Published formula references appear here when they need a standalone explanation.
Electrical Formulas and Reference Calculations
A topic-by-topic index of how each Elecatrix calculator derives its result, written in plain language so it can be checked against the adopted code edition, the equipment nameplate, and the project conditions. Open a calculator to run it and read the full assumptions behind the number.
Conduit Bending
-
Box Offset Calculator
Box-offset travel equals box offset depth divided by sine of bend angle. The second mark adds travel to the first mark.
-
Concentric Bend Calculator
Target radius equals inside centerline radius plus spacing times the conduit offset count. Developed arc length equals radius times bend angle in radians, and mark spacing divides that arc by the segment count.
-
Conduit 30-Degree Bend Calculator
For a fixed 30-degree bend, diagonal travel is rise divided by sine of a 30-degree angle, tangent run is rise divided by tangent of a 30-degree angle, and arc length is the circular 30-degree arc from the entered radius.
-
Conduit 45-Degree Bend Calculator
For a fixed 45-degree bend, diagonal travel is rise divided by sine of a 45-degree angle, tangent run is rise divided by tangent of a 45-degree angle, and arc length is the circular 45-degree arc from the entered radius.
-
Conduit 90-Degree Bend Take-Up Calculator
The mode adds the entered take-up to the desired stub height using the local stub-up reference convention.
-
Conduit Back-to-Back Bend Calculator
Each bend travel equals its entered rise divided by the sine of its angle. Bend separation is the sum of the two travels.
-
Conduit Bend Angle Calculator
Bend angle equals inverse sine of rise divided by travel. The result is valid only when rise does not exceed travel.
-
Conduit Bend Multiplier Calculator
The mode calculates the offset multiplier from sine and the shrink factor from the half-angle tangent.
-
Conduit Bend Radius Calculator
Centerline radius is the average of inside and outside radius. Developed arc length uses the centerline radius and entered bend angle. The margin compares the centerline radius with the entered minimum.
-
Conduit Cut Length Calculator
Cut length equals total straight runs plus bend shrink, then plus the entered waste allowance.
-
Conduit Multibend Layout Calculator
Total bend angle is the sum of angle times mark count for each group. Developed length equals radius times total angle in radians, and mark spacing divides that span across one fewer interval than the total mark count.
-
Conduit Offset Travel Calculator
Travel equals offset rise divided by sine of bend angle. The second mark equals the first mark plus travel.
-
Conduit Parallel Run Calculator
Total route length multiplies equal run length by run count. Centerline spread is spacing times the number of gaps, and outside span adds one entered conduit diameter.
-
Conduit Saddle Shrink Calculator
Mark spacing is rise divided by sine of the outside angle. Shrink per saddle is rise multiplied by tangent of half the outside angle. Total shrink multiplies that estimate by the entered saddle count.
-
Conduit Shrink Calculator
One-set shrink uses offset depth times the tangent of half the bend angle; total shrink multiplies that value by bend-set count.
-
Conduit Stub Length Calculator
Tangent run equals stub height divided by tangent of bend angle. Take-up and end allowance are added as separate user-entered quantities.
-
Conduit Three-Bend Sequence Calculator
Each travel equals common rise divided by sine of its angle. Marks accumulate the three travels in sequence.
-
Kick Bend Calculator
The kick multiplier is 1 divided by tan(angle). Mark-to-obstruction distance is rise times that multiplier. The obstruction edge mark adds that distance to the bend layout mark. Estimated shrink is rise multiplied by tan(angle divided by 2).
-
Offset Bend Calculator
The offset multiplier is 1 divided by sin(angle). Travel between marks is rise times that multiplier. Estimated shrink is rise multiplied by tan(angle divided by 2). The first mark is the reference mark, and the second mark is the first mark plus travel.
-
Parallel Offset Calculator
The offset multiplier is 1 divided by sin(angle). Travel between marks is rise divided by sin(angle). Adjacent first-mark stagger is the bend-plane center-to-center spacing multiplied by tan(angle divided by 2). Under the later-mark convention, the last conduit first mark adds one stagger for each additional conduit.
-
Rolling Offset Calculator
True rolling offset is the square root of horizontal offset squared plus vertical offset squared. Travel, the second mark, and estimated shrink then follow from the entered bend angle and first mark.
-
Saddle Bend Calculator
The spacing multiplier is 1 divided by sin(outside bend angle). Center-to-outside mark spacing is rise times that multiplier. Near and far outside marks are the center mark minus or plus that spacing. The center bend angle is twice the outside bend angle, and estimated shrink uses rise multiplied by tan(outside bend angle divided by 2).
-
Segment Bend Calculator
Angle per bend is the total angle divided by the bend count. Developed bend length is radius multiplied by the total angle in radians. Spacing interval count is one less than the number of bends. Equal mark spacing is developed length divided by that interval count, and the last mark is the first mark plus one spacing for each interval between bends.
-
Stub-Up Bend Calculator
For a standard 90-degree stub-up mark, the mark from the conduit end is the desired stub height minus the entered bender take-up.
Circuits And Components
-
24 VDC Control Voltage Drop Calculator
The 24 VDC loop uses twice the one-way length. Voltage drop equals current multiplied by round-trip length and entered resistance per 1000 ft, divided by 1000.
-
Capacitor Code Calculator
For a three-digit code, the first two digits are significant and the third digit is the power-of-ten multiplier in picofarads.
-
Capacitor Parallel Value Calculator
Parallel capacitances add directly.
-
Capacitor Series Value Calculator
The reciprocal of series equivalent capacitance equals the sum of the reciprocals of each capacitor.
-
Contactor Coil VA Calculator
Steady and inrush VA equal coil voltage multiplied by steady-state and inrush current, respectively.
-
Control Cable Shield Calculator
The shield loop uses twice the one-way length. Loop resistance scales with length, voltage drop is current times resistance, and power is current squared times resistance.
-
Control Circuit Fuse Calculator
Steady current equals control VA divided by control voltage; inrush reference applies an entered multiplier and both currents are compared with an entered fuse rating.
-
Control Panel Heat Load Calculator
Component heat is summed from entered losses, quantity, and duty. Total watts are converted to BTU/h and divided by an airflow heat-capacity approximation.
-
Control Relay Contact Load Calculator
Relay contact load equals entered contact voltage multiplied by entered contact current. Utilization compares that load with the entered contact VA rating.
-
Control Transformer VA Calculator
The preliminary VA basis compares continuous VA with margin against a combined sealed/inrush VA magnitude.
-
Current Divider Calculator
Parallel current divides in proportion to branch conductance. Each branch current equals total current times that branch conductance divided by total conductance.
-
Current Limiting Resistor Calculator
The resistor takes the difference between supply and load voltage. Divide that resistor voltage by target current to get ideal resistance.
-
Enclosure Heat Dissipation Calculator
Temperature rise equals internal watts multiplied by thermal resistance. Estimated internal temperature is ambient temperature plus the rise, and margin is the entered maximum minus that estimate.
-
Impedance Calculator
Net reactance equals inductive reactance minus capacitive reactance. Impedance magnitude is the square root of resistance squared plus net reactance squared, and phase angle is atan2(net reactance, resistance).
-
Impedance Magnitude Calculator
Impedance magnitude is the square root of resistance squared plus signed reactance squared. Phase angle uses atan2 of reactance and resistance.
-
Inductor Parallel Value Calculator
Parallel inductors are combined from the reciprocal of each participating inductance.
-
Inductor Series Value Calculator
Uncoupled inductances add in series.
-
4-20 mA Instrumentation Loop Power Calculator
Series resistance creates current-dependent voltage drop. The worst-case transmitter voltage is compared with the entered minimum compliance voltage at the entered maximum loop current.
-
LED Resistor Calculator
The resistor drops the supply voltage left after the series LED forward-voltage estimates, using Ohm's law.
-
LED Series Resistor Calculator
The resistor takes the remaining supply voltage after the series LED forward-voltage total.
