decreases.

For a step-down transformer, the secondary current is normally higher than the primary current. That relationship is visible immediately in the calculated values and helps establish the expected feeder and secondary-conductor loading.

The calculator provides:

ResultElectrical use
Primary currentEstimated line current on the transformer supply side
Secondary currentEstimated line current available on the transformer output side
Apparent powerEntered transformer kVA expressed in VA
Phase multiplierThe multiplier used for the selected phase calculation

The current results are based on apparent power, not measured operating demand. Actual current can be lower when the connected load is below the transformer rating, or it can vary with load type and operating conditions.

Inputs and Calculation Method

Transformer size

Transformer size is the transformer apparent power rating or load basis, entered in kVA.

The calculator converts kVA to volt-amperes:

\(\text{Apparent power (VA)} = \text{Transformer size (kVA)} \times 1{,}000\)

A 75 kVA transformer therefore has an apparent power value of:

\(75 \times 1{,}000 = 75{,}000\ \text{VA}\)

Primary voltage and Secondary voltage

Primary voltage is the transformer input line voltage. Secondary voltage is the transformer output line voltage.

For balanced three-phase calculations, each voltage should represent the applicable line-to-line system voltage. The calculator uses the primary voltage to determine Primary current and the secondary voltage to determine Secondary current.

Phase

The Phase field chooses between single-phase and balanced three-phase current math.

Phase selectionCurrent formulaPhase multiplier
Single-phase\(I = \frac{VA}{V}\)1
Balanced three-phase\(I = \frac{VA}{\sqrt{3} \times V}\)1.7321 x

For balanced three-phase systems, the calculator uses the line-current relationship:

\(\text{Current (A)} = \frac{\text{Apparent power (VA)}}{\sqrt{3} \times \text{Line voltage (V)}}\)

The displayed Phase multiplier of 1.7321 x is the rounded value of \(\sqrt{3}\).

Calculation Example

Use the following entered values:

InputValue
Transformer size75 kVA
Primary voltage480 V
Secondary voltage208 V
PhaseBalanced three-phase

First, convert the transformer size to apparent power:

\(75\ \text{kVA} \times 1{,}000 = 75{,}000\ \text{VA}\)

Calculate primary current at 480 V:

\(I_{primary} = \frac{75{,}000}{1.7321 \times 480} = 90.211\ \text{A}\)

Calculate secondary current at 208 V:

\(I_{secondary} = \frac{75{,}000}{1.7321 \times 208} = 208.1792\ \text{A}\)

Result

ResultCalculated value
Primary current90.211 A
Secondary current208.1792 A
Apparent power75000 VA
Phase multiplier1.7321 x

The 75 kVA transformer has a lower calculated line current at its 480 V primary than at its 208 V secondary because the same apparent power is delivered at a lower voltage on the secondary side.

Using Transformer Current in Design

Transformer current is commonly carried into several downstream electrical calculations:

  • Establishing the ampere basis for primary and secondary feeder conductors.
  • Reviewing conductor ampacity after applying applicable adjustment factors and correction factors.
  • Checking whether conductor terminal ratings and insulation temperature ratings support the final conductor selection.
  • Estimating voltage drop on the transformer primary feeder or secondary conductors.
  • Evaluating raceway fill and conduit layout after the conductor count, insulation type, and AWG or kcmil size are known.
  • Reviewing downstream panelboard, switchboard, disconnect, and bus current ratings.
  • Comparing transformer secondary capacity with calculated branch-circuit and feeder loads.
  • Coordinating motor loads, continuous loads, and other connected load categories in the broader distribution design.

A calculated secondary current of 208.1792 A does not automatically mean that a 208 A conductor, breaker, or fuse is selected. The final design must account for the installation and equipment requirements that govern the circuit.

Field Verification

Use the transformer nameplate and installation documents to verify the electrical basis before applying the calculated current to a design. Confirm the actual transformer kVA rating, primary and secondary voltage configuration, phase arrangement, tap position where applicable, and whether the load is balanced three-phase or single-phase.

Conductor and overcurrent-protection decisions require separate review of applicable code requirements, conductor ampacity, terminal limitations, current-carrying conductors, ambient temperature, raceway conditions, voltage drop, available fault current, transformer impedance, equipment listings, and AHJ requirements. The calculator’s Primary current and Secondary current results are the kVA-to-ampere starting values for that work.

FAQs

Can this size transformer conductors?

No. It only estimates current from kVA and voltage. Conductor and protection sizing require separate code and equipment review.

Should I use line-to-line voltage for three-phase?

Use the voltage basis that matches the transformer kVA and phase model you are evaluating.