-
Maximum Power Transfer Calculator
Maximum resistive DC load power occurs when load resistance equals source resistance.
-
Motor Control Circuit Calculator
Entered control loads are summed, spare percent is added, and the result is compared with an entered control transformer VA rating.
-
Parallel Circuit Calculator
Parallel conductance values add. Equivalent resistance is the reciprocal of total conductance, and each branch current is source voltage divided by branch resistance.
-
PLC I/O Load Calculator
Rail current is the sum of manufacturer-entered module currents. Field current is adjusted by entered simultaneous duty, then other 24 V loads and planning margin are added.
-
RC Filter Cutoff Calculator
The first-order RC cutoff frequency is the reciprocal of 2 pi times resistance times capacitance.
-
RC Time Constant Calculator
The RC time constant is resistance times capacitance. Charge and discharge target times use the ideal first-order exponential relationship.
-
Reactance Calculator
The mode calculates inductive and capacitive reactance and subtracts XC from XL.
-
Resistor Color Code Calculator
The first two color bands form a two-digit number, the multiplier band scales that number, and the tolerance band gives the nominal tolerance range.
-
Parallel Resistor Value Calculator
The reciprocal of equivalent resistance equals the sum of the reciprocals of the individual parallel resistance values.
-
Resistor Power Rating Calculator
Calculate electrical dissipation, divide by the entered allowable utilization, and compare with an optional selected rating.
-
Series Resistor Value Calculator
The equivalent resistance of fixed resistors in series is the sum of the individual resistance values.
-
RL Time Constant Calculator
The RL time constant is inductance divided by resistance.
-
RLC Resonance Calculator
Resonant frequency is set by inductance and capacitance. For a simple series RLC model, resistance also sets quality factor and bandwidth.
-
Sensor Resistor Calculator
The resistor receives the difference between supply voltage and target sensor voltage. Divide that difference by sensor current in amperes for resistance and multiply it by current for power.
-
Series Circuit Calculator
Series resistances add directly. Circuit current is source voltage divided by total resistance, and each voltage drop is current times that resistance.
-
Shunt Resistor Calculator
The meter voltage drop is meter current times meter resistance. The shunt carries target current minus meter current, so shunt resistance is meter voltage divided by shunt current.
-
Soft Starter Bypass Calculator
Running current is motor FLA times running-load percent. Service-factor reference current is motor FLA times service factor and is compared with the entered bypass rating.
-
Thevenin Equivalent Calculator
The connected load sees Vth through Rth. The load current is Vth divided by Rth plus RL, then voltage and power follow from that current.
-
Voltage Divider Calculator
Voltage divider output is source voltage times the bottom resistance divided by total resistance. A load is treated as parallel with the bottom resistor.
-
Voltage Drop Across Resistor Calculator
Resistor voltage drop equals current times resistance, and resistor power equals voltage drop times current.
-
Wheatstone Bridge Calculator
An ideal Wheatstone bridge is balanced when R1/R2 equals R3/R4. The selected unknown is solved from that ratio.
Voltage, Current And Resistance
-
AC Circuit Current Calculator
Line current equals real power divided by power factor, voltage, and the selected phase multiplier.
-
AC VA From Voltage And Current Calculator
Apparent power equals RMS voltage multiplied by RMS current.
-
AC Watts From Voltage And Current Calculator
Active power equals RMS voltage multiplied by RMS current and power factor.
-
Admittance Calculator
Admittance is the complex reciprocal of impedance and can be represented by conductance plus susceptance.
-
Conductance Calculator
Conductance is the reciprocal of resistance.
-
Current From Power And Voltage Calculator
Current equals power divided by voltage.
-
DC Power From Voltage And Current Calculator
DC power equals voltage multiplied by current.
-
Ohm's Law Calculator
Ohm law relates voltage, current, and resistance. Power is voltage multiplied by current.
-
Peak To RMS Voltage Calculator
For a sinusoidal waveform, RMS voltage equals peak voltage divided by square root of 2, and peak-to-peak voltage is twice the peak magnitude.
-
RMS Current Calculator
RMS current is derived from the selected waveform model. Sample mode uses the root mean square of equally spaced current samples.
-
RMS Voltage Calculator
RMS voltage is estimated from peak voltage and an entered waveform factor.
-
Voltage From Power And Current Calculator
Voltage equals power divided by current.
-
Watts Amps Volts Calculator
For single-phase, current is watts divided by voltage and power factor. For balanced three-phase, divide by voltage, power factor, and sqrt(3).
-
Watts Volts Amps Calculator
The mode converts real power to apparent power and current using entered power factor and phase model.
Power, Energy And Cost
-
AC Circuit Power Calculator
Apparent power uses RMS voltage, RMS current, and the selected phase multiplier. Real power equals apparent power times power-factor magnitude.
-
Annual Equipment Energy Calculator
Annual energy equals equipment watts times quantity, converted to kWh, multiplied by runtime and operating days. Annual cost applies the entered electricity rate.
-
Battery Energy Cost Calculator
Usable battery energy equals capacity times depth of discharge. Charging energy adds round-trip losses, then annual cost applies the entered rate.
-
Carbon Emissions from Electricity Calculator
Electricity emissions equal kWh multiplied by the entered emissions factor. The calculator also converts the result to short tons and metric tons.
-
Demand Charge Cost Calculator
Demand charge equals billing demand multiplied by the demand charge rate. The selected-period charge scales the monthly charge across the billed months.
-
Electricity Cost Calculator
Energy in kWh is watts divided by 1000, multiplied by runtime hours and days. Cost is kWh multiplied by the entered rate.
-
Energy Cost per Device Calculator
Per-device energy equals device watts multiplied by runtime and operating days. Total cost scales that energy by device count and the entered rate.
-
Energy From Power And Time Calculator
Energy in watt-hours equals power in watts multiplied by time in hours; divide by 1000 for kilowatt-hours.
-
Energy Intensity Calculator
Energy intensity equals annual kWh divided by floor area. The calculator also shows annual energy cost and cost per square foot.
-
Energy Savings Payback Calculator
Annual savings equal existing annual cost minus proposed annual cost. Simple payback divides project cost by annual cost savings.
-
Energy Use Calculator
Total energy equals watts per item times quantity, divided by 1000, then multiplied by runtime and days.
-
Generator Fuel Cost Calculator
Fuel cost equals burn rate multiplied by runtime and fuel price. Cost per hour equals burn rate multiplied by fuel price.
-
Load Factor Calculator
Load factor equals average demand divided by peak demand. Average demand equals period energy divided by period hours.
-
Monthly Electricity Bill Calculator
Energy charge equals monthly kWh multiplied by the energy rate. Demand charge equals billing demand multiplied by the demand rate. Taxes and fees apply to the subtotal.
-
Operating Cost Comparison Calculator
Each operating cost equals annual kWh multiplied by the entered rate plus fixed annual cost. The comparison shows annual savings and simple payback from the incremental project cost.
-
Peak Demand Calculator
Peak demand equals connected load multiplied by the diversity factor. Spare capacity and utilization compare that peak demand to service capacity.
-
Power Dissipation Calculator
Ideal DC or unity-power-factor real power is voltage times current, and energy is power times time.
-
Power Factor Calculator
Power factor is real power divided by apparent power. Reactive power uses the kW-kVA-kVAR triangle.
-
Power Factor Penalty Calculator
Current apparent power equals real power divided by current power factor. The penalty estimate multiplies the apparent-power shortfall by the entered rate and billed months.
-
Power From Energy And Time Calculator
Average power is energy divided by elapsed time, with watt-hours divided by hours producing watts.
-
Power Triangle Angle Calculator
Power factor equals real power divided by apparent power. The power-triangle angle is arccos(power factor), and reactive power is the remaining triangle leg.
-
Reactive Energy Calculator
Reactive energy equals real energy multiplied by the tangent of the phase angle that comes from the entered power factor. Apparent energy equals real energy divided by power factor.
-
Reactive Power Calculator
Reactive power is kW multiplied by tan(arccos(power factor)). The kVAR reduction is current kVAR minus target kVAR.
-
Solar Energy Cost Calculator
Lifetime total cost equals system cost plus annual O and M multiplied by lifetime. Levelized cost divides that lifetime total by lifetime energy.
-
Time of Use Electricity Cost Calculator
Period cost equals each period energy multiplied by its rate. The total bill adds the fixed charge and calculates the effective rate from total bill divided by total kWh.
Wire, Raceway And Ampacity
-
Ampacity Calculator
Adjusted ampacity is the user-supplied base ampacity multiplied by the explicit adjustment and temperature decimal factors. The total factor is the product expressed as a percentage.
-
AWG Wire Resistance Calculator
AWG diameter is estimated from the AWG geometric progression. Circular mil area is diameter in mils squared. Resistance per 1000 ft uses material K value divided by circular mil area and then applies the entered temperature factor.
-
Box Fill Calculator
The calculation sums entered volume allowances and compares the result with entered box volume.
-
Cable Bend Radius Calculator
Minimum bend radius equals cable outside diameter multiplied by the entered bend-radius multiplier. Bend arc length equals radius multiplied by bend angle in radians.
-
Cable Jacket Diameter Calculator
Cable outside diameter equals conductor diameter plus twice the entered concentric layer build; tolerance is applied to the nominal outside diameter.
-
Cable Pull Bend Count Calculator
Total bend angle is the sum of each entered bend angle multiplied by the bend count in that row.
-
Cable Tray Fill Calculator
The worksheet sums entered cable areas and compares occupied area with an entered tray-area limit.
-
Cable Tray Separation Calculator
Required tray width equals cable group count times group width plus separations between adjacent groups and edge clearance on both sides.
-
Cable Tray Width Calculator
Cable envelope width is increased by spacing allowance, divided by the usable width factor, then edge clearance is added on both sides.
-
Conductor Ampacity Correction Factor Calculator
The mode multiplies base ampacity by the two entered correction factors.
-
Conductor Current Density Calculator
Current density equals current divided by conductor cross-sectional area.
-
Conductor Resistance Calculator
Resistance equals resistivity multiplied by length and divided by cross-sectional area.
-
Conductor Resistance Temperature Calculator
Adjusted resistance equals base resistance times one plus temperature coefficient times temperature change.
-
Conductor Temperature Rise Calculator
Estimated temperature rise equals entered allowable rise multiplied by the square of load current divided by reference ampacity.
-
Conductor Weight Calculator
Verified unit weight is converted from pounds per 1,000 feet and multiplied by entered length, material quantity, and parallel runs.
-
Conduit Body Fill Calculator
Required area equals entered area per conductor times conductor count, plus any entered splice or device allowance. Fill percent compares required area against entered conduit body capacity.
-
Conduit Expansion Movement Calculator
The page applies a user-entered thermal expansion coefficient to the run length and temperature change, then compares total movement with an entered fitting movement range.
-
Conduit Fill Calculator
Total conductor area is conductor area multiplied by conductor count. Fill ratio is total conductor area divided by raceway internal area multiplied by 100. Remaining area is raceway internal area minus total conductor area. For three or more conductors, the 40% screening area limit is raceway area multiplied by 0.40, and the screening margin is that limit minus total conductor area.
-
Conduit Support Spacing Calculator
The run span after the entered end allowance is divided by the entered maximum support interval and rounded up.
-
Conduit Trade Size Calculator
Total conductor area is count multiplied by area per conductor. Conduit internal area is pi times radius squared. Fill is total conductor area divided by conduit area, and required inside diameter solves the entered fill limit.
-
DC Voltage Drop Calculator
The mode uses two times one-way length for a two-conductor DC path and applies Ohm law to entered resistance.
-
Electrical Duct Bank Concrete Volume Calculator
The gross duct-bank envelope is calculated from conduit count, outside diameter, clearances, and cover. The conduit cylindrical void volume is subtracted to estimate concrete quantity.
-
Equipment Grounding Conductor Size Calculator
The worksheet subtracts the entered required area from the selected conductor area.
-
Grounding Electrode Conductor Size Calculator
The calculation subtracts the entered required area from the selected conductor area.
-
Medium Voltage Cable Drop Calculator
Three-phase uses sqrt(3) and the one-way route per phase; single-phase uses 2 and twice the one-way length. Voltage drop equals that product times (R cos(phi) + X sin(phi)) per km, times the route, divided by 1000.
-
Parallel Conductor Calculator
Ideal current divides total load by parallel sets. The entered mismatch allowance increases the highest-set current before comparing it to entered ampacity.
-
Parallel Raceway Ampacity Calculator
Current per raceway equals total load current divided by parallel raceways. Total adjusted ampacity equals entered per-raceway ampacity times adjustment factor times raceway count.
-
Raceway Fill Area Calculator
Allowable fill area is raceway inside area times entered fill percent; available area subtracts reserved area.
-
Raceway Size Calculator
The calculation divides entered conductor area by the entered fill-limit fraction and compares the result with selected area.
-
Terminal Temperature Limit Check Calculator
Required ampacity equals noncontinuous current plus continuous current times the entered multiplier, then optional spare margin is applied.
-
Voltage Drop Calculator
Voltage drop equals phase multiplier times current times one-way length times effective impedance per 1000 ft, divided by 1000. Effective impedance follows NEC Table 9 Note 2 (R times PF plus X times sine of the PF angle); Table 8 resistance is corrected to operating temperature. Percentage drop divides that value by system voltage.
-
Voltage Drop Length Calculator
The mode solves the voltage-drop equation for maximum one-way length.
-
Wire and Cable Takeoff Calculator
Each run row adds route and allowance lengths, multiplies by conductor or cable quantity and parallel runs, and then applies the entered waste allowance.
-
Wire Derating Calculator
Multiply the two user-supplied decimal factors to get the combined factor, then multiply base ampacity by that combined factor. Conductor count is a review flag only; it does not choose the bundling factor. Four or more conductors return a review warning.
-
Wire Pull Length Calculator
Add the entered straight lengths and bend allowances for an early pull-length record.
-
Wire Pulling Tension Calculator
Total conductor weight equals conductor count times weight per 1000 ft times pull length divided by 1000. Estimated tension adds starting tension to total weight times friction coefficient, and sidewall pressure divides tension by bend radius in feet.
-
Wire Size Calculator | Voltage-Drop Review
Use the two-conductor loop length to estimate voltage drop, convert that drop to a percentage of system voltage, and calculate the resistance threshold that keeps the drop within the entered limit.
-
Wireway Fill Calculator
Occupied area is the sum of each entered conductor or cable area multiplied by its quantity. Fill percentage compares occupied area with verified internal area, and the entered limit is used only as a transparent comparison.
Residential Load And Service
-
Appliance Load Calculator
Each appliance row multiplies quantity by VA each, applies the entered demand factor and continuous multiplier, then converts the adjusted total to current.
-
Dryer Load Calculator
Connected dryer VA equals nameplate kW times 1000 times dryer count. Demand VA applies the entered demand factor before current conversion.
-
Dwelling Addition Load Calculator
addition connected load = lighting + receptacle + HVAC + appliance loads planned peak after addition = existing peak + addition connected load x coincidence percent / 100 service capacity margin = entered service capacity - planned peak after addition
-
Dwelling Detached Structure Load Calculator
Base detached-structure load is the sum of entered load groups. Planned load applies the spare percent, and margin subtracts planned load from entered feeder capacity.
-
Dwelling Garage Load Calculator
Connected garage load is the sum of entered garage load groups. Non-EV load excludes the EV allowance, capacity margin compares connected load with entered capacity, and EV share divides EV allowance by connected load.
-
Dwelling General Lighting Load Calculator
The area-based dwelling lighting line item equals floor area multiplied by the entered VA-per-square-foot basis. A verified override can be selected instead.
-
Dwelling Hot Tub Load Calculator
Connected hot tub load equals the sum of entered component loads. Planning demand applies the entered simultaneous factor and margin subtracts demand from entered capacity.
-
Dwelling HVAC Load Calculator
Auxiliary-heat current equals entered kW converted by voltage and phase. The preliminary HVAC load is the largest of entered cooling current, heating current, and auxiliary-heat current.
-
Dwelling Load Schedule Calculator
connected schedule load = general + fixed appliance + HVAC + EV + other loads demand schedule load = connected schedule load x entered demand percent / 100 entered capacity margin = entered capacity - demand schedule load
-
Dwelling Pool Equipment Load Calculator
Connected pool equipment load equals the sum of entered component loads. Planning demand applies the entered simultaneous factor and margin subtracts demand from entered capacity.
-
Dwelling Small Appliance Load Calculator
Connected small-appliance allowance equals circuit count times the entered VA allowance. Assessed allowance applies the entered demand factor.
-
Dwelling Water Heater Load Calculator
Power-basis current equals rated kW multiplied by 1000 and divided by entered voltage. The selected unit current is multiplied by quantity and the entered demand factor.
-
Electrical Panel Load Calculator
The calculator sums the three entered circuit currents, estimates apparent power from panel voltage and phase count, compares the equivalent connected-load current to the entered panel rating, and calculates any gap to the selected target reserve.
-
Electrical Service Size Calculator
Convert the entered real-power demand basis to apparent service VA using power factor, divide by voltage and the phase multiplier to estimate service current, divide by the utilization ratio to produce planning VA, and subtract apparent VA to show planning headroom.
-
EV Charger Load Calculator
EVSE current is multiplied by charger count and the entered continuous-load factor, then added to the entered existing load for a panel-capacity comparison.
-
Heat Pump Electrical Load Calculator
Equipment VA uses entered MCA, voltage, and phase. Auxiliary heat kW is converted to VA and added before converting the total load back to current.
-
Demand Factor Estimate (NEC 220 Context)
Add the fixed allowance to the factored first and remaining load blocks to estimate demand, subtract demand from connected load for the diversity allowance, and divide demand by connected load for the effective factor.
-
Optional Method Dwelling Load Calculator
The calculation sums each entered load multiplied by its entered demand factor.
-
Panel Capacity Calculator
The calculation adds entered loads, compares total load with entered rating, and applies an entered reserve target.
-
Range Demand Calculator
The mode applies an entered demand factor to additional range load while retaining the largest range load.
-
Residential Battery Load Calculator
Required battery energy equals essential kW times hours, divided by efficiency and multiplied by reserve. Runtime reverses the calculation using entered battery capacity and efficiency.
-
Residential Electrification Load Scenario Calculator
Incremental connected load is proposed connected load minus existing electric connected load for each row. Scenario peak is existing base peak plus the entered coincident peak contribution of each proposed row. Headroom is entered capacity minus scenario peak.
-
Residential EV Diversity Load Calculator
Connected EV load equals EVSE count times EVSE kW. Diversified EV load applies the entered diversity factor, then margin subtracts it from entered capacity.
-
Residential Generator Load Calculator
Required generator kW equals essential running load plus largest motor starting allowance, multiplied by the entered reserve factor. Required kVA divides required kW by entered power factor.
-
Residential Heat Pump Service Load Calculator
net added heat pump load = heat pump + auxiliary heat + outdoor unit - replaced electric heating load planned peak with heat pump = existing peak + net added heat pump load x coincidence percent / 100 service capacity margin = entered service capacity - planned peak with heat pump
-
Residential Load Calculator
Add the four entered load categories to get connected load, apply the user-supplied demand factor percentage to estimate demand, divide demand VA by service voltage to estimate current, and subtract demand from connected load to show the diversity allowance.
-
Residential Panel Phase Balance Calculator
Each 120 V row is assigned to L1 or L2. A line-to-line row contributes the entered current equally to both legs. The imbalance comparison uses the absolute leg difference over the larger leg, while the neutral-current comparison uses only the difference between linear 120 V rows.
-
Residential Service Headroom Calculator
Current service headroom = entered service capacity - existing peak; coincident added load = planned added load x coincidence percent / 100; headroom after added load = current service headroom - coincident added load.
-
Residential Well Pump Duty-Point Power Calculator
The page converts flow and total dynamic head into hydraulic power, then divides by entered pump and motor efficiency to estimate electrical input.
-
Residential Well Pump Electrical Load Calculator
The page uses entered voltage, running current, and phase to estimate apparent power, then applies entered power factor and motor efficiency.
-
Service Upgrade Calculator
Projected demand adds the new load to the entered calculated demand. Spare capacity is compared to the entered headroom target.
-
Subpanel Load Calculator
Connected VA is multiplied by the entered demand factor, converted to feeder current, then compared against entered subpanel rating and target spare capacity.
Commercial And Industrial Loads
-
Commercial Data Center Load Calculator
Rack IT load is scaled by utilization. PUE converts IT load to facility load, while UPS efficiency and power factor provide additional planning outputs.
-
Commercial Elevator Load Calculator
Motor output is divided by efficiency, then by power factor, and multiplied by duty factor. Current uses the selected phase multiplier and voltage.
-
Commercial Fan Load Calculator
Air power equals airflow multiplied by total pressure and a standard conversion constant. Shaft and electrical input power divide by the entered efficiencies.
-
Commercial Feeder Voltage Drop Calculator
Voltage drop scales the entered conductor resistance by one-way length and the selected phase path.
-
Commercial HVAC Load Calculator
The preliminary MCA estimate applies 125 percent to the entered largest motor FLA, adds other motor FLA and heater current, and compares the result only with an optional entered manufacturer MCA.
-
Commercial Kitchen Load Calculator
The factor-based kitchen demand is connected load multiplied by an entered factor. The selected preliminary demand is the greater of that result and the entered sum of the two largest equipment loads.
-
Commercial Lighting Demand Calculator
Sum connected VA, apply each row demand factor and continuous multiplier, then convert adjusted VA to line current.
-
Commercial Load Calculator
Each load block is multiplied by its entered demand factor and continuous multiplier. The adjusted total is converted to line current from the selected phase model and voltage.
-
Commercial Load Diversity Calculator
Connected block load is the sum of the four entered load blocks. Diversified load applies the entered diversity factor, and capacity margin compares the diversified load with entered capacity.
-
Commercial Neutral Diversity Calculator
The linear neutral estimate uses the three-phase vector-sum expression, then multiplies by the entered diversity percentage.
-
Commercial Office Load Calculator
Sum connected VA, apply each row demand factor and continuous multiplier, then convert adjusted VA to line current.
-
Commercial Panel Capacity Calculator
Panel apparent capacity equals panel rating times voltage and phase multiplier; connected load is compared directly with that capacity.
-
Commercial Phase Allocation Calculator
Phase allocation compares three entered VA values with their average and converts each phase load to current using entered voltage.
-
Commercial Pump Load Calculator
Hydraulic horsepower equals flow times specific weight times head divided by 3960. Shaft and electrical input power divide by the entered efficiencies.
-
Commercial Receptacle Demand Calculator
Sum connected VA, apply each row demand factor and continuous multiplier, then convert adjusted VA to line current.
-
Commercial Retail Load Calculator
Sum connected VA, apply each row demand factor and continuous multiplier, then convert adjusted VA to line current.
-
Commercial Tenant Load Calculator
Connected tenant load is the sum of entered load groups; entered-demand tenant load applies the reviewed tenant demand factor; capacity margin compares demand load with entered capacity.
-
Commercial Warehouse Load Calculator
Sum connected VA, apply each row demand factor and continuous multiplier, then convert adjusted VA to line current.
-
Continuous Load Calculator
The entered load current is split into continuous and noncontinuous portions. The continuous portion is multiplied by the entered factor before recombining.
-
Demand Factor Calculator
The mode multiplies connected load by an entered factor and adds an entered fixed allowance.
-
Feeder Load Calculator
Connected VA is multiplied by the entered demand factor. The entered continuous portion adds only the extra multiplier portion above 100 percent.
-
Industrial Branch Load Calculator
Adjusted branch load applies explicit demand and continuous multipliers to connected VA.
-
Industrial Connected Load Calculator
The page keeps industrial equipment rows visible, multiplies each connected kW by quantity, converts rows to kVA with entered power factor, and estimates current from voltage and phase.
-
Industrial Demand Load Calculator
The calculation totals process, motor, heating, and support loads, applies each entered demand factor, and compares coincident demand with entered capacity.
-
Industrial Feeder Capacity Calculator
Adjusted feeder load is connected VA times the explicit demand factor, converted to current and compared with capacity.
-
Lighting Load Calculator
Lighting VA equals entered area times entered VA per square foot. Demand and continuous multipliers are then applied before current conversion.
-
Neutral Load Calculator
Split-phase neutral current is the absolute difference between two line currents. Three-phase wye neutral current uses the vector-sum expression for 120-degree phase displacement.
-
Panel Schedule Calculator
Each circuit row is assigned to one, two, or three phases. The largest phase VA is converted to current and compared with the entered panel rating.
-
Receptacle Load Calculator
Connected receptacle VA equals count times entered VA per receptacle. Demand VA applies the entered demand factor, then current is converted from voltage and phase.
-
Three-Phase Load Balance Calculator
Average phase load is the total divided by three. Imbalance percent uses the largest absolute deviation from average divided by average.
Motors And Starters
-
Electrical Load Calculator
Scale load current by utilization, apply the single-phase or balanced three-phase line-voltage relationship to estimate apparent power, then use power factor to resolve real power and reactive-power magnitude.
-
Full-Load Current Estimate Calculator
Convert motor horsepower to mechanical watts, divide by efficiency to estimate input watts, divide by power factor to estimate apparent VA, then divide by voltage and the phase multiplier to estimate full-load current.
-
Locked Rotor Current Calculator
Locked-rotor current equals full-load current multiplied by the entered locked-rotor multiplier. If a starting-current reference is entered, the calculator also reports the margin and ratio.
-
Motor Branch Circuit Protection Calculator
The calculation multiplies entered motor FLA by an entered protection factor and compares the result with the selected rating.
-
Motor Circuit Conductor Size Calculator
The calculation multiplies entered motor FLA by an entered factor and compares the result with selected ampacity.
-
Motor Current Calculator
Convert horsepower to shaft watts, divide by efficiency to estimate electrical input watts, divide by power factor to estimate apparent VA, and divide by voltage and the phase multiplier to estimate running current.
-
Motor Current Unbalance Calculator
The page computes the mean of three entered phase currents, then expresses the largest absolute phase deviation as a percentage of the mean.
-
Motor Disconnect Size Calculator
Motor FLA is multiplied by the entered disconnect multiplier, then compared against an entered disconnect current rating.
-
Motor Efficiency Calculator
Motor efficiency is mechanical output power divided by electrical input power. Estimated loss is input power minus output power.
-
Motor Feeder Calculator
The calculation sums motor running currents and adds an entered factor of the largest motor.
-
Motor Load Percentage Calculator
The page converts measured input power into an estimated mechanical output with an entered efficiency, then compares output with rated motor output.
-
Motor Overload Calculator
Motor nameplate FLA is multiplied by the entered overload setting percent, then compared against an entered setting value.
-
Motor Power From Current Calculator
Multiply current by voltage and the phase multiplier to estimate apparent power, apply power factor for electrical input watts, then apply efficiency to estimate mechanical output power and horsepower.
-
Motor Slip Calculator
Slip rpm equals synchronous rpm minus measured rpm. Slip percent divides slip rpm by synchronous rpm.
-
Motor Slip Frequency Calculator
Slip frequency in hertz equals supply frequency multiplied by slip expressed as a decimal.
-
Motor Starter Current Reference Calculator
Multiply motor FLA by the user-entered overload reference percentage, starting-current multiplier, and starter continuous-current margin percentage to produce transparent preliminary current reference values.
-
Motor Starting Current Calculator
Starting current is full-load current multiplied by the entered starting multiplier. Voltage sag reference is line voltage multiplied by the entered sag percentage.
-
Motor Synchronous Speed Calculator
Synchronous speed in rpm equals 120 times frequency in hertz divided by the number of motor poles.
-
Motor Torque Calculator
Torque in lb-ft equals 5252 times horsepower divided by rpm. Torque in N-m is the converted result.
-
Motor Voltage Drop Calculator
Motor voltage drop is calculated twice: once with running current and once with starting current. Each drop uses phase multiplier, current, one-way length, and conductor resistance per 1000 ft.
-
NEMA Code Letter Calculator
Locked-rotor kVA per horsepower equals voltage times locked-rotor amps and phase multiplier, divided by 1000 and horsepower, then mapped to a code-letter range.
-
VFD DC Bus Voltage Calculator
The page applies an entered rectifier multiplier to the entered AC line voltage, then compares that expectation with measured DC bus and ripple readings.
-
VFD Dynamic Braking Resistor Calculator
The page converts a rotating-load speed change into kinetic energy, applies an entered braking fraction, then estimates peak, average, duty-adjusted power, and resistance at the entered DC bus voltage.
-
VFD Sizing Calculator
Motor FLA is multiplied by the entered application factor and divided by the entered derating factor before comparing against an entered VFD output rating.
-
VFD Volts-per-Hertz Calculator
The page calculates a base volts-per-hertz ratio from motor nameplate values, applies the target frequency and entered boost, and caps the reference at the entered maximum voltage.
Motors, Starters And VFD
-
Motor Acceleration Time Calculator
Acceleration time equals total inertia multiplied by the speed change in rad/s and divided by average net torque.
-
Motor Branch Voltage Drop Calculator
Motor branch voltage drop is calculated separately for running current and starting current using entered conductor resistance and the selected phase multiplier.
-
Motor Feeder Voltage Drop Calculator
Motor feeder voltage drop compares aggregate running current with a user-entered starting event that replaces one motor running current with its starting current.
-
Motor Horsepower From Torque Calculator
Mechanical horsepower equals torque times speed divided by 5252, then horsepower is converted to kilowatts.
-
Motor Multi-Speed Current Calculator
Multi-speed current rows convert entered horsepower, efficiency, and power factor to apparent power and current for each speed row.
-
Motor Reflected Inertia Calculator
Each load row contributes entered inertia or mass multiplied by radius squared. The total load inertia is reflected to the motor shaft with the speed ratio squared and then added to motor-side inertia.
-
Motor Service Factor Load Calculator
Service-factor load screening compares entered measured current with nameplate FLA and an entered service-factor current reference.
-
Motor Soft-Starter Current Calculator
Soft-starter current screening compares across-line starting current with the entered soft-starter current limit as a percent of FLA.
-
Motor Torque From Power Calculator
Torque equals 5252 times horsepower divided by speed, then lb-ft is converted to N-m.
-
Motor VFD Cable Length Calculator
The page compares the actual one-way VFD-to-motor cable length with a manufacturer-entered maximum length, then reports the remaining margin and percent of the stated limit used.
-
Motor Wye-Delta Current Calculator
Wye-delta current screening uses an ideal one-third wye-start current relationship from entered across-line starting current.
-
VFD Harmonic Current Calculator
Current THD is converted to harmonic RMS current, combined by quadrature with fundamental current, and multiplied by drive count for fleet context.
Power Quality And Transformers
-
Buck-Boost Transformer Calculator
Voltage change is target minus supply. Buck-boost winding kVA uses load current and the absolute voltage change, then applies the entered sizing multiplier.
-
Capacitor Bank Size Calculator
Required kVAR is the difference between current and target reactive power. Capacitance is estimated from kVAR, frequency, voltage squared, and the selected connection divisor.
-
Generator Size Calculator
Running rating applies the entered margin to running watts. Surge rating applies margin to running watts plus entered starting watts.
-
Harmonic Distortion Calculator
THD is the RMS sum of the selected harmonic components divided by the fundamental RMS value.
-
Power Factor Correction Calculator
Correction kVAR is the difference between current and target reactive power at the entered real power.
-
Power Quality Crest Factor Calculator
Crest factor equals absolute peak divided by true-RMS. When positive and negative peaks are both supplied, peak-to-peak is the sum of the positive peak and the absolute negative peak.
-
Transformer All-Day Efficiency Calculator
The page applies no-load loss for every entered hour, scales load loss by load fraction squared, and computes output energy from rated kVA, load fraction, power factor, and hours.
-
Transformer Bank Capacity Calculator
Total nameplate capacity equals unit count multiplied by unit kVA. Usable capacity applies the explicit utilization assumption.
-
Transformer Cooling Load Calculator
Entered transformer losses are adjusted by diversity and safety factors, then converted to BTU per hour, tons, and daily kWh.
-
Transformer Current Calculator
Current equals transformer VA divided by voltage and the selected single-phase or balanced three-phase multiplier.
-
Transformer Delta-Wye Voltage Calculator
Secondary line voltage equals primary line voltage divided by turns ratio. The secondary connection determines the line-to-phase conversion.
-
Transformer Efficiency Calculator
Transformer efficiency equals output power divided by input power, multiplied by 100.
-
Transformer Generator Coordination Calculator
Transformer kVA is scaled by expected loading, converted to kW by power factor, then compared with entered generator kVA and kW ratings.
-
Transformer Grounding Resistor Calculator
Resistor ohms equal voltage divided by target current; power and energy are calculated from voltage, current, and duration.
-
Transformer Harmonic Heating Calculator
THD is converted to harmonic RMS current. RMS current and a THD-squared weighted heating index are then calculated.
-
Transformer Impedance Calculator
Base current comes from transformer kVA, voltage, and phase. Percent impedance is converted to per-unit impedance and multiplied by base impedance.
-
Transformer Inrush Current Calculator
Rated current is transformer VA divided by voltage and phase multiplier. Estimated inrush current is rated current times the entered multiplier.
-
Transformer Inrush Duration Calculator
Duration cycles equal the entered time constant times the natural log of initial multiplier divided by target multiplier.
-
Transformer K-Factor Calculator
K-factor normalizes each harmonic current to a reference current and weights each contribution by harmonic order squared.
-
Transformer kVA Calculator
Single-phase kVA equals volts times amps divided by 1000. Balanced three-phase kVA multiplies volts and amps by sqrt(3) before dividing by 1000.
-
Transformer Losses Calculator
Total transformer loss equals core loss plus load loss. Input power equals output power plus total loss.
-
Transformer Percent Impedance Test Calculator
Percent impedance is reverse-calculated from impedance-test voltage on the rated test winding when the measured test current matches the rated-current basis.
-
Transformer Primary Current Calculator
Primary current equals transformer VA divided by primary voltage and the selected phase multiplier.
-
Transformer Regulation Calculator
Voltage regulation equals the no-load voltage minus full-load voltage, divided by full-load voltage, multiplied by 100.
-
Transformer Secondary Current Calculator
Secondary current equals transformer VA divided by secondary voltage and the selected phase multiplier.
-
Transformer Service Factor Calculator
Available capacity equals nameplate kVA multiplied by the entered service factor. Utilization and margin compare entered load kVA with that capacity.
-
Transformer Short Circuit Contribution Calculator
Rated current is transformer VA divided by voltage and phase multiplier. Approximate fault current is rated current divided by per-unit impedance.
-
Transformer Tap Voltage Calculator
The no-load secondary estimate scales rated secondary voltage by the measured-to-rated primary ratio, then applies the entered signed tap correction.
-
Transformer UPS Capacity Calculator
UPS load kW is divided by power factor to get kVA, then reserve is added and compared with entered transformer kVA.
-
Transformer Voltage Drop Calculator
Transformer voltage regulation is estimated as load fraction times resistance percent times power factor plus or minus reactance percent times the sine of the load angle.
-
Transformer Voltage Ratio Calculator
Voltage ratio equals primary voltage divided by secondary voltage.
-
Voltage Sag Calculator
Source impedance is estimated from voltage, phase multiplier, and available fault current. Sag voltage is load-current step times source impedance and phase multiplier; sag percent divides sag voltage by system voltage.
Lighting And Illumination
-
Daylight Factor Calculator
Daylight factor equals measured indoor illuminance divided by measured outdoor illuminance; the percentage is the ratio multiplied by 100.
-
Dimming Energy Savings Calculator
Dimming savings compare baseline annual kWh with the same schedule at the entered average dimmed power percentage.
-
Emergency Lighting Battery Calculator
Load energy equals watts times runtime. Required battery Wh divides load energy by usable capacity and efficiency, then applies the reserve adder.
-
Emergency Lighting Duration Calculator
Estimated duration equals usable battery energy multiplied by efficiency and the non-reserved fraction, divided by emergency load.
-
Exit Sign Load Calculator
Total exit-sign load equals watts per sign multiplied by sign count; optional emergency energy equals total load multiplied by duration.
-
Fixture Count Calculator
Effective lumens per fixture equal lumens times utilization times light-loss factor; fixture count rounds the target area result up.
-
Fixture Spacing Calculator
Maximum spacing equals mounting height times spacing criterion; fixture rows and columns are ceiling counts of room dimensions divided by spacing.
-
Footcandle Calculator
Footcandles equal lumens times coefficient of utilization and light loss factor, divided by area.
-
LED Driver Load Calculator
Total watts equals driver watts times quantity. Total VA divides watts by power factor, then the entered continuous multiplier is applied before current conversion.
-
LED Retrofit Payback Calculator
LED retrofit payback compares existing and LED annual energy under the same schedule and divides project cost by annual energy-cost savings.
-
Light Loss Factor Calculator
Maintained lumens are initial lumens multiplied by the product of the entered light-loss factors.
-
Lighting Circuit Load Calculator
Fixture watts are multiplied by fixture count and the entered continuous factor before current and entered-breaker comparisons.
-
Lighting Circuit Voltage Drop Calculator
Lighting circuit voltage drop applies the selected phase multiplier to current and entered one-way conductor resistance.
-
Lighting Controls Savings Calculator
Annual energy equals watts multiplied by hours per day and days per year, divided by 1000; savings are baseline minus controlled energy.
-
Lighting Energy Savings Calculator
Annual energy equals fixture watts times fixture count times hours per day times operating days, divided by 1000.
-
Lighting Layout Calculator
Spacing limit equals mounting height times spacing criterion. Rows and columns are ceiling counts of room dimensions divided by that limit.
-
Lighting Power Density Calculator
Lighting power density equals connected lighting watts divided by served floor area.
-
Lighting Uniformity Calculator
Lighting uniformity ratios compare entered minimum, average, and maximum illuminance readings.
-
Lumen Calculator
Required lumens equal target footcandles times room area, divided by coefficient of utilization and light loss factor.
-
Mounting Height Calculator
Mounting height above workplane subtracts workplane height from luminaire mounting height. Maximum spacing multiplies that height by the entered spacing-to-mounting-height ratio, and row count rounds room length divided by spacing up.
-
Occupancy Sensor Savings Calculator
Annual energy equals lighting watts multiplied by daily hours and operating days, divided by 1000; savings are baseline hours minus reduced hours applied to the same load.
-
Photocell Load Calculator
Total load equals connected watts per unit multiplied by count; annual energy equals total watts multiplied by duty hours and operating days, divided by 1000.
-
Room Footcandles Calculator
Effective lumens equal total lumens times utilization and light-loss factors; footcandles divide effective lumens by square feet.
-
Task Lighting Load Calculator
Task lighting load scales connected watts by active-use percent and annual schedule before applying the energy rate.
Solar PV Design
-
Microinverter Count Calculator
Microinverter count is the module count divided by inputs per unit and rounded up. AC and DC totals use entered equipment watts, and branch groups divide entered AC watts by the entered branch limit.
-
PV Array Azimuth Calculator
The screen uses the shortest circular difference between the array and reference azimuth and applies a cosine factor to the entered baseline.
-
PV Array Tilt Calculator
The screen compares array tilt with the absolute latitude reference and applies a cosine factor to the entered baseline energy.
-
Solar Panel Size Calculator
Required PV watts equal daily energy divided by peak sun hours and the retained production factor after system losses.
Solar PV Electrical
-
Charge Controller Size Calculator
Charge-controller current equals PV array watts divided by battery voltage, then multiplied by the entered margin factor.
-
PV String Current Calculator
A series string retains the selected module current. Parallel strings multiply that current. The entered adjustment factor is then applied before comparison with the entered review limit.
-
PV String Voltage Calculator
Cold module Voc applies the entered percent-per-C coefficient to the difference between minimum and reference temperature. String voltage multiplies per-module voltage by modules in series.
-
Solar AC Voltage Rise Calculator
Three-phase uses sqrt(3) and the one-way run length per phase; single-phase uses 2 and twice the one-way length for the loop. Rise equals that product times the resistance basis per 1000 ft, divided by 1000.
-
Solar Cable Voltage Drop Calculator
Voltage drop equals current times circuit resistance. Circuit resistance equals entered resistance per 1000 ft times the circuit length basis divided by 1000.
-
Solar String Calculator
Cold Voc adjusts module Voc by the entered temperature coefficient and temperature delta. String limits compare cold Voc and Vmp with entered inverter and MPPT voltage windows.
Solar PV Energy
-
PV Array Energy Calculator
Annual energy equals PV DC nameplate capacity multiplied by the entered net site-specific yield. Monthly and daily outputs are averages.
-
Solar Export Energy Calculator
Solar generation is allocated to direct site use, then the entered battery charge, and remaining energy is treated as export.
-
Solar Self-Consumption Calculator
Each time interval serves load with PV first, then applies entered battery flows, and allocates remaining energy to grid import or export.
Solar And Backup Power
-
Backup Generator Sizing Calculator
The calculation sums backup loads, adds an entered starting contribution, applies reserve, and converts surge kW to kVA using the entered power factor.
-
Backup Load Priority Calculator
Priority load equals critical plus essential load. Available capacity subtracts the entered reserve from backup capacity, then optional support is limited by the priority margin.
-
Battery Bank Series Parallel Calculator
Series count multiplies voltage. Parallel-string count multiplies amp-hour capacity. Nominal energy equals bank voltage times bank capacity.
-
Battery Capacity Calculator
Required battery Wh equals load watts times runtime, divided by usable depth-of-discharge factor and efficiency factor.
-
Battery Charge Time Calculator
Available amp-hours equal capacity times the unfilled state-of-charge fraction. Estimated time equals available amp-hours divided by effective charging current.
-
Battery Discharge Current Calculator
Battery discharge current equals load watts divided by efficiency and then divided by battery voltage.
-
Battery Runtime Calculator
Runtime equals usable battery Wh divided by load watts. Usable Wh equals Ah times volts times depth-of-discharge and efficiency factors.
-
Generator Fuel Runtime Calculator
Average generator load is rating multiplied by average load percent. Fuel burn is load kW multiplied by the entered fuel rate, and runtime is usable fuel divided by fuel burn.
-
Generator Transfer Load Calculator
Effective generator capacity applies the entered usable-capacity factor. Available capacity subtracts reserve, then transfer margin compares available capacity with the entered transfer load.
-
Inverter Size Calculator
Continuous and surge ratings apply the entered margin to their respective load values. VA divides the continuous rating by power factor, and estimated DC input divides by the efficiency factor.
-
Residential Sump Pump Backup Runtime Calculator
The page reduces battery energy by usable fraction, inverter efficiency, and reserve, then divides it by the pump running power averaged over the entered duty cycle.
-
Solar Battery Size Calculator
Autonomy energy equals daily kWh times days. Required battery kWh divides that load energy by depth-of-discharge and efficiency factors, then applies the reserve adder.
Battery, Generator And Backup Power
-
Generator Load Bank Calculator
Target apparent load is generator kVA times the target percent. Target real power is that times the power factor, and line current is target kW divided by voltage and the phase factor. Bank steps are the per-phase real power divided by the step size, rounded up.
-
Inverter Efficiency Calculator
Inverter efficiency equals AC output power divided by DC input power; loss is input minus output.
-
Off Grid Load Calculator
Daily off-grid energy equals average load times daily hours; autonomy energy scales by days of autonomy.
-
Solar Battery Runtime Calculator
Nominal energy equals Ah times voltage; usable energy applies depth-of-discharge and efficiency factors; runtime divides by load.
-
UPS Battery Size Calculator
UPS battery energy equals load watts times runtime divided by efficiency and usable-capacity factors.
-
UPS Runtime Calculator
UPS runtime equals available battery watt-hours divided by load watts after efficiency and reserve adjustments.
EV Charging And Electrical Infrastructure
-
EV Charger Circuit Size Calculator
Required ampacity is entered EVSE current multiplied by the entered continuous-load factor. VA values convert current to apparent load using voltage and phase.
-
EV Charging Time Calculator
Battery energy added equals battery capacity times the SOC window. Grid energy divides by charging efficiency, and time divides grid energy by charger kW.
-
EV Solar Charging Calculator
Allocated solar energy equals available solar kWh times allocation percent. Delivered EV energy applies charging efficiency, estimated miles multiply by vehicle efficiency, and remaining grid energy is the target minus delivered energy floor at zero.
-
Residential EV Circuit Sharing Capacity Calculator
The EV current is limited by the entered EVSE cap and the entered shared-circuit limit. Under mutual exclusion, the EVSE receives no current while the appliance is active. Under current sharing, the available current is the shared limit minus the appliance current.
-
Residential EV Daily Energy and Charger Power Calculator
Driving energy equals daily miles divided by vehicle efficiency. Wall energy adjusts for charging efficiency, and average required power divides wall energy by the available charging window.
-
Residential EV Group Power Sharing Calculator
The group cap is allocated using the selected explicit policy. Equal share assigns each port the lesser of its request and an equal share of the group cap. Priority share assigns remaining capacity in ascending priority order.
Estimating And Material Planning
-
Cable Pulling Lubricant Quantity Calculator
The page approximates cable surface area from circumference and route length, multiplies by cable and pull counts, and divides by the selected product coverage rate.
-
Cable Reel Capacity Calculator
The page treats the wound region as an annulus volume, multiplies by traverse width and packing factor, and divides by cable cross-sectional area.
-
Cable Tray Material Takeoff Calculator
Each tray route is rounded up to stock section lengths. Entered fittings, splice joints, covers, partitions, and supports are aggregated, while the entered waste allowance applies to straight sections and length-based accessories.
Testing, Protection And Grounding
-
Approach Boundary Worksheet Calculator
The calculation converts recorded distances to inches and compares them without deriving a new boundary.
-
Arc Flash Boundary Calculator
The calculation subtracts the entered reference distance from the entered comparison distance.
-
Arc Flash Input Data Completeness Calculator
The calculation counts input rows by availability and flags missing rows marked critical.
-
Arc Flash Study Scenario Comparison Calculator
The calculation compares absolute and relative differences between two recorded values after their basis and source fields match.
-
Available Fault Current Calculator
Full-load current divides transformer VA by voltage and phase multiplier. Transformer-limited fault current divides full-load current by impedance per unit. Adjusted available fault current applies the entered source multiplier.
-
Breaker Interrupting Rating Calculator
Rating margin subtracts available fault current from the entered rating. Utilization percent divides available fault current by the entered rating.
-
Breaker Size Calculator
The worksheet adds noncontinuous load to factored continuous load and compares the adjusted load with the selected rating.
-
Circuit Identification Calculator
The worksheet averages A-B, B-C, and C-A readings, finds the largest nominal deviation, and compares it with the entered tolerance.
-
Conductor Short-Circuit Withstand Calculator
Estimated withstand time equals (K times conductor area)^2 divided by fault current squared. I-squared-t equals fault current squared times clearing time.
-
Continuity Test Calculator
Corrected resistance equals measured resistance minus lead resistance. The result is compared with the user-entered threshold.
-
CT Ratio Test Calculator
Expected ratio comes from the selected CT nameplate values. Measured ratio and deviation come from the entered test currents.
-
Data Logger Interval Calculator
Expected points include the first reading plus each full logging interval in the entered duration.
-
Earth Electrode Test Calculator
The calculator summarizes measured resistance readings and optionally calculates resistance from test voltage divided by test current.
-
Electrical Inspection Checklist Calculator
The worksheet counts row states, calculates completion as pass plus not-applicable rows, and flags required failures.
-
Electrical Safe Work Distance Calculator
The mode converts recorded distances to inches and compares them without deriving a new work boundary.
-
Enclosure IP Rating Screen Calculator
The screen compares the entered dust and water digits independently with entered minimum digits.
-
Equipment Short Circuit Rating Calculator
Rating margin subtracts available fault current from the entered rating. Utilization percent divides available fault current by the entered rating.
-
Extension Cord Voltage Drop Calculator
The mode doubles one-way length, applies conductor resistance, calculates voltage drop, and compares entered limits.
-
Fault Loop Impedance Calculator
Measured loop impedance equals test voltage divided by measured fault current.
-
Fuse Coordination Screen Calculator
Required upstream clearing time is downstream clearing time multiplied by one plus the entered margin.
-
Fuse Size Calculator
The calculation multiplies entered load current by an entered factor and compares the result with the selected rating.
-
Generator Backfeed Safety Calculator
The worksheet counts control states and divides present controls by total controls.
-
GFCI Trip Time Calculator
Trip-time margin equals entered reference limit minus measured trip time. Percent of limit divides measured time by the entered reference limit.
-
Ground Fault Current Calculator
Prospective fault current equals fault voltage divided by loop impedance.
-
Ground Grid Resistance Calculator
The calculation uses a transparent area-based resistance approximation and a user-entered parallel-path factor.
-
Ground Rod Spacing Calculator
The mode compares entered electrode spacing with entered rod length and target spacing.
-
Grounding Bond Test Calculator
Loop resistance equals measured voltage drop divided by test current; corrected bond resistance subtracts entered lead resistance.
-
Grounding Conductor Continuity Calculator
Corrected conductor resistance equals measured resistance less lead resistance.
-
Grounding Resistance Calculator
A simplified driven-rod approximation estimates single-rod resistance from soil resistivity, rod length, and diameter. Combined resistance is reduced by a capped spacing-effectiveness factor.
-
Instrument Transformer Burden Calculator
Resistive burden voltage equals current times resistance; VA equals current squared times resistance.
-
Polarization Index Calculator
Polarization index is the 10-minute insulation resistance divided by the 1-minute insulation resistance.
-
Insulation Resistance Calculator
Corrected resistance is the measured resistance multiplied by the user-supplied temperature correction factor, then compared to the entered screening reference for worksheet context only.
-
Insulation Test Duration Calculator
Duration completion equals actual duration divided by entered target duration.
-
Insulation Test Trend Calculator
Resistance ratio equals ending resistance divided by starting resistance; percent change divides the difference by starting resistance.
-
Insulation Test Voltage Calculator
The entered test voltage is compared with equipment rated voltage and a user-entered voltage window.
-
Leakage Current Screen Calculator
The calculator compares measured leakage current with an entered reference and optionally expresses it as a share of load current.
-
Limited Approach Boundary Calculator
The limited mode converts recorded distances to inches and compares them as a mode of the approach worksheet.
-
Lockout Tagout Sequence Calculator
The worksheet counts step states, checks order against row position, and identifies repeated energy-source identifiers.
-
Measurement Uncertainty Calculator
Combined uncertainty is the root-sum-square of three entered independent components.
-
Megohm Test Trend Calculator
Change equals latest megohm reading minus previous reading; percent change divides by the previous reading.
-
Meter Burden Voltage Calculator
Burden voltage equals current times input resistance; resistive burden power equals current squared times resistance.
-
Motor Winding Resistance Imbalance Calculator
Resistance imbalance equals the maximum absolute deviation from the three-phase average divided by that average.
-
Oscilloscope Bandwidth Calculator
Required bandwidth equals signal frequency times the entered bandwidth multiplier.
-
Oscilloscope Timebase Calculator
The oscilloscope time window is time per division times divisions; frequency is cycles divided by the time window.
-
Phase Sequence Check Calculator
The screen normalizes phase angles relative to A, infers order from relative B/C angles, and measures deviation from 120/240 degree spacing.
-
Polarity Test Calculator
Signed polarity math uses the sign and absolute magnitude of the entered measured voltage.
-
Power Analyzer Sampling Calculator
Nyquist screening rate is twice the entered highest harmonic frequency, where highest frequency equals fundamental frequency times harmonic order.
-
PPE Category Screen Calculator
The worksheet subtracts entered incident energy from entered arc rating after the shared basis and source record are present.
-
Protective Device Clearing Time Calculator
Clearing-time margin equals entered limit minus measured clearing time. The ratio divides measured time by the entered limit.
-
Protective Relay Pickup Calculator
Primary pickup current equals secondary pickup setting times CT primary divided by CT secondary. Margin subtracts primary pickup from available fault current.
-
Protective Relay Time Calculator
Current multiple divides fault current by pickup current. Operating time uses entered curve constants and time dial. Margin subtracts calculated time from the entered operating-time limit.
-
PT Ratio Calculator
Measured ratio equals primary voltage divided by secondary voltage; ratio error is measured minus nominal divided by nominal.
-
Pull Box Sizing Calculator
The straight-pull reference uses eight times the largest raceway. The angle-pull reference uses six times the largest raceway plus the same-wall raceway sum, then the selected pull type controls the recommended screening length.
-
Resistance Measurement Error Calculator
Resistance error equals measured minus reference, with percentage error normalized to the reference.
-
Restricted Approach Boundary Calculator
Recorded restricted-boundary distances are converted to inches before the entered project distance is compared with the reference distance.
-
SCCR Calculator
The calculation compares entered available fault current with entered component SCCR.
-
Shock Risk Screen Calculator
Entered shock-review factor rows are counted by state, and recorded rows are divided by total rows to report completeness.
-
Short-Circuit Current Calculator
Available fault current is source voltage divided by total impedance when both are entered on the same equivalent-circuit basis. The adjusted value multiplies that current by the entered screening multiplier.
-
Step And Touch Voltage Screen Calculator
Grid potential rise is fault current times grid resistance; step and touch screens apply entered fractions and compare with entered limits.
-
Test Lead Correction Calculator
Corrected resistance equals the measured reading minus entered lead resistance, then compares to an entered reference.
-
Thermal Scan Temperature Difference Calculator
Temperature rise equals component temperature minus ambient; delta against reference equals component temperature minus reference temperature.
-
Touch Voltage Safety Screen Calculator
Touch voltage equals entered fault current multiplied by grid resistance and touch fraction.
-
Transformer Turns-Ratio Test Calculator
The expected and measured ratios are calculated from their respective primary and secondary voltage pairs.
-
Transformer Winding Resistance Temperature Calculator
Measured resistance is adjusted to the reference temperature using the entered linear temperature coefficient.
-
Voltage Presence Check Calculator
Absolute measured voltage is compared with an entered display threshold and nominal voltage.
-
Three-Phase Voltage Unbalance Calculator
Voltage unbalance equals the maximum absolute deviation from the three-reading average divided by that average.